| Plan Review Stops For Permit 06060101 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2006-08-01 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-08-01 |
Time |
10:51 |
Rev Time |
0.55 |
| Received By |
jwitmer |
Date |
2006-08-01 |
Time |
10:50 |
Sent To |
|
|
| Notes |
| 2006-08-01 00:00:00 | ADD: 1801 PALM BCH LAKES# 7046 | | | CONT: ALLEGHENY DESIGN MANAGEMENT | | | TEL: (724)845-7336 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2ND REVIEW | | | ACTION: DENIED | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | | | | 1) ENERGY CALCULATIONS, SIGNED AND | | | SEALED.THE SIGNATURE IS A COPY NOT | | | ORIGINALS. | | | PLANS, SPECIFICATIONS, REPORTS OR | | | OTHER DOCUMENTS PREPARED BY THE DESIGN | | | PROFESSIONAL AND BEING FILED FOR PUBLIC | | | RECORD SHALL HAVE THE SIGNATURE AND | | | SEAL OF THE DESIGN PROFESSIONAL AFFIXED | | | TO THE DOCUMENT. | | | FL STATE STAT: 61G15-23.002 ENGINEERS | | | FL ATATE STAT: 61G16.003 ARCHITECTS | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-06-21 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-06-21 |
Time |
12:10 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2006-06-21 |
Time |
11:51 |
Sent To |
PC |
|
| Notes |
| 2006-06-21 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 06060101 | | | ADD: 1801 PALM BCH LAKES# 7046 | | | CONT: ALLEGHENY DESIGN MANAGEMENT | | | TEL: (724)845-7336 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2) FL S S 713.13 | | | NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT BEFORE A | | | PERMIT WILL BE ISSUED. NOTE: 713.13(2) | | | IF THE WORK DESCRIBED IN THE NOTICE OF | | | COMMENCEMENT IS NOT ACTUALLY COMMENCED | | | WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. | | | | | | 3) CODE SYNOPSIS: | | | 3A) CONSTRUCTION TYPE: IV HEAVY TIMBER | | | CORRECT SEE TABLE 601 | | | | | | 3B) MISSING CODE 2004 FBC, EXISTING | | | BUILDINGCODELEVEL OF ALTERATIONS? | | | CHAPTER 3. | | | | | | 4) DISSABLED RESTROOMS: | | | 11-4.22.2(1) DOORS. ALL DOORS TO | | | ACCESSIBLE TOILET ROOMS SHALL COMPLY | | | WITH SECTION 11-4.13 . DOORS SHALL NOT | | | SWING INTO THE CLEAR FLOOR SPACE | | | REQUIRED FOR ANY FIXTURE. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2006-07-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-07-26 |
Time |
16:15 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-07-26 |
Time |
15:25 |
Sent To |
|
|
| Notes |
| 2006-07-26 00:00:00 | ******** UNSAT 2ND REVIEW ********** | | | | | | ** PLEASE SEE SOME COMMENTS FROM | | | PREVIOUS REVIEW WHICH STILL NEEDS TO BE | | | ADDRESSED. | | | | | | ** PLEASE SEE NOTE BELOW ARE TAKEN | | | DIRECTLY FROM PREVIOUS REVIEW. | | | | | | 1) NOTE:NO, SAME COMMENT AS THE SAME | | | CALCULATIONS WERE SUBMITTED BACK. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE ENERGY COMPLIANCE | | | FORMS ARE SEALED PHOTO-COPIES OF | | | DESIGNER'S SIGNATURE. | | | PLEASE SEE FS 481.221,471.025 WHICH | | | REQUIRES AN ORIGINAL SIGNATUE. | | | | | | 2) NOTE: NO, PLEASE SEE THE NOTE #6 AND | | | #7 ON E-1 IS NOT CLEAR. PLEASE SEE CODES | | | BELOW. PLEASE SEE SEPARATE SPACES, WITH | | | FLR TO CEILIGN HEIGHT PARITIONS ETC. | | | PLEASE PROVIDE AN ASTRONOMICAL TC IF | | | USING A TC. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE FBC CHAPTER 13 , | | | 13-415.1ABC.1.1, .1.2,.1.3. | | | PLEASE SEE THE PANEL SCHEDULE MENTIONS | | | SOME SORT OF TIME CLOCK, HOWEVER NO | | | DETAIL SUBMITTED FOR TYPE REQUIRED. | | | PLEASE ALSO SEE LOCATIONS OF OVER RIDES | | | COULD NOT BE FOUND. PLEASE ALSO INDICATE | | | TIME LIMITS FOR DEVICES WHICH ARE | | | CHOSEN. | | | | | | 3) NOTE: OK. | | | | | | 4) NOTE: OK. | | | | | | 5) NOTE: OK. | | | | | | *** NEW NOTE ** | | | | | | 6) NOTE: PLEASE SEE FS 553.80(2)(B). | | | | | | ** IMPROTANT** | | | WHEN RESUBMITING PLANS ONCE ALL REVIEWS | | | ARE COMPLETED, PLEASE COMPLETELTY | | | REMOVED ANY OLD/VOIDED SHEETS AND ONLY | | | INSERT NEW REVISED SHEETS INTO COMPLETE | | | SETS FOR REVIEW AND STAMPING. | | | PLEASE ONLY SUBMIT ONE COPY OF THE | | | OLD/VOIDED SHEETS FOR REFERENCE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-06-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-06-14 |
Time |
07:34 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-06-14 |
Time |
06:57 |
Sent To |
|
|
| Notes |
| 2006-06-14 00:00:00 | *** UNSAT *** | | | | | | 1) NOTE: PLEASE SEE ENERGY COMPLIANCE | | | FORMS ARE SEALED PHOTO-COPIES OF | | | DESIGNER'S SIGNATURE. | | | PLEASE SEE FS 481.221,471.025 WHICH | | | REQUIRES AN ORIGINAL SIGNATUE. | | | | | | 2) NOTE: PLEASE SEE FBC CHAPTER 13 | | | ,13-415.1ABC.1.1, .1.2,.1.3. | | | PLEASE SEE THE PANEL SCHEDULE MENTIONS | | | SOME SORT OF TIME CLOCK, HOWEVER NO | | | DETAIL SUBMITTED FOR TYPE REQUIRED. | | | PLEASE ALSO SEE LOCATIONS OF OVER RIDES | | | COULD NOT BE FOUND. PLEASE ALSO INDICATE | | | TIME LIMITS FOR DEVICES WHICH ARE | | | CHOSEN. | | | | | | 3) PLEASE SEE COLOR CODING ON NOTE WHICH | | | MENTIONS 277/480 AS BROWN, ORANGE, | | | YELLOW. | | | PLEASE KNOW, A HIGH LEG IS MARKED WITH | | | ORANGE AND 277/480 SYSTEM DOES NOT | | | CONTAIN A HIGH LEG. | | | PLEASE INDICATE AS BR,PURPLE YEL. | | | 215.5,90.4 | | | | | | 4) NOTE: PLEASE SEE THE "LOCK ON" DEVICE | | | BEING PROPOSED SHALL HAVE THE DEVICE | | | USED FOR "LOCKING" A PERMANANT PART OF | | | THE BREAKER. THE DEVICE CAN NOT BE A | | | CLIP/SNAP ON TYPE AND IS NOT ACCEPTABLE | | | TO THIS AHJ. PLEASE KNOW, IF THE BREAKER | | | DOES NOT COME FROM THE MANUFACTURE WITH | | | THE DEVICE MADE ONTO THE BREAKER, THEN | | | EM/EXT LTS DO NOT MEET THE EXCEPTIONS | | | SETFORTH ON 700.12EXPT AND ALL EM / EXT | | | LTS SHALL BE CIRCUITED AHEAD OF LOCAL | | | SWITCH FOR LOCAL LIGHTING IN ANY ONE | | | AREA. | | | | | | 5) NOTE: PLEASE PROVIDE LOAD | | | CALCUALTIONS,AND PLEASE INDICATE THE | | | CONTINUOUS LOADS AT 125%. | | | 215.3,230.42,220.3,220.10,220.11,220.13, | | | ETC | | | PLEASE SEE TRK CALCUALTIONS SHALL BE | | | SHOWN FOR LIN FT ETC. | | | 220.12 | | | | | | ** IMPROTANT** | | | WHEN RESUBMITING PLANS ONCE ALL REVIEWS | | | ARE COMPLETED, PLEASE COMPLETELTY | | | REMOVED ANY OLD/VOIDED SHEETS AND ONLY | | | INSERT NEW REVISED SHEETS INTO COMPLETE | | | SETS FOR REVIEW AND STAMPING. | | | PLEASE ONLY SUBMIT ONE COPY OF THE | | | OLD/VOIDED SHEETS FOR REFERENCE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2006-08-02 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2006-08-02 |
Time |
10:55 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2006-08-02 |
Time |
10:42 |
Sent To |
|
|
| Notes |
| 2006-08-02 00:00:00 | *******DENIED*************************** | | | | | | 1) LIFE SAFETY SHALL COMPLY WITH NFPA | | | 101, 2003 EDITION. | | | | | | 2) 2A-10B,C RATED FIRE EXTINGUISHERS ARE | | | REQUIRED AND SHALL BE MOUNTED AT | | | DISTANCES NOT TO EXCEED 75' TRAVEL | | | DISTANCE REQUIREMENT. | | | | | | 3) AUDIBLE/VISUAL DEVICES REQUIRED FOR | | | DUCT SMOKE DETECTORS. IF SPACE HAS FIRE | | | ALARM SYSTEM, DETECTORS SHALL INITAITE A | | | GENERAL FIRE ALARM IN ACCORDANCE WITH | | | LOCAL REQUIREMENTS. | | | | | | 4) SEPARATE SHOP DRAWINGS AND PERMIT | | | APPLICATIONS ARE REQUIRED FOR FIRE ALARM | | | AND FIRE SPRINKLER REMODEL. | | | | | | PLEASE ADDRESS THESE COMMENTS AND | | | RE-SUBMIT FOR APPPROVAL. IF YOU HAVE ANY | | | QUESTIONS PLEASE FEEL FREE TO CONTACT | | | THIS OFFICE AT 561-804-4754 | | | | | | NATE MCCRAY, ASSISTANT FIRE MARSHAL |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2006-06-16 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-06-16 |
Time |
15:37 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-06-16 |
Time |
15:37 |
Sent To |
|
|
| Notes |
| 2006-06-16 00:00:00 | ***DENIED*** | | | | | | 1) 2A-10B,C RATED FIRE EXTINGUISHERS ARE | | | REQUIRED AND SHALL BE MOUNTED AT | | | DISTANCES NOT TO EXCEED 75' TRAVEL | | | DISTANCE REQUIREMENT. | | | | | | 2) SEPARATE SHOP DRAWINGS AND PERMIT | | | REQUIRED FOR FIRE SPRINKLER REMODEL. | | | | | | 3) AUDIBLE/VISUAL DEVICES REQUIRED FOR | | | DUCT SMOKE DETECTORS. IF SPACE HAS FIRE | | | ALARM SYSTEM, DETECTORS SHALL INITAITE A | | | GENERAL FIRE ALARM IN ACCORDANCE WITH | | | LOCAL REQUIREMENTS. | | | | | | 4) LIFE SAFETY SHALL COMPLY WITH NFPA | | | 101, 2003 EDITION. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-07-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-07-19 |
Time |
10:06 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-07-19 |
Time |
10:06 |
Sent To |
|
|
| Notes |
| 2006-07-25 00:00:00 | TO "BOB"#5 | | 2006-07-19 00:00:00 | WAITING FOR "BOB"-NEW "MECH" SHEETS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-06-21 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-06-21 |
Time |
11:50 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2006-06-06 |
Time |
16:49 |
Sent To |
|
|
| Notes |
| 2006-06-06 00:00:00 | TO "BOB"#8 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2006-07-27 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-07-27 |
Time |
11:26 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2006-07-27 |
Time |
11:26 |
Sent To |
|
|
| Notes |
| 2006-07-27 00:00:00 | *** DENIED *** | | | 1) SEE ELECTRICAL REVIEW NOTE #1 ENERGY | | | CAL'S. NEED AN ORIGINAL SIGNATUE. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2006-06-15 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-06-15 |
Time |
09:12 |
Rev Time |
0.45 |
| Received By |
tgordon |
Date |
2006-06-15 |
Time |
09:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2006-07-26 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-07-26 |
Time |
08:25 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-07-26 |
Time |
08:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2006-06-14 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-06-14 |
Time |
13:13 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-06-14 |
Time |
13:13 |
Sent To |
|
|
| Notes |
| 2006-06-14 00:00:00 | DENIED; | | | 1.GENERAL NOTES #2; DELETE THE WORDS | | | "AIR CHAMBERS" FOR WATER HAMMER | | | ARRESTORS TO BE INSTALLED PER FBC-2004 | | | PLUMBING SEC. 604.9. | | | 2.PAGE M-2, LANDLORD COMMENTS - PLUMBING | | | NOTE#5 FLOOR DRAINS REQUIRED IN | | | BATHROOMS. IF BATHROOMS HAVE FLOOR | | | DRAINS SHOW THEM ON PLANS AS EXISTING, | | | IF NOT PLEASE ADD TO RISER DIAGRAM. | | | 3.PAGE A-6.1 (3) ELEVATION; PLEASE SHOW | | | DIMENTIONS REQUIRED TO MEET FBC-2004 | | | CHAPTER 11 SECTION 11-4.15.2 THRU | | | 11-4.15.4.4. | | | 4.PLEASE LIST DRINKING FOUNTAIN AND MOP | | | SINK TO BE USED MODEL # AND MANUFACTURE. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 | | | | | | | | | |
|
|