Plan Review Details - Permit 06060101
Plan Review Stops For Permit 06060101
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-08-01 Cont ID  
Sent By jwitmer Date 2006-08-01 Time 10:51 Rev Time 0.55
Received By jwitmer Date 2006-08-01 Time 10:50 Sent To  
Notes
2006-08-01 00:00:00ADD: 1801 PALM BCH LAKES# 7046
 CONT: ALLEGHENY DESIGN MANAGEMENT
 TEL: (724)845-7336
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 1) ENERGY CALCULATIONS, SIGNED AND
 SEALED.THE SIGNATURE IS A COPY NOT
 ORIGINALS.
 PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-06-21 Cont ID  
Sent By jwitmer Date 2006-06-21 Time 12:10 Rev Time 2.22
Received By jwitmer Date 2006-06-21 Time 11:51 Sent To PC
Notes
2006-06-21 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06060101
 ADD: 1801 PALM BCH LAKES# 7046
 CONT: ALLEGHENY DESIGN MANAGEMENT
 TEL: (724)845-7336
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) CODE SYNOPSIS:
 3A) CONSTRUCTION TYPE: IV HEAVY TIMBER
 CORRECT SEE TABLE 601
  
 3B) MISSING CODE 2004 FBC, EXISTING
 BUILDINGCODELEVEL OF ALTERATIONS?
 CHAPTER 3.
  
 4) DISSABLED RESTROOMS:
 11-4.22.2(1) DOORS. ALL DOORS TO
 ACCESSIBLE TOILET ROOMS SHALL COMPLY
 WITH SECTION 11-4.13 . DOORS SHALL NOT
 SWING INTO THE CLEAR FLOOR SPACE
 REQUIRED FOR ANY FIXTURE.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-07-26 Cont ID  
Sent By dpalmer Date 2006-07-26 Time 16:15 Rev Time 0.00
Received By dpalmer Date 2006-07-26 Time 15:25 Sent To  
Notes
2006-07-26 00:00:00******** UNSAT 2ND REVIEW **********
  
 ** PLEASE SEE SOME COMMENTS FROM
 PREVIOUS REVIEW WHICH STILL NEEDS TO BE
 ADDRESSED.
  
 ** PLEASE SEE NOTE BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW.
  
 1) NOTE:NO, SAME COMMENT AS THE SAME
 CALCULATIONS WERE SUBMITTED BACK.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE ENERGY COMPLIANCE
 FORMS ARE SEALED PHOTO-COPIES OF
 DESIGNER'S SIGNATURE.
 PLEASE SEE FS 481.221,471.025 WHICH
 REQUIRES AN ORIGINAL SIGNATUE.
  
 2) NOTE: NO, PLEASE SEE THE NOTE #6 AND
 #7 ON E-1 IS NOT CLEAR. PLEASE SEE CODES
 BELOW. PLEASE SEE SEPARATE SPACES, WITH
 FLR TO CEILIGN HEIGHT PARITIONS ETC.
 PLEASE PROVIDE AN ASTRONOMICAL TC IF
 USING A TC.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FBC CHAPTER 13 ,
 13-415.1ABC.1.1, .1.2,.1.3.
 PLEASE SEE THE PANEL SCHEDULE MENTIONS
 SOME SORT OF TIME CLOCK, HOWEVER NO
 DETAIL SUBMITTED FOR TYPE REQUIRED.
 PLEASE ALSO SEE LOCATIONS OF OVER RIDES
 COULD NOT BE FOUND. PLEASE ALSO INDICATE
 TIME LIMITS FOR DEVICES WHICH ARE
 CHOSEN.
  
 3) NOTE: OK.
  
 4) NOTE: OK.
  
 5) NOTE: OK.
  
 *** NEW NOTE **
  
 6) NOTE: PLEASE SEE FS 553.80(2)(B).
  
 ** IMPROTANT**
 WHEN RESUBMITING PLANS ONCE ALL REVIEWS
 ARE COMPLETED, PLEASE COMPLETELTY
 REMOVED ANY OLD/VOIDED SHEETS AND ONLY
 INSERT NEW REVISED SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
 PLEASE ONLY SUBMIT ONE COPY OF THE
 OLD/VOIDED SHEETS FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-14 Cont ID  
Sent By dpalmer Date 2006-06-14 Time 07:34 Rev Time 0.00
Received By dpalmer Date 2006-06-14 Time 06:57 Sent To  
Notes
2006-06-14 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE SEE ENERGY COMPLIANCE
 FORMS ARE SEALED PHOTO-COPIES OF
 DESIGNER'S SIGNATURE.
 PLEASE SEE FS 481.221,471.025 WHICH
 REQUIRES AN ORIGINAL SIGNATUE.
  
 2) NOTE: PLEASE SEE FBC CHAPTER 13
 ,13-415.1ABC.1.1, .1.2,.1.3.
 PLEASE SEE THE PANEL SCHEDULE MENTIONS
 SOME SORT OF TIME CLOCK, HOWEVER NO
 DETAIL SUBMITTED FOR TYPE REQUIRED.
 PLEASE ALSO SEE LOCATIONS OF OVER RIDES
 COULD NOT BE FOUND. PLEASE ALSO INDICATE
 TIME LIMITS FOR DEVICES WHICH ARE
 CHOSEN.
  
 3) PLEASE SEE COLOR CODING ON NOTE WHICH
 MENTIONS 277/480 AS BROWN, ORANGE,
 YELLOW.
 PLEASE KNOW, A HIGH LEG IS MARKED WITH
 ORANGE AND 277/480 SYSTEM DOES NOT
 CONTAIN A HIGH LEG.
 PLEASE INDICATE AS BR,PURPLE YEL.
 215.5,90.4
  
 4) NOTE: PLEASE SEE THE "LOCK ON" DEVICE
 BEING PROPOSED SHALL HAVE THE DEVICE
 USED FOR "LOCKING" A PERMANANT PART OF
 THE BREAKER. THE DEVICE CAN NOT BE A
 CLIP/SNAP ON TYPE AND IS NOT ACCEPTABLE
 TO THIS AHJ. PLEASE KNOW, IF THE BREAKER
 DOES NOT COME FROM THE MANUFACTURE WITH
 THE DEVICE MADE ONTO THE BREAKER, THEN
 EM/EXT LTS DO NOT MEET THE EXCEPTIONS
 SETFORTH ON 700.12EXPT AND ALL EM / EXT
 LTS SHALL BE CIRCUITED AHEAD OF LOCAL
 SWITCH FOR LOCAL LIGHTING IN ANY ONE
 AREA.
  
 5) NOTE: PLEASE PROVIDE LOAD
 CALCUALTIONS,AND PLEASE INDICATE THE
 CONTINUOUS LOADS AT 125%.
 215.3,230.42,220.3,220.10,220.11,220.13,
 ETC
 PLEASE SEE TRK CALCUALTIONS SHALL BE
 SHOWN FOR LIN FT ETC.
 220.12
  
 ** IMPROTANT**
 WHEN RESUBMITING PLANS ONCE ALL REVIEWS
 ARE COMPLETED, PLEASE COMPLETELTY
 REMOVED ANY OLD/VOIDED SHEETS AND ONLY
 INSERT NEW REVISED SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
 PLEASE ONLY SUBMIT ONE COPY OF THE
 OLD/VOIDED SHEETS FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-08-02 Cont ID  
Sent By nmccray Date 2006-08-02 Time 10:55 Rev Time 0.00
Received By nmccray Date 2006-08-02 Time 10:42 Sent To  
Notes
2006-08-02 00:00:00*******DENIED***************************
  
 1) LIFE SAFETY SHALL COMPLY WITH NFPA
 101, 2003 EDITION.
  
 2) 2A-10B,C RATED FIRE EXTINGUISHERS ARE
 REQUIRED AND SHALL BE MOUNTED AT
 DISTANCES NOT TO EXCEED 75' TRAVEL
 DISTANCE REQUIREMENT.
  
 3) AUDIBLE/VISUAL DEVICES REQUIRED FOR
 DUCT SMOKE DETECTORS. IF SPACE HAS FIRE
 ALARM SYSTEM, DETECTORS SHALL INITAITE A
 GENERAL FIRE ALARM IN ACCORDANCE WITH
 LOCAL REQUIREMENTS.
  
 4) SEPARATE SHOP DRAWINGS AND PERMIT
 APPLICATIONS ARE REQUIRED FOR FIRE ALARM
 AND FIRE SPRINKLER REMODEL.
  
 PLEASE ADDRESS THESE COMMENTS AND
 RE-SUBMIT FOR APPPROVAL. IF YOU HAVE ANY
 QUESTIONS PLEASE FEEL FREE TO CONTACT
 THIS OFFICE AT 561-804-4754
  
 NATE MCCRAY, ASSISTANT FIRE MARSHAL

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-06-16 Cont ID  
Sent By mwennerg Date 2006-06-16 Time 15:37 Rev Time 0.00
Received By mwennerg Date 2006-06-16 Time 15:37 Sent To  
Notes
2006-06-16 00:00:00***DENIED***
  
 1) 2A-10B,C RATED FIRE EXTINGUISHERS ARE
 REQUIRED AND SHALL BE MOUNTED AT
 DISTANCES NOT TO EXCEED 75' TRAVEL
 DISTANCE REQUIREMENT.
  
 2) SEPARATE SHOP DRAWINGS AND PERMIT
 REQUIRED FOR FIRE SPRINKLER REMODEL.
  
 3) AUDIBLE/VISUAL DEVICES REQUIRED FOR
 DUCT SMOKE DETECTORS. IF SPACE HAS FIRE
 ALARM SYSTEM, DETECTORS SHALL INITAITE A
 GENERAL FIRE ALARM IN ACCORDANCE WITH
 LOCAL REQUIREMENTS.
  
 4) LIFE SAFETY SHALL COMPLY WITH NFPA
 101, 2003 EDITION.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-19 Cont ID  
Sent By adarroug Date 2006-07-19 Time 10:06 Rev Time 0.00
Received By adarroug Date 2006-07-19 Time 10:06 Sent To  
Notes
2006-07-25 00:00:00TO "BOB"#5
2006-07-19 00:00:00WAITING FOR "BOB"-NEW "MECH" SHEETS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-21 Cont ID  
Sent By jwitmer Date 2006-06-21 Time 11:50 Rev Time 0.00
Received By jwitmer Date 2006-06-06 Time 16:49 Sent To  
Notes
2006-06-06 00:00:00TO "BOB"#8

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-07-27 Cont ID  
Sent By tgordon Date 2006-07-27 Time 11:26 Rev Time 0.30
Received By tgordon Date 2006-07-27 Time 11:26 Sent To  
Notes
2006-07-27 00:00:00*** DENIED ***
 1) SEE ELECTRICAL REVIEW NOTE #1 ENERGY
 CAL'S. NEED AN ORIGINAL SIGNATUE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-06-15 Cont ID  
Sent By tgordon Date 2006-06-15 Time 09:12 Rev Time 0.45
Received By tgordon Date 2006-06-15 Time 09:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-07-26 Cont ID  
Sent By jleech Date 2006-07-26 Time 08:25 Rev Time 0.00
Received By jleech Date 2006-07-26 Time 08:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-06-14 Cont ID  
Sent By jleech Date 2006-06-14 Time 13:13 Rev Time 0.00
Received By jleech Date 2006-06-14 Time 13:13 Sent To  
Notes
2006-06-14 00:00:00DENIED;
 1.GENERAL NOTES #2; DELETE THE WORDS
 "AIR CHAMBERS" FOR WATER HAMMER
 ARRESTORS TO BE INSTALLED PER FBC-2004
 PLUMBING SEC. 604.9.
 2.PAGE M-2, LANDLORD COMMENTS - PLUMBING
 NOTE#5 FLOOR DRAINS REQUIRED IN
 BATHROOMS. IF BATHROOMS HAVE FLOOR
 DRAINS SHOW THEM ON PLANS AS EXISTING,
 IF NOT PLEASE ADD TO RISER DIAGRAM.
 3.PAGE A-6.1 (3) ELEVATION; PLEASE SHOW
 DIMENTIONS REQUIRED TO MEET FBC-2004
 CHAPTER 11 SECTION 11-4.15.2 THRU
 11-4.15.4.4.
 4.PLEASE LIST DRINKING FOUNTAIN AND MOP
 SINK TO BE USED MODEL # AND MANUFACTURE.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  
  
  