Plan Review Details - Permit 06060261
Plan Review Stops For Permit 06060261
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-08-24 Cont ID  
Sent By amorse Date 2006-08-24 Time 13:17 Rev Time 0.00
Received By amorse Date 2006-08-24 Time 13:17 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-08-15 Cont ID  
Sent By amorse Date 2006-08-15 Time 08:05 Rev Time 0.00
Received By amorse Date 2006-08-15 Time 08:05 Sent To PC
Notes
2006-08-15 00:00:00 
  
 DENIED
  
 1) PROVIDE WIND DESIGN DATA ON DRAWINGS
 PER 1603.1.4 FBC
  
 2) PROVIDE MIN ROOF SHEATHING ATTACHMENT
 PER TABLE 2304.9.1 FBC
  
 3) A RECORDED COPY OF THE NOTICE OF
  
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-06-09 Cont ID  
Sent By amorse Date 2006-06-09 Time 12:11 Rev Time 0.75
Received By amorse Date 2006-06-09 Time 12:11 Sent To  
Notes
2006-06-09 00:00:00 
 *****TO KEN CONRAD FOR PRE-INSPECT*****
  
 DENIED
  
 1) ROOF PRODUCT HAS MAX DESIGN PRESSURE
 OF -85PSF WITHOUT MEAN ROOF HT.,
 BUILDING SIZE, ETC. COMPLIANCE WITH THE
 WIND LOAD CANNOT BE CALCULATED. UNDER
 LIMITATIONS ON PAGE 4 OF THE NOA ANY
 INCREASE IN THE DESIGN PRESSURES FOR
 CORNERS SHALL BE CALCULATED BY A DESIGN
 PROFESSIONAL.
  
 2) A GENERAL CONTRACTOR CANNOT INSTALL
 ROOFING OTHER THAN THAT PROVIDED UNDER
 EXECUTIVE ORDER 06-83 THAT EXPIRES
 6/12/06 WHICH ALLOWS A CGC TO INSTALL
 WOOD SHINGLES AND SHAKES OR ASPHALT AND
 FIBERGLASS SHINGLES.PER 489.113(3)B&G
  
 3) DRAWING SHOWS MUCH MORE THAN ROOFING
 BEING PERFORMED,(NEW PILASTER AND TIE
 BEAM, STRUCTURAL STEEL,ETC.) AS SUCH A
 PRE-INSPECTION IS WARRANTED AND FURTHER
 PLANS MAY BE REQUIRED TO COVER SCOPE OF
 WORK BEING PERFORMED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716