Plan Review Details - Permit 06060492
Plan Review Stops For Permit 06060492
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-07-19 Cont ID  
Sent By jwitmer Date 2006-07-19 Time 10:27 Rev Time 1.11
Received By jwitmer Date 2006-07-19 Time 10:21 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-06-22 Cont ID  
Sent By jwitmer Date 2006-06-22 Time 08:09 Rev Time 1.11
Received By jwitmer Date 2006-06-22 Time 08:01 Sent To FIRE
Notes
2006-06-22 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06060492
 ADD: 1801 S FLAGLER# 711
 CONT: PROJECT ONE INTERIORS
 TEL: (561)541-4555
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) 110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 PLANS INDICATE (2) WRONG CODES 2001
 FBC AND THE CABO NATIONAL CODE.
 ADOPTED CODES: 2004 FLORIDA BUILDING
  
 CODE, 2004 EXISTING BUILDING CODE,
 CLASSIFICATION OF WORK, LEVEL OF
 ALTERATION, 1 2 OR 3.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 4) SOUND TRANSMITION:
 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING
 ASSEMBLIES SEPARATING DWELLING UNITS
 FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND
 TRANSMISSION CLASS (STC) OF NOT LESS
 THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN
 ACCORDANCE WITH ASTM E 90. PENETRATIONS
 OR OPENINGS IN CONSTRUCTION ASSEMBLIES
 FOR PIPING; ELECTRICAL DEVICES; RECESSED
 CABINETS; BATHTUBS; SOFFITS; OR HEATING,
 VENTILATING OR EXHAUST DUCTS SHALL BE
 SEALED, LINED, INSULATED OR OTHERWISE
 TREATED TO MAINTAIN THE REQUIRED
 RATINGS. THIS REQUIREMENT SHALL NOT
 APPLY TO DWELLING UNIT ENTRANCE DOORS;
 HOWEVER, SUCH DOORS SHALL BE TIGHT
 FITTING TO THE FRAME AND SILL.
  
 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING
 UNIT AND A PUBLIC OR SERVICE AREA WITHIN
 THE STRUCTURE SHALL HAVE AN IMPACT
 INSULATION CLASS (IIC) RATING OF NOT
 LESS THAN 50 (45 IF FIELD TESTED) WHEN
 TESTED IN ACCORDANCE WITH ASTM E 492.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-07-15 Cont ID  
Sent By dpalmer Date 2006-07-15 Time 18:55 Rev Time 0.00
Received By dpalmer Date 2006-07-15 Time 18:41 Sent To  
Notes
2006-07-15 00:00:00** REDLINED **
  
 1) AS SD'S ARE NOT CIRCUITED AS
 PERVIOUSLY NOTED, PLEASE BE SURE ARC
 FAULT PROTECTION IS PROVIDED AS REQUIRED
 UNDER THE 2002 NEC 210.12B.
 THESE MAY BE CIRCUITED TO BEDRM(S)
 CIRCUITS.
  
 2) MAIN ELECTRICAL PANEL SHALL FACE THE
 MAIN HALL WAY AND MAY NOT FACE BATH RM.
 SHALL ALSO MEET ALL CLEARNCES PER
 110.26, 240.24, 408.7.
  
 THE ABOVE HAS BEEN REDLINED AND AND NO
 REVISIONS ARE REQUIRED AT THIS TIME.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-13 Cont ID  
Sent By dpalmer Date 2006-06-13 Time 08:15 Rev Time 0.00
Received By dpalmer Date 2006-06-13 Time 07:46 Sent To  
Notes
2006-06-13 00:00:00*********UNSAT ************
  
 1) NOTE: PLEASE SEE PLANS INDICATE THE
 2001 FBC. PLEASE KNOW, AS OF OCT 1ST,
 2005, FLORIDA ADOPTED THE 2004 FBC.
 PLEASE SEE THE FOLLOWING CODES SHALL
 ALSO BE REFERENCED ON PLANS AT A MIN.
 2002 NFPA-72, 2002 NFPA-70, NFPA-101
 2003.
  
 2) NOTE: PLEASE SEE PANEL LOCATION AS
 SHOWN IS NOT PERMITTED AND DOES NOT MEET
 110.26,408.7,240.24 ETC.
 PLEASE RELOCATE.
  
 3) NOTE: PLEASE VERIFY SD'S ARE SHOWN.
 PLEASE INDICATE IF THESE ARE 120V W/
 BATTERY BACK AND CIRCUITING.
 PLEASE SEE SD'S ARE MISSING OUTSIDE
 BEDRMS. IF WITHIN 20' OF COOKING
 APPLIANCES,THEN SD'S SHALL BE OF A
 RE-SETTING TYPE OR PHOTOELECTRIC EYE
 TYPE.
 NFPA-72 11.5.1.1, 11.5.3.5,
 FBC R313
  
 4) NOTE: PLEASE SEE THE CIRCUITS IN
 PANEL SCHEDULE LABELED AS GEN LTS AND
 GEN RECEPTS SHALL BE SPECIFIC TO THE
 LOCATIONS IN WHICH THEY FEED.
 408.4.
 IE: MAST BEDRM LTS, KITCHEN LTS, BEDRM
 #2 RECETPS ETC.
  
 5) NOTE: PLEASE SEE POSSIBEL MISSIGN
 RECEPT PER 210.52 IN BEDRM.
 REDLINED.
  
  
 **PLEASE BE SURE TO SEE ANY COMMENTS
 FROM OTHER TRADES WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 ** WHEN RESUBMITTING PLANS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS FROM SETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 SUBMIT ONLY ONE COPY OF THE OLD/VOIDED
 SHEETS FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-07-18 Cont ID  
Sent By mwennerg Date 2006-07-18 Time 10:37 Rev Time 0.00
Received By mwennerg Date 2006-07-18 Time 10:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-06-22 Cont ID  
Sent By mwennerg Date 2006-06-22 Time 09:32 Rev Time 0.00
Received By mwennerg Date 2006-06-22 Time 09:31 Sent To  
Notes
2006-06-22 00:00:00***DENIED***
  
 1) LIFE SAFETY SHALL COMPLY WITH NFPA
 101, 2003 EDITION.
  
 2) SEPARATE SHOP DRAWINGS AND PERMITS
 REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL IF APPLICABLE.
  
 3) PLEASE SEE ELECTRICAL COMMENT (3)
 REGARDING SMOKE DETECTORS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-07-11 Cont ID  
Sent By adarroug Date 2006-07-11 Time 11:03 Rev Time 0.00
Received By adarroug Date 2006-07-11 Time 11:03 Sent To  
Notes
2006-07-11 00:00:00TO "BOB"#16

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-07 Cont ID  
Sent By adarroug Date 2006-07-07 Time 16:25 Rev Time 0.00
Received By adarroug Date 2006-07-07 Time 16:25 Sent To  
Notes
2006-07-07 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-07 Cont ID  
Sent By adarroug Date 2006-06-22 Time 16:20 Rev Time 0.00
Received By adarroug Date 2006-06-09 Time 10:50 Sent To  
Notes
2006-06-09 00:00:00TO "BOB"#18

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-07-11 Cont ID  
Sent By tgordon Date 2006-07-11 Time 14:46 Rev Time 0.20
Received By tgordon Date 2006-07-11 Time 14:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-06-20 Cont ID  
Sent By tgordon Date 2006-06-20 Time 14:32 Rev Time 0.20
Received By tgordon Date 2006-06-20 Time 14:32 Sent To  
Notes
2006-06-20 00:00:00*** DENIED ***
 1) PLEASE SHOW NEW DUCT WORK ON PLANS AS
 FLEX DUCT (IF USING FLEX DUCT).
  
 2) PLEASE SHOW DUCT SIZES OF ALL NEW
 DUCT.
  
 3) PLEASE SHOW SUPPLY AIR GRILL SIZES.
  
 4) PLEASE SHOW SUPPLY AIR CFM'S. AT EACH
 SUPPLY AIR GRILL.
  
 5) PLEASE PROVIDE RETURN AIR FOR NEW
 STUDY. SEE NOTE #6.
  
 6) BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-07-15 Cont ID  
Sent By jleech Date 2006-07-15 Time 13:33 Rev Time 0.00
Received By jleech Date 2006-07-15 Time 13:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-06-19 Cont ID  
Sent By jleech Date 2006-06-19 Time 13:29 Rev Time 0.00
Received By jleech Date 2006-06-19 Time 13:29 Sent To  
Notes
***NONE***