Plan Review Details - Permit 06060507
Plan Review Stops For Permit 06060507
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-06-28 Cont ID  
Sent By alange Date 2006-06-28 Time 11:32 Rev Time 0.25
Received By alange Date 2006-06-28 Time 11:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-07-23 Cont ID  
Sent By dpalmer Date 2006-07-23 Time 09:51 Rev Time 0.00
Received By dpalmer Date 2006-07-23 Time 09:23 Sent To P
Notes
2006-07-23 00:00:00** REDLINED THE FOLLOWING.
  
 MISSING "EQUIPMENT GROUNDING CONDUCTOR"
 AFTER THE FIRST MEANS OF DISCONNECT AND
 FROM GEN TO ATS.
 250.24B,250.110,250.122 ETC.
  
 SIGNAGE REQUIRED FOR NEW SERVICE RATED
 MAIN AND GEN DISCONNECT.
 230.2E, 702.8

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-07-15 Cont ID  
Sent By dpalmer Date 2006-07-15 Time 12:25 Rev Time 0.00
Received By dpalmer Date 2006-07-15 Time 12:05 Sent To P
Notes
2006-07-15 00:00:00******* UNSAT 2ND REVIEW *******
  
 1) NOTE: PLEASE SEE STILL MISSING
 DISCONNECT FOR FEEDERS COMING FROM GEN
 REQUIRED AT HOUSE AND GROUPED WITH THE
 NEW SE RATED ATS WITH MAIN.
 PLEASE KNOW, THE ATS AS SHOWN ONLY
 DISCONECTS POWER FROM THE LINE/FPL SIDE
 AND DEOS NOT DISCONNECT POWWER FROM THE
 GEN FEEDERS.
 PLEASE KNOW THE BRKR ON GEN IS NOT
 ACCEPTABLE FOR THIS.
 225.31-225.39, 110.27ETC.
 PLEASE KNOW, THIS DISCONNECT DOES NOT
 REQUIRE OCP AND IS ONLY REQUIRED TO BE A
 MEANS OF DISCONNECT, RATED FOR THE LOAD
 SERVED,GROUPED AND RATED AS SERVICE
 EQUIPMENT.( NOT SE RATED)
 PLEASE KNOW, AS THE EXISTING MCB SEEMS
 TO BE LOCATED INSIDE AND IS NOT GROUPED
 WITH NEW ATS W/MAIN.
  
 2) NOTE: PLEASE SEE THAT A SLAB DETAIL
 IS REQUIRED AND INDICATING HOW THIS UNIT
 WILL BE ATTACHED TO SLAB.
 NOTES WERE PLACED ON THE SURVEY ON THE
 NEW 8" SLAB, HOWEVER THE SLAB DETAIL IS
 REQUIRED AND HOW THIS UNIT WILL BE
 ATTACHED, ISOLATION PADS ETC?
  
  
 3) NOTE: PLEASE KNOW, ALL NEUTRALS AND
 EQUIPMENT GROUNDSWILL BE REQUIRED TO
 BE SEPARATED IN THE EXISTING PANEL.
 250.6,250.24B.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-23 Cont ID  
Sent By dpalmer Date 2006-06-23 Time 13:45 Rev Time 0.00
Received By dpalmer Date 2006-06-23 Time 13:42 Sent To M
Notes
2006-06-23 00:00:00********** UNSAT ***********
  
 1) NOTE: PLEASE SEE THAT THE SURVEY WITH
 "PEN" WRITTEN ON PLANS SHALL BE COPIED
 IN TWO SETS. AS PEN AND PENCIL PLANS ARE
 NOT PERMITTED UNLESS COPIED.
 106.2.1
 THESE SITE SURVEY PLANS WHICH ALREADY
 STMAPED FROM ZONGIN WILL BERE-STAMPED.
  
 2) NOTE: PLEASE SEE THAT CONDUIT FROM
 METER TO GUTTER SHALL BE REQUIRED TO BE
 REMOVED.
  
 3) NOTE: PLEASE SEE 250.24B,250.6 AS AN
 "EQUIPMENT GROUNDING CONDUCTOR" IS NOT
 INSTALLED FROM METER TO THE FIRST MEANS
 OF DISCONNECT.
  
 4) NOTE: PLEASE SEE NO SPEC/MANUFACTURE
 SHEETS WERE SUBMITTED FOR THE ATS.
 PLEASE KNOW, AS SHOWN ON RISER THIS ATS
 SHALL BE SERVICE ENTRANCE RATED WITH A
 MANUAL MEANS OF DISCONNECT RATED FOR THE
 LOAD SERVED TO DISCONNECT POWER FROM
 FPL.
 230.70,230.2,230.72,230.76,230.79
 PLEASE ALSO SEE MISSING DISC RATED FOR
 THE LOAD SERVED FOR THE FEEDERS FROM
 GEN 225.31-225.39
  
 5) NOTE: PLEASE SEE BUILDING REVIEW
 COMMENTS AS NO SLAB DETAIL WAS
 SUBMITTED.
  
 6) NOTE: PLEASE BE SURE THE ELECTRICAL
 CONT/PERSON RESPONSIBLE FOR PLANS AND
 DESIGN SHALL PRINT AND SIGN NAMES ON
 PLANS.
 106.2.1 FBC ADMIN SEC.
  
 7) NOTE: PLEASE BE SURE ALL SPECS ARE
 HIGHLIGHTED FOR MODELS BEING INSTALLED
 PLEASE SEE THAT MANUFACTURES SHEETS
 SHALL CLEARLY INDICAT ETH MIN CLEARENCES
 REQUIRED FOR EQUIPMENT.
 110.3, 215.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status N Date 2006-07-17 Cont ID  
Sent By jleech Date 2006-07-17 Time 09:37 Rev Time 0.00
Received By jleech Date 2006-07-17 Time 09:37 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-07-26 Cont ID  
Sent By jleech Date 2006-07-26 Time 07:11 Rev Time 0.00
Received By jleech Date 2006-07-26 Time 07:11 Sent To Z
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-07-17 Cont ID  
Sent By jleech Date 2006-07-17 Time 09:38 Rev Time 0.00
Received By jleech Date 2006-07-17 Time 09:38 Sent To  
Notes
2006-07-17 00:00:00DENIED;
 1. SHOW LOCATION OF REGULATORS AND
 SHUTOFF VALVES.
 2.NEED SPEC. SHEETS FOR REGULATORS THAT
 WILL BE USED. CHECK RANGE OF REGULATORS
 NOT ALL REGS. WILL ALLOW 750,000 BTU'S.
 TO PASS.
 GAS PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-07-31 Cont ID  
Sent By adarroug Date 2006-07-31 Time 11:58 Rev Time 0.00
Received By adarroug Date 2006-07-31 Time 11:58 Sent To E
Notes
2006-07-31 00:00:00TO "ALANGE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-07-22 Cont ID  
Sent By adarroug Date 2006-07-22 Time 17:13 Rev Time 0.00
Received By adarroug Date 2006-07-22 Time 17:13 Sent To E
Notes
2006-07-22 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-07-13 Cont ID  
Sent By adarroug Date 2006-07-13 Time 15:42 Rev Time 0.00
Received By adarroug Date 2006-07-13 Time 15:42 Sent To E
Notes
2006-07-13 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-19 Cont ID  
Sent By adarroug Date 2006-06-19 Time 10:48 Rev Time 0.00
Received By adarroug Date 2006-06-19 Time 10:48 Sent To E
Notes
2006-06-19 00:00:00TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-28 Cont ID  
Sent By alange Date 2006-06-28 Time 11:32 Rev Time 0.00
Received By alange Date 2006-06-14 Time 10:39 Sent To  
Notes
2006-06-14 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-06-26 Cont ID  
Sent By tgordon Date 2006-06-26 Time 14:50 Rev Time 0.15
Received By tgordon Date 2006-06-26 Time 14:50 Sent To B
Notes
2006-06-26 00:00:00*** PROVISO ***
 1) PER 2004 FBC, FUEL GAS - POWERED
 EQUIPMENT - PERMANENTLY INSTALLED
 EQUIPMENT POWERED BY INTERNAL COMBUSTION
 ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AND NFPA 37.
  
 NFPA 37 INSTALLATION & USE OF STATIONARY
 COMBUSTION ENGINES & GAS TURBINES:
 4.1.4ENGINES (GENERATORS) LOCATED
 OUTDOORS SHALL BE MINIMUM OF 5 FT FROM
 OPENINGS IN WALLS & AT LEAST 5 FT FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS.A
 MINIMUM CLEARANCE IS NOT REQUIRED WHEN
 (1) THE ADJACENT WALL HAS A MINIMUM FIRE
 RESISTANCE RATING OF 1 HOUR OR (2) THE
 WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF
 NON-COMBUSTIBLE MATERIALS, AND IT HAS
 BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE.
 INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS
 SHOULD NOT TERMINATE UNDER STRUCTURES OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO
 THE VENTILATION INTAKES.
  
 2004 FMC 804.3.5 #3, WHERE THE
 TERMINATION IS LOCATED BELOW AN ADJACENT
 ROOF STRUCTURE, THE TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE
 ROOF STRUCTURE.
  
 PLEASE NOTE, WHILE ZONING ALLOWS
 MECHANICAL EQUIPMENT TO ENCROACH 4 FT
 INTO THE REQUIRED SETBACK, GENERATORS
 SHALL MAINTAIN THE REQUIRED ABOVE
 MENTIONED CLEARANCES TO THE ADJACENT
 PROPERTY STRUCTURES, I.E. FENCE,
 BUILDING, WINDOWS, DOORS, OR OPENINGS.
  
 PROVIDE MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AT THE JOBSITE FOR THE
 FIELD INSPECTOR.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-07-17 Cont ID  
Sent By jleech Date 2006-07-17 Time 09:37 Rev Time 0.00
Received By jleech Date 2006-07-17 Time 09:37 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2006-07-28 Cont ID  
Sent By mmclean Date 2006-07-28 Time 08:14 Rev Time 0.00
Received By mmclean Date 2006-07-28 Time 08:14 Sent To I
Notes
2006-07-28 00:00:00RESTAMP OF PLANS.
 THE PROPOSED GENERATOR SHALL NOT BE
 CLOSER THAN 6FT FROMSIDE PROPERTY
 LINE.
  
2006-07-23 00:00:00NEEDS RESTAMP FOR NEW SHEETS.

Review Stop Z ZONING
Rev No 1 Status P Date 2006-06-18 Cont ID  
Sent By mmclean Date 2006-06-18 Time 18:39 Rev Time 0.00
Received By mmclean Date 2006-06-18 Time 18:39 Sent To  
Notes
2006-06-18 00:00:00NOTE: THE PROPOSED GENERATOR WILL BE 8FT
 FROM SIDE PROPERTY LINE.
 SEC 94-303 MECHANICAL/POOL
 EQUIPMENT/GENERATOR MAY NOT PROJECT MORE
 THAN FOUR FEET INTO A SETBACK.
  