| Plan Review Stops For Permit 06060507 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2006-06-28 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-06-28 |
Time |
11:32 |
Rev Time |
0.25 |
| Received By |
alange |
Date |
2006-06-28 |
Time |
11:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2006-07-23 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-07-23 |
Time |
09:51 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-07-23 |
Time |
09:23 |
Sent To |
P |
|
| Notes |
| 2006-07-23 00:00:00 | ** REDLINED THE FOLLOWING. | | | | | | MISSING "EQUIPMENT GROUNDING CONDUCTOR" | | | AFTER THE FIRST MEANS OF DISCONNECT AND | | | FROM GEN TO ATS. | | | 250.24B,250.110,250.122 ETC. | | | | | | SIGNAGE REQUIRED FOR NEW SERVICE RATED | | | MAIN AND GEN DISCONNECT. | | | 230.2E, 702.8 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2006-07-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-07-15 |
Time |
12:25 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-07-15 |
Time |
12:05 |
Sent To |
P |
|
| Notes |
| 2006-07-15 00:00:00 | ******* UNSAT 2ND REVIEW ******* | | | | | | 1) NOTE: PLEASE SEE STILL MISSING | | | DISCONNECT FOR FEEDERS COMING FROM GEN | | | REQUIRED AT HOUSE AND GROUPED WITH THE | | | NEW SE RATED ATS WITH MAIN. | | | PLEASE KNOW, THE ATS AS SHOWN ONLY | | | DISCONECTS POWER FROM THE LINE/FPL SIDE | | | AND DEOS NOT DISCONNECT POWWER FROM THE | | | GEN FEEDERS. | | | PLEASE KNOW THE BRKR ON GEN IS NOT | | | ACCEPTABLE FOR THIS. | | | 225.31-225.39, 110.27ETC. | | | PLEASE KNOW, THIS DISCONNECT DOES NOT | | | REQUIRE OCP AND IS ONLY REQUIRED TO BE A | | | MEANS OF DISCONNECT, RATED FOR THE LOAD | | | SERVED,GROUPED AND RATED AS SERVICE | | | EQUIPMENT.( NOT SE RATED) | | | PLEASE KNOW, AS THE EXISTING MCB SEEMS | | | TO BE LOCATED INSIDE AND IS NOT GROUPED | | | WITH NEW ATS W/MAIN. | | | | | | 2) NOTE: PLEASE SEE THAT A SLAB DETAIL | | | IS REQUIRED AND INDICATING HOW THIS UNIT | | | WILL BE ATTACHED TO SLAB. | | | NOTES WERE PLACED ON THE SURVEY ON THE | | | NEW 8" SLAB, HOWEVER THE SLAB DETAIL IS | | | REQUIRED AND HOW THIS UNIT WILL BE | | | ATTACHED, ISOLATION PADS ETC? | | | | | | | | | 3) NOTE: PLEASE KNOW, ALL NEUTRALS AND | | | EQUIPMENT GROUNDSWILL BE REQUIRED TO | | | BE SEPARATED IN THE EXISTING PANEL. | | | 250.6,250.24B. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-06-23 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-06-23 |
Time |
13:45 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-06-23 |
Time |
13:42 |
Sent To |
M |
|
| Notes |
| 2006-06-23 00:00:00 | ********** UNSAT *********** | | | | | | 1) NOTE: PLEASE SEE THAT THE SURVEY WITH | | | "PEN" WRITTEN ON PLANS SHALL BE COPIED | | | IN TWO SETS. AS PEN AND PENCIL PLANS ARE | | | NOT PERMITTED UNLESS COPIED. | | | 106.2.1 | | | THESE SITE SURVEY PLANS WHICH ALREADY | | | STMAPED FROM ZONGIN WILL BERE-STAMPED. | | | | | | 2) NOTE: PLEASE SEE THAT CONDUIT FROM | | | METER TO GUTTER SHALL BE REQUIRED TO BE | | | REMOVED. | | | | | | 3) NOTE: PLEASE SEE 250.24B,250.6 AS AN | | | "EQUIPMENT GROUNDING CONDUCTOR" IS NOT | | | INSTALLED FROM METER TO THE FIRST MEANS | | | OF DISCONNECT. | | | | | | 4) NOTE: PLEASE SEE NO SPEC/MANUFACTURE | | | SHEETS WERE SUBMITTED FOR THE ATS. | | | PLEASE KNOW, AS SHOWN ON RISER THIS ATS | | | SHALL BE SERVICE ENTRANCE RATED WITH A | | | MANUAL MEANS OF DISCONNECT RATED FOR THE | | | LOAD SERVED TO DISCONNECT POWER FROM | | | FPL. | | | 230.70,230.2,230.72,230.76,230.79 | | | PLEASE ALSO SEE MISSING DISC RATED FOR | | | THE LOAD SERVED FOR THE FEEDERS FROM | | | GEN 225.31-225.39 | | | | | | 5) NOTE: PLEASE SEE BUILDING REVIEW | | | COMMENTS AS NO SLAB DETAIL WAS | | | SUBMITTED. | | | | | | 6) NOTE: PLEASE BE SURE THE ELECTRICAL | | | CONT/PERSON RESPONSIBLE FOR PLANS AND | | | DESIGN SHALL PRINT AND SIGN NAMES ON | | | PLANS. | | | 106.2.1 FBC ADMIN SEC. | | | | | | 7) NOTE: PLEASE BE SURE ALL SPECS ARE | | | HIGHLIGHTED FOR MODELS BEING INSTALLED | | | PLEASE SEE THAT MANUFACTURES SHEETS | | | SHALL CLEARLY INDICAT ETH MIN CLEARENCES | | | REQUIRED FOR EQUIPMENT. | | | 110.3, 215.5 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
FUEL |
DIESEL GENERATOR |
| Rev No |
1 |
Status |
N |
Date |
2006-07-17 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-07-17 |
Time |
09:37 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-07-17 |
Time |
09:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2006-07-26 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-07-26 |
Time |
07:11 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-07-26 |
Time |
07:11 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2006-07-17 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-07-17 |
Time |
09:38 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-07-17 |
Time |
09:38 |
Sent To |
|
|
| Notes |
| 2006-07-17 00:00:00 | DENIED; | | | 1. SHOW LOCATION OF REGULATORS AND | | | SHUTOFF VALVES. | | | 2.NEED SPEC. SHEETS FOR REGULATORS THAT | | | WILL BE USED. CHECK RANGE OF REGULATORS | | | NOT ALL REGS. WILL ALLOW 750,000 BTU'S. | | | TO PASS. | | | GAS PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2006-07-31 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-07-31 |
Time |
11:58 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-07-31 |
Time |
11:58 |
Sent To |
E |
|
| Notes |
| 2006-07-31 00:00:00 | TO "ALANGE" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2006-07-22 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-07-22 |
Time |
17:13 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-07-22 |
Time |
17:13 |
Sent To |
E |
|
| Notes |
| 2006-07-22 00:00:00 | TO "DPALMER" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-07-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-07-13 |
Time |
15:42 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-07-13 |
Time |
15:42 |
Sent To |
E |
|
| Notes |
| 2006-07-13 00:00:00 | TO "DPALMER" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-06-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-06-19 |
Time |
10:48 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-06-19 |
Time |
10:48 |
Sent To |
E |
|
| Notes |
| 2006-06-19 00:00:00 | TO "GEN-RES" "E" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-06-28 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-06-28 |
Time |
11:32 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2006-06-14 |
Time |
10:39 |
Sent To |
|
|
| Notes |
| 2006-06-14 00:00:00 | TO "Z" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2006-06-26 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-06-26 |
Time |
14:50 |
Rev Time |
0.15 |
| Received By |
tgordon |
Date |
2006-06-26 |
Time |
14:50 |
Sent To |
B |
|
| Notes |
| 2006-06-26 00:00:00 | *** PROVISO *** | | | 1) PER 2004 FBC, FUEL GAS - POWERED | | | EQUIPMENT - PERMANENTLY INSTALLED | | | EQUIPMENT POWERED BY INTERNAL COMBUSTION | | | ENGINES SHALL BE INSTALLED IN ACCORDANCE | | | WITH MANUFACTURE'S INSTALLATION | | | INSTRUCTIONS AND NFPA 37. | | | | | | NFPA 37 INSTALLATION & USE OF STATIONARY | | | COMBUSTION ENGINES & GAS TURBINES: | | | 4.1.4ENGINES (GENERATORS) LOCATED | | | OUTDOORS SHALL BE MINIMUM OF 5 FT FROM | | | OPENINGS IN WALLS & AT LEAST 5 FT FROM | | | STRUCTURES HAVING COMBUSTIBLE WALLS.A | | | MINIMUM CLEARANCE IS NOT REQUIRED WHEN | | | (1) THE ADJACENT WALL HAS A MINIMUM FIRE | | | RESISTANCE RATING OF 1 HOUR OR (2) THE | | | WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF | | | NON-COMBUSTIBLE MATERIALS, AND IT HAS | | | BEEN DEMONSTRATED THAT A FIRE WITHIN THE | | | ENCLOSURE WILL NOT IGNITE COMBUSTIBLE | | | MATERIALS OUTSIDE THE ENCLOSURE. | | | INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS | | | SHOULD NOT TERMINATE UNDER STRUCTURES OR | | | WHERE THE EXHAUST MIGHT BE DRAWN INTO | | | THE VENTILATION INTAKES. | | | | | | 2004 FMC 804.3.5 #3, WHERE THE | | | TERMINATION IS LOCATED BELOW AN ADJACENT | | | ROOF STRUCTURE, THE TERMINATION POINT | | | SHALL BE LOCATED AT LEAST 3 FT FROM THE | | | ROOF STRUCTURE. | | | | | | PLEASE NOTE, WHILE ZONING ALLOWS | | | MECHANICAL EQUIPMENT TO ENCROACH 4 FT | | | INTO THE REQUIRED SETBACK, GENERATORS | | | SHALL MAINTAIN THE REQUIRED ABOVE | | | MENTIONED CLEARANCES TO THE ADJACENT | | | PROPERTY STRUCTURES, I.E. FENCE, | | | BUILDING, WINDOWS, DOORS, OR OPENINGS. | | | | | | PROVIDE MANUFACTURE'S INSTALLATION | | | INSTRUCTIONS AT THE JOBSITE FOR THE | | | FIELD INSPECTOR. | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2006-07-17 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-07-17 |
Time |
09:37 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-07-17 |
Time |
09:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2006-07-28 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-07-28 |
Time |
08:14 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-07-28 |
Time |
08:14 |
Sent To |
I |
|
| Notes |
| 2006-07-28 00:00:00 | RESTAMP OF PLANS. | | | THE PROPOSED GENERATOR SHALL NOT BE | | | CLOSER THAN 6FT FROMSIDE PROPERTY | | | LINE. | | | | | 2006-07-23 00:00:00 | NEEDS RESTAMP FOR NEW SHEETS. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2006-06-18 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-06-18 |
Time |
18:39 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-06-18 |
Time |
18:39 |
Sent To |
|
|
| Notes |
| 2006-06-18 00:00:00 | NOTE: THE PROPOSED GENERATOR WILL BE 8FT | | | FROM SIDE PROPERTY LINE. | | | SEC 94-303 MECHANICAL/POOL | | | EQUIPMENT/GENERATOR MAY NOT PROJECT MORE | | | THAN FOUR FEET INTO A SETBACK. | | | |
|
|