Plan Review Details - Permit 06060449
Plan Review Stops For Permit 06060449
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-06-29 Cont ID  
Sent By alange Date 2006-06-29 Time 13:47 Rev Time 0.00
Received By alange Date 2006-06-29 Time 13:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-08-06 Cont ID  
Sent By dpalmer Date 2006-08-06 Time 09:19 Rev Time 0.00
Received By dpalmer Date 2006-08-06 Time 08:51 Sent To P
Notes
2006-08-06 00:00:00******* UNSAT2ND REVIEW ********
  
 ** PLEASE SEE SOME COMMENTS REMAIN AND
 SOME ARE NEW DUE TO CHANGES ON PLANS.
  
  
 1) NOTE: OK.
  
 2) NOTE: NO, ? PLEASE SEE RISER NOW
 INDICATES SE RATED ATS, WHICH ARE NOW
 NOT REQUIRED AS NEW MAINS ARE BEING
 SHOWN IN FRONT OF THEESE ATS'S>??
 PLEASE VERIFY.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THAT THE ATS AS
 SHOWN MUST BE "SERVICE ENTRANCE RATED,
 CONTAING A MANUAL MEANS OF DISCONNECT
 RATED FOR THE LOAD SERVED ETC
 230.70,230.76,230.79
  
 3) NOTE: NO, PLEASE SEE THIS IS NOT
 DONE. PLEASE SEE NO DISCONNECT MEANS FOR
 FEEDERS FROM GEN ARE SHOWN. THE ATS
 UNITS SHOWN ONLY DISCONNECT POWER FROM
 THE NORMAL SIDE AND NOT EM FEEDERS. THE
 DISCONNECTING MEANS MUST BE RATED FOR
 THE LOAD SERVED. DOES NOT REQUIRE OCP.
 ONLY DISCONNECTING MEANS. PLEASE SEE
 COMMENT ABOVE AT THE ATS UNITS NEED ONLY
 RATED FOR "SERVICE EQUIPMENT" IF MAINS
 ARE LOCATED IN FRONT OF THESE ATS'S.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING DISCONNECT
 FOR FEEDERS FROM GEN.
 225.31-225.39
  
 4) NOTE: NO, REPSONSE MENTIONS THIS IS
 DONE, HOWEVER NOT ON RISER.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE THE OCP AT GEN
 ON RISER.
 215.5.
  
 5) NOTE: SAME, THIS IS DONE BUT LEFT IN
 AS COMMENT AS ATS AND OR GEN MAY CHANGE.
 PLEASE SEE THAT SPECS SHALL BE
 "HIGHLIGHTED" FOR THE GEN TO BE
 INSTALLED.
 215.5
  
 6) NOTE: NO, PLEASE SEE MIN CLEARENCES
 ARE SHOWN AS 3FT YET, DARWN AND SHOWN AS
 18"?? PLEASE KNOW, AS ZONING REQUIRES
 "X" DISTANCE FROM PROPERTY LINE AND GEN
 IS REQUIRED TO BE 3' FROM HOUSE, A NEW
 LOCATION FOR GEN MUST BE CHOSEN.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THAT THE GEN
 LOCATION AS SHOWN DOES NOT APPEAR IT
 WILL BE PERMITTED TO BE INSTALLED THIS
 CLOSE TO THE HOUSE.
 PLEASE KNOW, BASED ON ZOING REQUIREMENTS
 AND THE WIDTH OF THE GEN, THE DISTANCE
 OFF THE WALL OF THE HOUSE MAY BE AN
 ISSUE.
 ALL CLEARENCES SHALL BE INDICATED FROM
 HOUSE, WALL, ETC
 PLEASE SEE MECH COMMENTS AND PLEASE ALSO
 BE SURE THE MANUFACTURES SPECS/CUT
 SHEETS INCLUDE THE MIN CLEARENCES AROUND
 EQUIPMENT.
 215.5
  
 7) NOTE: OK.
  
 8) NOTE:NO, RESPONSE MENTIONS
 112A'S.THIS IS NOT THE AIC RATINGS AS
 REQUIRED.110.9,702.5 ETC
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT.
  
 9) NOTE: OK, AS NEW RISER WAS DRAWN. SEE
 ANY NEW COMMENTS.
  
 10)NOTE: OK.
  
 11) NOTE: NO, PLEASE SEE THAT ALL
 CONDUCTORS ARE REQUIRED TO BE SHOWN. THE
 NUMBER, THE SIZES, THE EQUIPMENT
 GROUNDINGETC .
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INCLUDE ALL CONDUCTORS
 IN RACEWAYS, INCLUDING EQUIPMENT
 GROUNDING CONDUCTORS.
 250.110,250.24B,250.122,240.4,310.16
  
 ** NEW NOTE **
  
 12) NOTE: PLEASE SEE FS 553.80(2)(B)
 WITH RESPECT TO DESIGNER AND REPEAT CODE
 COMPLIANT COMMENTS.
 THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
  
 13) NOTE: PLEASE SEE AHU'S ARE BEING
 NOTED AS 4KW AND THEN DE-RATED AT 65%.
 PLEASE SEE 4KW IS NOT A COMMON OR KNOWN
 HEAT SIZE.
 PLEASE PROVIDE INFORMATION ON HEAT AND
 FIGURE INTO CALCS OR PLEASE KNOW, LOAD
 SHEDDING MAY BE AN OPTION. IF SHEDDING
 A/C HEAT, PLEASE PROVIDE DETAIL ON HOW
 THIS WILL BE DONE.
 LOAD AS SHOWN TAKES LOAD VERY CLOSE TO
 OVERLOAD OF EQUIPMENT.
 EQUIPMENT SHALL BE SIZED TO CARRY THE
 INTENDED LOAD.
 702.5
  
 14) NOTE: PLEASE KNOW ALL PLANS/DESIGNS
 AND LOAD CALCS SHALL CONTAIN THE PRINTED
 NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR SAID PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-23 Cont ID  
Sent By dpalmer Date 2006-06-23 Time 12:04 Rev Time 0.00
Received By dpalmer Date 2006-06-23 Time 11:44 Sent To M
Notes
2006-06-23 00:00:00******* UNSAT ********
  
  
 1) NOTE: PLEASE SEE THAT THE LINE AND
 LOAD OF THE SEC'S AND FEEDERS MAY NOT
 OCCUPY THE METER ENCLOSURE.
 230.7 ETC.
  
 2) NOTE: PLEASE SEE THAT THE ATS AS
 SHOWN MUST BE "SERVICE ENTRANCE RATED,
 CONTAING A MANUAL MEANS OF DISCONNECT
 RATED FOR THE LOAD SERVED ETC
 230.70,230.76,230.79
  
 3) NOTE: PLEASE SEE MISSING DISCONNECT
 FOR FEEDERS FROM GEN.
 225.31-225.39
  
 4) NOTE: PLEASE INDICATE THE OCP AT GEN
 ON RISER.
 215.5.
  
 5) NOTE: PLEASE SEE THAT SPECS SHALL BE
 "HIGHLIGHTED" FOR THE GEN TO BE
 INSTALLED.
 215.5
  
 6) NOTE: PLEASE SEE THAT THE GEN
 LOCATION AS SHOWN DOES NOT APPEAR IT
 WILL BE PERMITTED TO BE INSTALLED THIS
 CLOSE TO THE HOUSE.
 PLEASE KNOW, BASED ON ZOING REQUIREMENTS
 AND THE WIDTH OF THE GEN, THE DISTANCE
 OFF THE WALL OF THE HOUSE MAY BE AN
 ISSUE.
 ALL CLEARENCES SHALL BE INDICATED FROM
 HOUSE, WALL, ETC
 PLEASE SEE MECH COMMENTS AND PLEASE ALSO
 BE SURE THE MANUFACTURES SPECS/CUT
 SHEETS INCLUDE THE MIN CLEARENCES AROUND
 EQUIPMENT.
 215.5
  
 7) NOTE: PLEASE SEE THAT PERMIT
 APPLICATION SHALL INCLUDE THE GEN TO BE
 INSTALLED.
  
 8) NOTE: PLEASE INDICATE AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT.
  
 9) NOTE: PLEASE SEE SERVICE SEEMS TO BE
 400A AND BOTH PANELS ARE SHWON BEING FED
 FROM THE 200A ATS. HOW IS THIS POSSIBLE
 WHEN BOTH PANELS EXISTING ARE 200A AS
 INDICATED BY THE CONDUCTORS SIZES.
 PLEASE SEE SPECS AS SHOWN WILL NOT BE
 ABLE TO BE USED.
  
 10)NOTE: PLEASE SEE THE ELEC CONT DID
 NOT SIGN ON THE ELECTRICAL LINE ON
 APPLICATION FOR THE ELECTRICAL PERMIT.
 IF THIS IS THE INTENT, PLEASE DO SO WHEN
 RESUBMITTING PLANS. IF THERE ARE ANY
 QUESTIONS, ON THIS PLEASE CALL.
  
 11) NOTE: PLEASE INCLUDE ALL CONDUCTORS
 IN RACEWAYS, INCLUDING EQUIPMENT
 GROUNDING CONDUCTORS.
 250.110,250.24B,250.122,240.4,310.16
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2006-07-13 Cont ID  
Sent By mperson Date 2006-07-13 Time 13:46 Rev Time 0.00
Received By mperson Date 2006-07-13 Time 13:46 Sent To  
Notes
2006-07-13 00:00:00NOTE: REFERENCE GAS PERMIT #06060451

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-01 Cont ID  
Sent By adarroug Date 2006-08-01 Time 14:19 Rev Time 0.00
Received By adarroug Date 2006-08-01 Time 14:19 Sent To E
Notes
2006-08-01 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-19 Cont ID  
Sent By adarroug Date 2006-06-19 Time 10:28 Rev Time 0.00
Received By adarroug Date 2006-06-19 Time 10:28 Sent To E
Notes
2006-06-19 00:00:00TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-29 Cont ID  
Sent By alange Date 2006-06-29 Time 13:47 Rev Time 0.00
Received By alange Date 2006-06-08 Time 10:33 Sent To  
Notes
2006-06-08 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-06-26 Cont ID  
Sent By tgordon Date 2006-06-26 Time 14:17 Rev Time 0.15
Received By tgordon Date 2006-06-26 Time 14:36 Sent To B
Notes
2006-06-26 00:00:00*** PROVISO ***
 1) PER 2004 FBC, FUEL GAS - POWERED
 EQUIPMENT - PERMANENTLY INSTALLED
 EQUIPMENT POWERED BY INTERNAL COMBUSTION
 ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AND NFPA 37.
  
 NFPA 37 INSTALLATION & USE OF STATIONARY
 COMBUSTION ENGINES & GAS TURBINES:
 4.1.4ENGINES (GENERATORS) LOCATED
 OUTDOORS SHALL BE MINIMUM OF 5 FT FROM
 OPENINGS IN WALLS & AT LEAST 5 FT FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS.A
 MINIMUM CLEARANCE IS NOT REQUIRED WHEN
 (1) THE ADJACENT WALL HAS A MINIMUM FIRE
 RESISTANCE RATING OF 1 HOUR OR (2) THE
 WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF
 NON-COMBUSTIBLE MATERIALS, AND IT HAS
 BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE.
 INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS
 SHOULD NOT TERMINATE UNDER STRUCTURES OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO
 THE VENTILATION INTAKES.
  
 2004 FMC 804.3.5 #3, WHERE THE
 TERMINATION IS LOCATED BELOW AN ADJACENT
 ROOF STRUCTURE, THE TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE
 ROOF STRUCTURE.
  
 PLEASE NOTE, WHILE ZONING ALLOWS
 MECHANICAL EQUIPMENT TO ENCROACH 4 FT
 INTO THE REQUIRED SETBACK, GENERATORS
 SHALL MAINTAIN THE REQUIRED ABOVE
 MENTIONED CLEARANCES TO THE ADJACENT
 PROPERTY STRUCTURES, I.E. FENCE,
 BUILDING, WINDOWS, DOORS, OR OPENINGS.
  
 PROVIDE MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AT THE JOBSITE FOR THE
 FIELD INSPECTOR.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-07-13 Cont ID  
Sent By tgordon Date 2006-06-26 Time 14:36 Rev Time 0.00
Received By mperson Date 2006-07-13 Time 13:45 Sent To G
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2006-06-18 Cont ID  
Sent By mmclean Date 2006-06-18 Time 19:24 Rev Time 0.00
Received By mmclean Date 2006-06-18 Time 19:24 Sent To I
Notes
2006-06-18 00:00:00NOTE:
 THE PROPOSED GENERATOR SHALL NOT BE
 CLOSER THAN 3'6" FROM PROPERTY LINE.