Plan Review Details - Permit 06060451
Plan Review Stops For Permit 06060451
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2006-07-13 Cont ID  
Sent By mperson Date 2006-07-13 Time 13:10 Rev Time 0.45
Received By mperson Date 2006-07-13 Time 13:10 Sent To PC
Notes
2006-07-13 00:00:00NOTE: REFERENCE GEN/RES PERMIT #06060449

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2006-07-03 Cont ID  
Sent By mperson Date 2006-07-03 Time 10:57 Rev Time 0.33
Received By mperson Date 2006-07-03 Time 10:57 Sent To PC
Notes
2006-07-03 00:00:00******DENIED 2ND TIME******
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR GAS RESUBMITTAL:
  
 1. THE MANUFACTURE CUT SHEETS SUBMITTED
 FOR THE GAS REGULATORS FOR THE
 RESUBMITTAL ARE FOR LP GAS, NOT NATURAL
 GAS AS THE DRAWING INDICATES. PLEASE SEE
 ATTACHED APPROVED NATURAL GAS REGULATOR
 APPROVED AND SUGGESTED FOR USE ON 2LP
 NATURAL GAS SYSTEMS BY FLORIDA PUBLIC
 UTILITIES COMPANY, THE AMERICAN METER
 MODEL #1813.
 2. A SEDIMENT TRAP IS REQUIRED PER
 FBC-2004, SEC. 408.4.
 3. A SHUT OFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR
 PER FBC-2004, SEC. 409.4.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-06-19 Cont ID  
Sent By mperson Date 2006-06-19 Time 10:26 Rev Time 0.33
Received By mperson Date 2006-06-19 Time 10:26 Sent To PC
Notes
2006-06-19 00:00:00******DENIED******
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLAN REVIEW FOR A GAS PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 2. TYPE OF GAS, (LP OR NATURAL) PLEASE
 INDICATE THIS ON DRAWINGS
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 4. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 (NOTE: PRESSURE INDICATED ON DRAWINGS IS
 7-11 INCH WATER COLUMN, 1/2" COPPER IS
 SIZED TO SMALL FOR A 0.5 PSI NATURAL GAS
 SYSTEM PER TABLE 404.4(8) SEE ATTACHED
 TABLE FOR REFERENCE FOR RESUBMITTAL)
 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2(NOTE:
 IF REGULATORS ARE USED MANUFACTURER CUT
 SHEETS REQUIRED)
 6. THE PERSON RESPONSIBLE FOR THE
 ISOMETRIC DRAWING SHALL PRINT, AND SIGN
 NAME, AND DATE DRAWINGS. PER CHAPTER 1
 FBC-2004
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. PLEASE SEE ATTACHED CITY OF WEST
 PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS, FBC-2004 FUEL GAS TABLES
 FOR SEMIRIGID COPPER TUBING FOR
 REFERENCE FOR RESUBMITTAL. PLEASE SEE
 THE CORRECTED DRAWING IN RED INK FOR
 REFERENCE FOR RESUBMITTAL, ONLY ONE COR-
 RECTED DRAWING IN RED INK.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-07-08 Cont ID  
Sent By adarroug Date 2006-07-08 Time 17:53 Rev Time 0.00
Received By adarroug Date 2006-07-08 Time 17:53 Sent To G
Notes
2006-07-08 00:00:00TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-25 Cont ID  
Sent By adarroug Date 2006-06-25 Time 18:08 Rev Time 0.00
Received By adarroug Date 2006-06-25 Time 18:07 Sent To G
Notes
2006-06-25 00:00:00TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-25 Cont ID  
Sent By adarroug Date 2006-06-19 Time 18:07 Rev Time 0.00
Received By adarroug Date 2006-06-08 Time 10:34 Sent To  
Notes
2006-06-08 00:00:00TO "G" BOX