| 2006-07-15 00:00:00 | ******* UNSAT ******* |
| | |
| | 1) NOTE: PLEASE SEE RISER IS NOW BEING |
| | SHOWN COMPLETELY REVISED FROM PREVIOUS |
| | RISERAND IS NOW SHOWING "TWO' ATS'S?? |
| | PLEASE SEE RISER SHOWS A NOTE WHICH |
| | MENTIONS TWO EXSITING PANELS, YET, RISER |
| | SHOWS ONE AS A MAIN DISCONNECT? |
| | PLEASE SEE NEW MAIN SHOWS CONNECTIONS TO |
| | BOTH ATS UNITS. ONE SE RATED AND THE |
| | OTHER NOT SE RATED?? |
| | |
| | PLEASE SEE THE SE RATED ATS AS ONLY |
| | DISCONNECTS THE POWER ON THE FPL/LINE |
| | SIDE AND DOES NOT DISCONNECT POWER ON |
| | THE GEN/FEEDER SIDE AS REQUIRED BY |
| | 225.31-225.39 |
| | PLEASE KNOW, PLANS DO NOT INDICATE IF |
| | THE EXISTING 200A PANEL IS MLO OR MCB |
| | AND IF THIS PANEL IS GROUPED WITH THE |
| | OTHER MAINS. |
| | 230.72,225.34 |
| | PLEASE KNOW, IF A MAIN DISCONNECT IS |
| | LOCATED AHEAD OF THE ATS, THEN THE ATS |
| | DOES NOT NEED TO BE SE RATED AND ONLY |
| | RATED AS "SERVICE EQUIPMENT". |
| | PLEASE EXPLAIN RATIONAL OF THE 2ND NON |
| | SE RATED ATS? WHY IS THIS BEING USED AS |
| | THIS IS SHOWN FEEDING THE SAME SE RATED |
| | ATS. |
| | PLEASE ALSO SEE THE NEW MAIN DISCONNECT |
| | IS BEING SHOWN FEEDING THE NEW SE RATED |
| | ATS AND THE NON SE RATED ATS? |
| | SPECS SHOULD REFLECT THE ATS BEING |
| | INSTALLED. |
| | |
| | ** PLEASE KNOW, RISER NOW ALSO MENTIONS |
| | TO ISOLATE NEUTRALS IN PANEL "IF |
| | NECESSARY". PLEASE KNOW, ALL NEUTRALS |
| | AND EQUIPMENT GROUNDING CONDUCTORS SHALL |
| | BE SEPARATED AFTER THE FIRST MEANS OF |
| | DISONNECT AS NOT TO PARALLEL THE |
| | NEUTRAL. |
| | 250.6,250.24B |
| | |
| | 2) NOTE: PLEASE KNOW, THE LATEST LTR |
| | FROM GENERAC FOR MIN CLEARENCES LEAVES |
| | THE REQUIRED MIN CLEARNECES TO THE AHJ, |
| | AND AS STATED AND RECOMMENDED ON A LTR |
| | OBTAIN FROM GENERAC, THE MIN CLEARNECES |
| | FOR AIR COOLED UNITS, SHALL BE 3' AND |
| | LIQUID COLLED UNITS SHALL BE 5' FROM ANY |
| | SURROUNDING WALLS , ETC. |
| | THIS IS A NOTE FOR ANY INSTALLATIONS. |
| | |
| | 3) NOTE: PLEASE SPECIFY THE ELEVATION OF |
| | THE SLAB FOR THE NEW GEN. THE LTR WHICH |
| | MENTIONS THE FLOOD ZONEIS OK, HOWEVER |
| | SLAB ELEVATIONS SHOULD BE NOTED OR |
| | SHOWN. PLEASE SEE AN ELEV OF 12 IS SHOWN |
| | IN LTR, BUT UNCLEAR IF THIS IS 12' |
| | (FEET). IF SO, ELEV SHOULD BE NOTED ON |
| | SLAB DETAIL TO BE 12'6" MIN. PLEASE |
| | KNOW, AN ELEVATION CERTIFICATE WILL BE |
| | REQUIRED BEFORE FINAL. |
| | |
| | |
| | 4) NOTE: PLEASE MAKE PLANS INTO TWO SETS |
| | AND REMOVE ANY OLD/VOIDED SHEETS FROM |
| | SETS AND LEAVE ANY PREVIOUSLY STAMPED |
| | SHEETS BE OTHER REVIEWER(S) IN SETS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |