| 2006-06-13 00:00:00 | ******DENIED****** |
| | REFERENCE: FBC-2004 FUEL GAS |
| | |
| | THE FOLLOWING INFORMATION IS REQUIRED |
| | FOR PLAN REVIEW FOR A GAS PERMIT: |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE.(NOTE: THIS ENCLUDES |
| | EXISTING SYSTEM) |
| | 2. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33).(NOTE: THIS ENCLUDES EXISTING |
| | SYSTEM) |
| | 3. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4).(NOTE: THIS |
| | ENCLUDES EXISTING SYSTEM, LONGEST LENGTH |
| | METHOD USED FOR SIZING SYSTEM) |
| | |
| | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN |
| | RESUBMITTING, PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE PROVIDE ONE |
| | COPY OF ALL OLD/VOIDED SHEETS FOR |
| | REFERENCE ONLY. PLEASE SEE ATTACHED COPY |
| | OF CITY OF WEST PALM BEACH, GAS PERMIT |
| | APPLICATION REQUIREMENTS FOR FUTURE |
| | REFERENCE. |
| | |
| | END OF COMMENTS: |
| | |