Plan Review Details - Permit 06060297
Plan Review Stops For Permit 06060297
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-07-19 Cont ID  
Sent By jwitmer Date 2007-07-19 Time 09:52 Rev Time 1.22
Received By jwitmer Date 2007-07-19 Time 09:37 Sent To  
Notes
2007-07-19 09:46:40BUILDING PROVISO;
 06060297 2916 S DIXIE HWY.
 TERRA CON BUILDERS
 1) THE ISSUED SET OF PLANS INDICATED A NEW 3'-0" DOOR
 AND SIDE LITE, TO DATE NO PRODUCT APPROVALS HAVE BEEN
 SUBMITTED.
 2) TEA BAR, THE LETTER DATED 1-26-07 FROM ARCHITECT
 THEODORE DAVIS STATES THE TEA BAR WILL ONLY BE USED BY
 EMPLOYEES SEE
 11-4.1.1(3)3)AREAS USED ONLY BY EMPLOYEES AS
 WORK AREAS. AREAS THAT ARE USED ONLY AS WORK AREAS
 SHALL BE DESIGNED
 AND CONSTRUCTED SO THAT INDIVIDUALS WITH DISABILITIES
 CAN APPROACH, ENTER, AND EXIT THE AREAS. THIS CODE DOES
 NOT REQUIRE THAT
 ANY AREAS USED ONLY AS WORK AREAS BE CONSTRUCTED TO
 PERMIT MANEUVERING WITHIN THE WORK AREA OR BE
 CONSTRUCTED OR EQUIPPED
 TO BE ACCESSIBLE.
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-06-15 Cont ID  
Sent By jwitmer Date 2007-06-15 Time 07:57 Rev Time 1.22
Received By jwitmer Date 2007-06-15 Time 07:57 Sent To  
Notes
2007-06-15 08:02:35BUILDING PLAN REVIEW
 PERMIT: 06060297
 ADD: 2916 S DIXIE HWY
 CONT: TERRA CON CONSTRUCTION
 TEL: (561)329-7676
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION:REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) PLEASE SEE COMMENT# 7 FROM THE ORIGINAL FIRST REVIEW
 ABOUT ACCESSIBILITY AND THE FRONT DOOR:
 7) EXISTING ENTRY DOORS APPEAR TO BE APPROXIMATELY
 2'-0" WIDE.ONE ENTRANCE HAS STAIRS, DOES THE OTHER
 ENTRANCE HAVE AN ACCESSIBLE ENTRANCE SINGLE DOOR 3'-0"
 WIDE?
 11-4.1.6(2) DUTY TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO ALTERED
 AREAS SHALL BE DEEMED DISPROPORTIONATE
 TO THE OVERALL ALTERATION WHEN THE COST
 EXCEEDS 20 % OF THE COST OF THE ALTERA-
 TION TO THE PRIMARY FUNCTION AREA.
 (A)(I) AN ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE REST-
 ROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STOR-
 AGE OR ALARMS.
  
 3) ALSO SEE ISSUED SET OF PLANSFOR ACCESSIBLE COUNTER
 & BAR SINK . SEE PLUMBING REVIEWER COMMENTS FIRST
 REVIEW FOR BAR SINK REQUIREMENTS!!!!!
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-09-15 Cont ID  
Sent By jwitmer Date 2006-09-15 Time 11:04 Rev Time 0.55
Received By jwitmer Date 2006-09-15 Time 11:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-08-24 Cont ID  
Sent By jwitmer Date 2006-08-24 Time 09:58 Rev Time 1.11
Received By jwitmer Date 2006-08-24 Time 09:58 Sent To  
Notes
2006-08-24 00:00:00PERMIT: 06060297
 ADD: 2916 S DIXIE HWY
 CONT: TERRA CONSTRUCTION
 TEL: (561)329-7676
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
 --- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) 110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 FLORIDA BUILDING CODE/ 2004
 EXISTING BUILDING CODE/ 2004
 CLASSIFICATION OF WORK,
 LEVEL 1,2 OR 3.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 IS THIS A CHANGE OF OCCUPANCY?
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER
 SYSTEM IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
  
 OF THE BUILDING PERMIT.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-06-22 Cont ID  
Sent By jwitmer Date 2006-06-22 Time 07:09 Rev Time 2.22
Received By jwitmer Date 2006-06-22 Time 07:09 Sent To  
Notes
2006-06-22 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06060297
 ADD: 2916 S DIXIE HWY
 CONT: TERRA CONSTRUCTION
 TEL: (561)329-7676
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 --- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 FLORIDA BUILDING CODE/ 2004
 EXISTING BUILDING CODE/ 2004
 CLASSIFICATION OF WORK,
 LEVEL 1,2 OR 3.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 IS THIS A CHANGE OF OCCUPANCY?
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER
 SYSTEM IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
  
 OF THE BUILDING PERMIT.
  
 2) SHEET A-1 OVERHEAD DOOR INFILL, PLANS
 INDICATE THE USE OF 22 GA. STEEL STUDS.
 THIS GAUGE STUDS ARE FOR INTERIOR USE
 ONLY. STRUCTURAL GAUGE FRAMING IS 18
 GAUGE AND HEAVIER.ASTM C955 LOAD BEARING
 STEEL STUDS, TABLE 22506.2.
  
 3) SAME DETAIL INDICATES THE USE OF
 PLYWOOD SHEATHING, SEE 2304.11.2.5 WOOD
 SIDING.
 CLEARANCE BETWEEN WOOD SIDING AND EARTH
 ON THE EXTERIOR OF A BUILDING SHALL NOT
 BE LESS THAN 6 INCHES (152 MM) EXCEPT
 WHERE SIDING, SHEATHING AND WALL FRAMING
 ARE OF NATURALLY DURABLE OR
 PRESERVATIVE-TREATED WOOD .
 2304.9.5 FASTENERS IN PRESERVATIVE
 TREATED AND FIRE-RETARDANT-TREATED WOOD
 . FASTENERS FOR PRESERVATIVE TREATED AND
 FIRE-RETARDANT-TREATED WOOD SHALL BE OF
 HOT-DIPPED ZINC-COATED GALVANIZED STEEL,
 STAINLESS STEEL, SILICON BRONZE OR
 COPPER. FASTENINGS FOR WOOD FOUNDATIONS
 SHALL BE AS REQUIRED IN AF&PA TECHNICAL
 REPORT NO. 7.
  
 4) OFFICE DOOR(A) MISSING 18" CLEARENCE
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 5) UNISEX RESTROOM DOOR:11-4.22.2 DOORS.
  
 (1)ALL DOORS TO ACCESSIBLE TOILET
 ROOMS SHALL COMPLY WITH SECTION 11-4.13
 . DOORS SHALL NOT SWING INTO THE CLEAR
 FLOOR SPACE REQUIRED FOR ANY
 FIXTURE.11-4.19.3 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE 30 INCHES BY 48
 INCHES (760 MM BY 1219 MM) COMPLYING
 WITH SECTION 11-4.2.4 SHALL BE PROVIDED
 IN FRONT OF A LAVATORY TO ALLOW FORWARD
 APPROACH. SUCH CLEAR FLOOR SPACE SHALL
 ADJOIN OR OVERLAP AN ACCESSIBLE ROUTE
 AND SHALL EXTEND A MAXIMUM OF 19 INCHES
 (485 MM) UNDERNEATH THE LAVATORY (SEE
 FIGURE 11-32 ).
  
 6) SHOWER:11-4.21.7 CURBS.
 IF PROVIDED, CURBS IN SHOWER STALLS 36
 INCHES BY 36 INCHES (915 MM BY 915 MM)
 SHALL BE NO HIGHER THAN ? INCH (13 MM).
 SHOWER STALLS THAT ARE 30 INCHES BY 60
 INCHES (760 MM BY 1525 MM) MINIMUM SHALL
 NOT HAVE CURBS.
  
 7) EXISTING ENTRY DOORS APPEAR TO BE
 APPROXIMATELY 2'-0" WIDE.ONE ENTRANCE
 HAS STAIRS, DOES THE OTHER ENTRANCE HAVE
 AN ACCESSIBLE ENTRANCE SINGLE DOOR 3'-0"
 WIDE?
 11-4.1.6(2) DUTY TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO ALTERED
 AREAS SHALL BE DEEMED DISPROPORTIONATE
 TO THE OVERALL ALTERATION WHEN THE COST
 EXCEEDS 20 % OF THE COST OF THE ALTERA-
 TION TO THE PRIMARY FUNCTION AREA.
 (A)(I) AN ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE REST-
 ROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STOR-
 AGE OR ALARMS.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2007-08-28 Cont ID  
Sent By dpalmer Date 2007-08-28 Time 14:37 Rev Time 0.00
Received By dpalmer Date 2007-08-28 Time 07:39 Sent To PC
Notes
2007-08-28 14:37:232007-08-28 14:37:23
  
 REVISED PLANS AND ENERGY CALCS, UNDER "T" FOR PU,
 TRIED TO CALL # AS LISTED ON SHEET FOR CONTACT
 (329-7171) BUT NUMBER IS NOT A WORKING # PER MESSAGE
 FROM PHONE COMPANY. NEEDS TO PAY FEE OF $60, RECEIPTS
 ATTACHED. DV PALMER.
2007-08-28 07:42:032007-08-28 07:42:03
  
 **HOLD **
  
 REVISIONS SUBMITTED ON 8/24 WERE WAITING ON NEW REVISED
 CORRECTED ENERGY CALCULATIONS TO BE BROUGHT IN.SPOKE
 TO THE PERSON DOING THE ENERGY CALCULATIONS THREE
 TIMES.
 AS THESE HAVE NOT BEEN BROUGHT IN THE PLANS ARE BEING
 PLACED OUTFRONT UNDER "T" (LARGE BINS) ON HOLD.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-805-6717

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2007-07-13 Cont ID  
Sent By dpalmer Date 2007-07-13 Time 07:30 Rev Time 0.00
Received By dpalmer Date 2007-07-13 Time 07:01 Sent To  
Notes
2007-07-13 07:30:36 
 **** UNSAT****
  
  
  
 1) NOTE: PLEASE SEE THE ENERGY CALCULATIONS NEED TO BE
 *SIGNED* BY THE DESIGNER OR RECORD. PLEASE SEE THE
 PREPARER IS NOT SIGNED ON SHEETS.
 13-103.1.1.1
  
 PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED AS THE
 INPUT DATA REPORTS DO NOT CORRELATE WITH THE PLANS FOR
 THE AMOUNT OF FIXTURES, TYPES OF FIXTURES AND WATTAGE
 OF FIXTURES.
 PLEASE CORRELATE AND REVISE.
  
 2) NOTE: PLEASE SEE THERE ARE FEES OWED AS THE REVISION
 WHICH WAS SUBMITTED ON 6/28 HAD 7 SHEETS AND NOT 5 AS
 INDICATED ON COVER SHEETS.
 PLEASE ALSO SEE REVISED ENERGY CALCULATIONS ARE NOT
 CONSIDERED A *SUBMITTAL* AND THE MINIMUM REVISION FEE
 IS OWED.
 THE TOTAL OWED FOR THESE REVISIONS ARE $80.00. PLEASE
 KNOW WHEN SUBMITTING CORRECTED PLANS AND ENERGY
 CALCULATIONS FEES WILL BE DUE FOR THE NEXT REVIEW
 ALSO.
  
 FBC 108.3
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2007-07-03 Cont ID  
Sent By dpalmer Date 2007-07-03 Time 13:02 Rev Time 0.00
Received By dpalmer Date 2007-07-03 Time 12:09 Sent To  
Notes
2007-07-03 13:02:46** UNSAT **
  
 1) NOTE: PLEASE SUBMIT THE REVISED ENERGY CALCULATIONS
 AS PREVIOUS REQUESTED.THE REVIEW OF THE ENERGY
 CALCULATIONS AND COORDINATION WITH PLANS CAN NOT BE
 DONE AT THIS TIME.
 FBC13-415.1.AB.1.1, 13-415.1.C, 13-415.2
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2007-06-08 Cont ID  
Sent By dpalmer Date 2007-06-08 Time 20:20 Rev Time 0.00
Received By dpalmer Date 2007-06-08 Time 20:02 Sent To  
Notes
2007-06-08 20:21:09** UNSAT*
  
 1) NOTE: PLEASE SUBMIT REVISED ELECTRICAL PLANS SHOWING
 REVISIONS. PLEASE SUBMIT REVISED PANEL SCHEDULE FOR
 CIRCUITS TO BE SPECIFIC TO ALL AREAS AND ROOMS IN WHICH
 THEY FEED. PLEASE SEE 408.4
  
 2) NOTE: PLEASE COORDINATE ALL ARCHITECTURAL,
 ELECTRICAL, MECHANICAL AND PLUMBING SHEETS AS PANELS
 ARE NOT THE SAME ON SHEETS.
 FBC 106.1.2
  
 3) NOTE: PLEASE SEE A SHEETS INDICATE A STACKED
 WASHER/DRYER HOWEVER ELECTRICAL PANEL SCHEDULE
 INDICATES THESE AS SEPARATE UNITS?
 PLEASE ADJUST A SHEETS OR ELECTRICAL PLANS AND PANEL
 SCHEDULE.
 FBC 106.1.2
  
 4) NOTE: PLEASE SEE THE CONDUCTORS FOR EACH AHU IS NOT
 OF SUFFICIENT SIZE PER 310.16. REQUIRES #6 MINIMUM FOR
 60AMP BREAKER.
  
 5) NOTE: PLEASE SEE PLANS SEEM TO SHOW A GUTTER OR
 J-BOX OUTSIDE, THIS SEEMS TO BE AN OLD CT CAN WHICH IS
 BEING REQUIRED TO BE REMOVED BASED ON FIELD CONDITIONS
 AND PICTURES SUBMITTED TO THIS OFFICE FROM THE
 ELECTRICAL INSPECTOR.
 PLEASE BE SURE THE ON-SITE WORK IS COORDINATED WITH
 PLANS.
  
 6) NOTE: PLEASE SUBMIT REVISED ENERGY CALCULATIONS
 BASED ON FIELD CHANGES. PLEASE SEE 13-415.1.AB.1.1,
 13-415.2.ABC.1.2 ETC.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-09-29 Cont ID  
Sent By dpalmer Date 2006-09-29 Time 20:11 Rev Time 0.00
Received By dpalmer Date 2006-09-29 Time 20:11 Sent To B
Notes
2006-09-29 00:00:00NEW SHEETS SIGNED , DATED AND SEALED BY
 THE ENGINEER OF RECORD.
 PLANS SENT BACK TO LUIS'S DESK.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-09-14 Cont ID  
Sent By dpalmer Date 2006-09-14 Time 18:15 Rev Time 0.00
Received By dpalmer Date 2006-09-14 Time 16:58 Sent To  
Notes
2006-09-14 00:00:00**** UNSAT ****
  
 1) NOTE: PLEASE SEE DUPLICATE PERMIT
 APPLICATION SUBMITTED IS REQUIRED OT
 HAVE THE PRINTED NAMES AND SIGNATURES OF
 THE TWO SUB-CONTRACTORS WHICH WERE
 ORIGINALLY SIGNED ON. THESE TWO WERE THE
 MECHANICAL AND ELECTRICAL ONLY. PLEASE
 SEE THAT NO PLUMBING SUB CONTRACTOR WAS
 ORIGINALLY SIGNED ON APPLICATION.
 PLEASE BE SURE ALL LICENSE INFORMATION
 IS ALSO FILLED OUT ON PERMIT
 APPLICATION.
  
 2) NOTE: PLEASE SEE THAT THE NEW REVISED
 ELECTRICAL PLANS ARE NOW SIGNED , DATED
 AND SEALED BY THE ARCHITECT OF RECORD
 WHICH IS NOT PERMITTED AS THESE
 PLANS/DESIGNS WERE DONE BY AN
 ENGINEERING FIRM. PLEASE BE SURE TO HAVE
 NEW ELECTRICAL SHEETS SIGNED, DATED AND
 SEALED BY THE RESPONSIBLE ENGINEER OF
 RECORD.
 FS 471.025, FAC 61G15-23.002
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-08-16 Cont ID  
Sent By dpalmer Date 2006-08-16 Time 07:36 Rev Time 0.00
Received By dpalmer Date 2006-08-16 Time 07:04 Sent To  
Notes
2006-08-16 00:00:00**** NOTE *****
  
 TEMP IN FAILED STATUS. NO PERMIT
 APPLICATION IN PACKAGE CALLED AND LEFT
 CONTRACTOR A MESSAGE FOR APPLICATION TO
 BE BROUGHT BACK IN.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-13 Cont ID  
Sent By dpalmer Date 2006-06-13 Time 07:34 Rev Time 0.00
Received By dpalmer Date 2006-06-13 Time 06:59 Sent To  
Notes
2006-06-13 00:00:00*************** UNSAT *************
  
 ** PLEASE KNOW, PLANS ARE NOT COMPLETE
 AT THIS TIME.
  
  
 1) NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH A PANEL
 SCHEDULE TO BE SUBMITTED.
 215.5
  
 2) NOTE: PLEASE SEE THAT NO PANEL
 SCHEDULE WAS SUBMITTED SHOWING ALL MIN
 CIRCUITS, LOADS, CONDUCTOR SIZES ETC.
 215.5,408.4, 310.16,240.4 ETC
  
 3) NOTE: PLEASE SUBMIT COMPLETE LOAD
 CALCULATIONS AND RISER SHOWING THE
 EXISTING SERVICE, SIZES OF EQQUIPMENT
 ETC. 220.3,220.10,220.11,220.13, ALL
 CONTINOUS LOADS @125% PER 215.3,230.42
 ETC
 215.5.240.4.310.16 ETC.
  
 4) NOTE: PLEASE SEE 700.12E FOR
 CIRCUTING OF ALL EM/ EXT LTS.
  
 5) NOTE: PLEASE INDICATE NEW OR EXISTING
 SIGN CIRCUIT REQUIRED PER 600.5
  
 6) NOTE: PLEASE SEE BUILDING SEEMS TO BE
 PART OF A LARGER STRUCTURE. IF THE
 BUILDING IS LARGER THAN 5000 SA FT OVER
 ALL, THEN PLEASE SEE FBC CHAPTER
 13,13-415.1.ABC.1.1, .1.2,.1.3.
 PLEASE PROVIDE LIGHTING CONTROLS WHICH
 ARE REQUIRED UNDER THE NEW FLORIDA
 ENERGY CODE.
  
 7) NOTE: PLEASE SEE PANEL AS SHOWN ON
 PLANS DOES NOT MEET 110.26,240.24.
 PLEASE ADJUST.
  
 8) NOTE: PLEASE SEE LOCATION OF WATER
 HEATER DOES NOT MIN CLEARENCES PER
 422.17
 PLEASE ADJUST.
  
 9) NOTE: PLEASE SEE POSSIBLE NOTES FROM
 BUILDING REVIEW FOR VALUATION OF PROJECT
 PER FBC 108.3 ADMINISTRATIVE SECTION AS
 ADOPTED BY THE CITY OF WEST PALM BEACH.
  
 10) NOTE: PLEASE SEE THE OWNER AS SIGNED
 ON NOTICE OF COMMENCEMENT IS DIFFERENT
 THAN THE OWNER AS LISTED IN OUR SYSTEM
 AND THE PROPERTY APPRAISER'S OFFICE.
 PLEASE PROVIDE DOCUMENTS FOR NEW
 OWNERSHIP.
 FS 713.13
  
 11) NOTE: PLEASE SEE THAT THE CODES IN
 EFFECT SHALL BE STATED ON PLANS. 106.1.2
 PLEASE SEE PLANS SHALL INCLUDE AT A MIN
 2004 FBC, NFPA-72 2002 , NFPA-101 2003,
 NFPA-70 2002 .
 PLEASE SEE OTHER CODES MAY BE REQUESTED
 BY OTHER REVIEWER(S).
  
 12) NOTE: PLEASE VERIFY WHAT TYPE OF
 EGRESS LIGHTING IS PROVIDED TO THE
 PUBLIC RIGHT OF WAY PER LS101 7.8,7.9
 NO LIGHTING INDICATED AT THIS TIME.
  
 ** PLEASE KNOW, PLANS MAY HAVE FURTHER
 COMMENTS AS PLANS WERE NOT COMPLETE AT
 THIS TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-06-22 Cont ID  
Sent By mawillia Date 2007-06-22 Time 10:57 Rev Time 0.00
Received By mawillia Date 2007-06-22 Time 10:46 Sent To  
Notes
2007-06-22 10:56:41*****PROVISO*****
  
  
 THE APPROPIATE REVISED PLAN SHEET(S) TO BE FIRE-STAMPED
 WHEN OTHER REVIEWERS HAVE BEEN SATISFIED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-09-15 Cont ID  
Sent By mawillia Date 2006-09-15 Time 15:06 Rev Time 0.00
Received By mawillia Date 2006-09-15 Time 14:53 Sent To  
Notes
2006-09-15 00:00:00*****APPROVED*****
  
  
  
  
 FIRE PLAN REVIEW COMMENTS OF 08/24/2006
 HAVE BEEN ADDRESSED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-08-24 Cont ID  
Sent By mawillia Date 2006-08-24 Time 16:08 Rev Time 0.00
Received By mawillia Date 2006-08-24 Time 16:08 Sent To  
Notes
2006-08-24 00:00:00**UNSAT**
  
  
  
 1.) FIRE REVIEW OF 6/19/2006 NOTE #3 HAS
 NOT BEEN ADDRESSED. PLEASE INDICATE
 INTERIOR FINISH FOR WALLS AND CEILING
 (CLASS A OR B) IN THE MEANS OF EGRESS
 AREAS.
  
 2.)PLEASE INDICATE WHY THERE IF NOT AN
 EXIT SIGN LIGHT AT THE EXISTING DOOR
 LEADING FROM YOGA STUDIO (PG E1.1 NEAR
 A-31).
  
 ALL OTHER NOTES AND(OR) CONCERNS OF
 06/19/2006 FIRE REVIEW HAVE BEEN
 ACKNOWLEDGED/ADDRESSED.THANK YOU
  
  
  
  
  
  
 LT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-06-19 Cont ID  
Sent By mcarsill Date 2006-06-19 Time 15:03 Rev Time 0.00
Received By mcarsill Date 2006-06-19 Time 14:57 Sent To  
Notes
2006-06-19 00:00:001. DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2. ONLY ONE EXIT SIGN COULD BE LOCATED
 ON PAGE A-4. PLEASE REVISE PLANS AS
 NECESSARY.
  
 3. PLEASE INDICATE INTERIOR FINISH FOR
 WALLS AND CEILINGS. CLASS A OR B IS
 REQUIRED IN MEANS OF EGRESS AREAS.
  
 4. NO PORTABLE FIRE EXTINGUISHERS
 ILLUSTRATED ON THE PLANS. PLEASE DISPLAY
 THESE EXISTING OR NEW DEVICES.
  
 5. PLEASE INDICATE EXISTING DOOR
 HARDWARE INCLUDING LOCKING DEVICES SO A
 DETERMINATION CAN BE MADE IF THEY MEET
 CODE.
  
 6. DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY.
  
 7. EXITS SHALL REMAIN CLEAR AND
 UNOBSTRUCTED.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2007-07-06 Cont ID  
Sent By adarroug Date 2007-07-06 Time 14:36 Rev Time 0.00
Received By adarroug Date 2007-07-06 Time 14:36 Sent To E
Notes
2007-07-06 14:36:27TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-06-29 Cont ID  
Sent By adarroug Date 2007-06-29 Time 13:09 Rev Time 0.00
Received By adarroug Date 2007-06-29 Time 13:09 Sent To  
Notes
2007-07-03 08:20:57TO "BOB"#12
2007-06-29 13:11:05WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-06-26 Cont ID  
Sent By adarroug Date 2007-06-26 Time 11:57 Rev Time 0.00
Received By adarroug Date 2007-06-26 Time 11:56 Sent To  
Notes
2007-06-29 11:57:30TO "BOB"#1

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-06-04 Cont ID  
Sent By adarroug Date 2007-06-04 Time 10:00 Rev Time 0.00
Received By adarroug Date 2007-06-04 Time 10:00 Sent To  
Notes
2007-06-04 10:00:54TO "BOB"#13

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-04-06 Cont ID  
Sent By spalmer Date 2007-04-06 Time 17:21 Rev Time 0.00
Received By spalmer Date 2007-04-06 Time 17:21 Sent To M
Notes
2007-04-06 17:21:51TO TOM GORDON

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-03-27 Cont ID  
Sent By spalmer Date 2007-03-27 Time 18:35 Rev Time 0.00
Received By spalmer Date 2007-03-27 Time 18:35 Sent To M
Notes
2007-03-27 18:35:45TO MECH BOX

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-09-13 Cont ID  
Sent By adarroug Date 2006-09-13 Time 11:51 Rev Time 0.00
Received By adarroug Date 2006-09-13 Time 11:51 Sent To  
Notes
2006-09-13 00:00:00TO "BOB"#1

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-09-11 Cont ID  
Sent By adarroug Date 2006-09-11 Time 09:34 Rev Time 0.00
Received By adarroug Date 2006-09-11 Time 09:34 Sent To  
Notes
2006-09-11 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-02 Cont ID  
Sent By adarroug Date 2006-08-02 Time 14:30 Rev Time 0.00
Received By adarroug Date 2006-08-02 Time 14:30 Sent To  
Notes
2006-08-11 00:00:00TO "BOB"#7
2006-08-02 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-02 Cont ID  
Sent By adarroug Date 2006-08-02 Time 14:29 Rev Time 0.00
Received By adarroug Date 2006-08-02 Time 14:29 Sent To  
Notes
2006-08-02 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-22 Cont ID  
Sent By jwitmer Date 2006-06-22 Time 07:10 Rev Time 0.00
Received By jwitmer Date 2006-06-07 Time 16:42 Sent To  
Notes
2006-06-07 00:00:00TO "BOB"#17

Review Stop M MECHANICAL (A/C)
Rev No 7 Status F Date 2007-07-13 Cont ID  
Sent By tgordon Date 2007-07-13 Time 15:32 Rev Time 0.25
Received By tgordon Date 2007-07-13 Time 15:32 Sent To  
Notes
2007-07-13 15:45:55*** REVISION DENIED ***
 1) REVISED COOLING LOAD CALCULATIONS ARE CALLING FOR
 A/C SYSTEM #2 TO BE A 2 TON, REVISED MECHANICAL PLANS
 ARE CALLING FOR A/C SYSTEM #2 TO BE A 3 TON. THE TWO
 MUST COINCIDE , PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 6 Status N Date 2007-06-12 Cont ID  
Sent By tgordon Date 2007-06-12 Time 08:48 Rev Time 0.25
Received By tgordon Date 2007-06-12 Time 08:48 Sent To  
Notes
2007-06-12 08:48:45NO MECHANICAL CHANGES TO PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2007-04-09 Cont ID  
Sent By tgordon Date 2007-04-09 Time 08:14 Rev Time 0.25
Received By tgordon Date 2007-04-09 Time 08:14 Sent To  
Notes
2007-04-09 08:15:12REVISION TO MECH. PLANS PAGE M-1.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-03-29 Cont ID  
Sent By tgordon Date 2007-03-29 Time 14:03 Rev Time 0.25
Received By tgordon Date 2007-03-29 Time 14:02 Sent To  
Notes
2007-03-29 14:03:39REVISION TO MECH. PLANS PAGE M-1.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-09-15 Cont ID  
Sent By tgordon Date 2006-09-15 Time 11:29 Rev Time 0.30
Received By tgordon Date 2006-09-15 Time 11:29 Sent To  
Notes
2006-09-15 00:00:00*** PROVISO ***
 1) CLOTHES DRYER VENT MUST TERMINATE A
 MINIMUM OF 4 FT. FROM DOOR AND 10 FT.
 FROM FRESH AIR INLETS. PER 2004 FBC/M
 401.5.1 AND 501.2 .
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-08-17 Cont ID  
Sent By tgordon Date 2006-08-17 Time 11:52 Rev Time 0.45
Received By tgordon Date 2006-08-17 Time 11:52 Sent To  
Notes
2006-08-17 00:00:00*** DENIED ***
 1) AS REQUESTED IN LAST REVIEW 6-19-06
 NOTE #2, PLEASE PROVIDE FRESH AIR
 CALCULATIONS, SEE 2004 FBC/M 403.3.
 20 CFM PER OCCUPANT IS NOT A
 CALCULATION. PLEASE ALSO SHOW HOW MANY
 CFM'S. ARE TO GO TO EACH AHU SO AIR
 BALANCING MAY BE DONE PROPERLY.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-06-19 Cont ID  
Sent By tgordon Date 2006-06-19 Time 09:24 Rev Time 0.30
Received By tgordon Date 2006-06-19 Time 09:24 Sent To  
Notes
2006-06-19 00:00:00*** DENIED ***
 1) PLEASE SHOW SIZE OF MAIN TRUNK LINES,
 SUPPLY & RETURN.
  
 2) PLEASE PROVIDE FRESH AIR & FRESH AIR
 CALCULATIONS, PER 2004 FBC/M 401.2 .
  
 3) PLEASE SHOW JOB ADDRESS ON MECHANICAL
 PLANS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop P PLUMBING
Rev No 6 Status F Date 2007-07-16 Cont ID  
Sent By jleech Date 2007-07-16 Time 11:09 Rev Time 0.00
Received By jleech Date 2007-07-16 Time 11:09 Sent To  
Notes
2007-07-16 11:17:21DENIED;
 THE BAR SINK IS REQUIRED TO MEET THE FLORIDA
 ACCESSIBILITY CODE SECTIONS 11-4.24.2 THRU 11-4.24.7.
 SHOW THE DETAIL DELETED FROM APPROVED PLANS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 5 Status F Date 2007-06-15 Cont ID  
Sent By jleech Date 2007-06-15 Time 09:04 Rev Time 0.00
Received By jleech Date 2007-06-15 Time 09:04 Sent To  
Notes
2007-06-15 09:12:04REVISION DENIED;
 1. PLEASE CLOUD AND LIST REVISED SECTIONS.
 2. HEIGHT OF BAR SINK TO BE 34" TO TOP MAX. FBC-2004
 BUILDING SECTION 11-4.24.2. PLEASE SHOW DETAIL THAT WAS
 DELETED FROM APPROVED PLANS.
 3. PAGE P-2 IS MISSING. ALL ACCESSIBLITY CODES WILL BE
 CHECKED AT FINAL INSPECTION.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-10-02 Cont ID  
Sent By jleech Date 2006-10-02 Time 12:44 Rev Time 0.00
Received By jleech Date 2006-10-02 Time 12:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-09-23 Cont ID  
Sent By jleech Date 2006-09-23 Time 12:23 Rev Time 0.00
Received By jleech Date 2006-09-23 Time 12:23 Sent To  
Notes
2006-09-23 00:00:00DENIED;
 1.LAVATORY DETAIL ON PAGE P-2 IS
 CORRECT. A WALLHUNG SINK. PAGE P-1
 (PLUMBING FIXTURE SCHEDULE) LAV IS SPECT
 OUT AS A CABINET MTD. CHANGE FIXTURE
 SCHEDULE.
 2.PAGE A-1 BAR SINK DETAIL DOES NOT MEET
 HANDICAP REQUIREMENTS AND REQUIRES A
 FRONT VIEW SHOWING THE OPEN FRONT FOR
 KNEE CLEARANCE. SECTION 11-4.24.2 HEIGHT
 OF SINK TO BE 34"'S NOT 36"'S AS
 SHOWN.MAXIMUM DEPTH OF SINK IS 6 1/2"'S
 NOT 9"'S SEE SECTION 11-4.24.4
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-08-12 Cont ID  
Sent By jleech Date 2006-08-12 Time 09:04 Rev Time 0.00
Received By jleech Date 2006-08-12 Time 09:04 Sent To  
Notes
2006-08-12 00:00:00DENIED;
 1.(SECOND REQUEST) WATER RISER REQUIRED.
 SIZE ALL PIPES. WATER HAMMER ARRESTORES
 REQUIRED AT AUTOMATIC CLOTHES WASHER AND
 BAR SINK. PLEASE SPEC OUT TYPE TO BE
 USED.
 2.SHOWER MISSING FROM SANITARY RISER
 DIAGRAM.
 3.(SECOND REQUEST) LIST ON PLANS
 COMPLIANC TO FBC-2004 PLUMBING TABLE
 403.1, NOT ON RESONCE SHEET. TYPE OF
 BUSINESS, SQ. FT. AND NUMBER OF PEOPLE
 TO OCCUPY UNIT.
 4.(SECOND REQUEST) SHOW DETAIL DRAWINGS
 OF HANDICAP FIXTURES.
 A)SHOWER; NO CURB OR DOOR PERMITED
 .SHOW LOCATION OF SHOWER VALVE AND
 LOCATION OF AJUSTABLE SHOWER HEAD.
 B)BATHROOM LAYOUT NEEDS TO BE
 CHANGED. THE WATER CLOSET SHOULD BE 18"
 OF THE WALL WITH GRAB BARS IN BACK AND
 ON THE SIDE AS REQUIRED. THE LAVATORY
 SHOULD BE IN THE MIDDLE 60" FROM TOILET
 WALL TO EDGE OF LAVATORY. SEE HANDICAP
 CODE FIGURE 30E.
 C)DOOR SWING ON P-1 HAS NOT BEEN
 CHANGED TO SWING OUT. ALSO DOOR SHOULD
 BE LOCATED DIAGONAL TO THE TOILET.
 D)SHOW DETAIL OF BAR SINK. CABINET
 TO BE OPEN FRONT FOR FRONTAL APPROACH.
 SHOW SIZE AND LOCATION OF WATER
 PURIFIER, CANNOT INTERFER WITH KNEE
 CLEARANCE UNDER BAR SINK.
 E)SHOW HEIGHT REQUIREMENT OF
 DRINKING FOUNTAIN, 36" TO SPOUT.
 F)DRESSING ROOM IS REQUIRED TO HAVE
 A FIXED SEAT SEE SECTIONS 11-4.35.4 AND
 11-4.35.5. SHOW IN DETAIL.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-06-14 Cont ID  
Sent By jleech Date 2006-06-14 Time 14:47 Rev Time 0.00
Received By jleech Date 2006-06-14 Time 14:47 Sent To  
Notes
2006-06-14 00:00:00DENIED;
 1.ADD NOTE TO PAGE A-2; "IN THE REMOVAL
 OF ANY PART OF A DRAINAGE SYSTEM DEAD
 ENDS ARE NOT PERMITED. DEMO PLUMBING
 INSPECTION REQUIRED".
 2.SANITARY AND WATER RISERS DIAGRAMS
 REQUIRED ON DRAWING PER FBC-2004 CHAPTER
 1 SEC. 106.3.5.1.3. PLEASE SIZE ALL
 PIPES.
 3.MINIMUM PLUMBING FIXTURES; SHOW
 COMPIANCE ON PLANS TO MINIMUM PLUMBING
 FIXTURES REQUIRED PER. TABLE 403.1. LIST
 ON PLANS.
 4.AUTOMATIC CLOTHES WASHER DRAIN
 REQUIRED TO BE 3" SEC. 406.3 WITH A
 CLEANOUT OT 48" ABOVE FINISH FLOOR.
 5.SHOW DETAILS ON PLANS OF HANDICAP
 REQUIREMENTS AS LISTED BELOW;
 A.BATHROOM DIMENSIONS AND SHOW CLEAR
 FLOOR SPACE OF FIXTURES.
 B. SHOWER STALL REQUIRED TO MEET ALL
 REQUIREMENTS OF CHAPTER 11 SEC 11-4.21.1
 THRU 11-4.21.8.
 C.LACATORY SEC. 11-4.19.1 THRU
 11-4.19.6.
 D.TOILET SEC.11-4.16.1 THRU 11-4.16.6.
 E.GRAB BARS SEC. 11-4.17.6.
 F. DOOR SWING INTO CLEAR FLOOR SPACE
 SEC.11-4.17.5
 G.DRESSING ROOM SEC. 11-4.35.2 THRU
 11-4.35.5.
 6.MEANS OF THERMAL EXPANSION REQUIRED
 PLUMBING CODE SEC. 607.3. SHOW ON PLANS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695


Account Summary | Usage Policy | Privacy Policy