Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-19 Cont ID  
Sent By btrobaug Date 2006-06-19 Time 17:16 Rev Time 0.75
Received By btrobaug Date 2006-06-19 Time 16:53 Sent To PC
Notes
2006-06-19 00:00:00 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 THERE ARE SEVERAL NEW SERVICES FOR THIS
 PROJECT CURRENTLY UNDER REVIEW. THE
 INFORMATION REQUESTED IS TO INSURE
 PUBLIC RECORDS HAVE ALL ELECTRICAL
 SERVICES LOCATED, AND HAVE PROPER LOADS
 AND DEMANDS ON SAME, RECORDED.
  
 1} PLEASE LOCATE ALL SERVICE EQUIPMENT
 ON A SITE PLAN, METER ENCLOSURE,
 DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN
 BE REVIEWED. INDICATE THE PANEL
 DESIGNAIONS, VOLTAGE AND AMPERAGE
 RATINGS.
  
 2} SUBMIT A LOAD CALCULATION FOR THE
 SERVICE FEEDING THE NEW PANEL, AND A
 LOAD CALCULATION FOR THE NEW PANEL.
  
 3} THE SCOPE OF THIS WORK REQUIRES
 ENGINEERING PER CHAPTER 471.003, IF THE
 VOLTAGE IS ABOVE 240.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  