Plan Review Details - Permit 06051267
Plan Review Stops For Permit 06051267
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2006-06-06 Cont ID  
Sent By lursu Date 2006-06-06 Time 10:09 Rev Time 0.00
Received By amorse Date 2006-06-06 Time 13:49 Sent To  
Notes
2006-06-06 00:00:00NEW SITE ADDRESS HAD BEEN ASSIGNED TO
 THIS VACANT PARCEL AS 930 29TH ST .

Review Stop AD ADDRESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By ssherman Date 2006-06-02 Time 08:25 Sent To  
Notes
2006-06-02 00:00:00NEED NUMERICAL ADDRESS FOR THIS PARCEL

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-08-25 Cont ID  
Sent By amorse Date 2007-08-25 Time 10:48 Rev Time 0.00
Received By amorse Date 2007-08-25 Time 10:48 Sent To PC
Notes
2007-08-25 10:49:54 
 PASSED
  
 REVISION FOR SGD, SH WINDOWS AND METAL ENTRANCE DOOR

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-07-31 Cont ID  
Sent By amorse Date 2006-07-31 Time 15:52 Rev Time 0.00
Received By amorse Date 2006-07-31 Time 15:52 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-06-23 Cont ID  
Sent By amorse Date 2006-06-23 Time 13:50 Rev Time 1.50
Received By amorse Date 2006-06-23 Time 13:50 Sent To PC
Notes
2006-06-23 00:00:00 
  
 DENIED
  
 1) NOTE 7(E)ON PREVIOUS REVIEW NOT
 ADDRESSED, PROVIDE UPDATED NOA THAT
 BELONGS WITH FL#183 FOR GAF SHINGLES
 (04-0820.01)
  
 2) NOTE 9 ON PREVIOUS REVIEW NOT
 ADDRESSED, PROVIDE A NOTE ON DETAIL OF
 FRAMED BUILDOUTS FOR APPLICATION OF
 HARDIEPLANK SIDING.SHOW HOW BUILDOUTS
 ARE ATTACHED, IN REAR TO BLOCK WALL IN
 FRONT TO SHEATHED GABLE END TRUSS AND
 HOW THEY ARE CONSTRUCTED (EG.2X4- 16" OC
 WITH 5/8" PLYWOOD SHEATHING, ETC.)
  
 3) IF LISTING PRODUCT APPROVALS MAKE
 CORRECTIONS TO LIST AND STATE
 "REVIEWED AND APPROVED FOR USE" AS WELL
 AS SIGNITURE
  
 ********PROVISO******
 SUBMIT ENGINEERED TRUSS DRAWINGS FOR
 REVIEW PRIOR TO INSTALLATION
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-06-13 Cont ID  
Sent By amorse Date 2006-06-13 Time 14:22 Rev Time 2.00
Received By amorse Date 2006-06-13 Time 14:22 Sent To PC
Notes
2006-06-13 00:00:00 
  
 DENIED
  
 1) BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SETS OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION.
  
 2) THE CLAIMED VALUATION ON THE PERMIT
 APPLICATION IS LOW. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT
 COST EXCLUDING LAND VALUE. OUR VALUATION
 REFERENCE IS ICC (BVD), MARSHALL-SWIFT
 AND MEANS COST ANALYSIS SERVICES PER
 108.3 FBC* VALUE WILL BE ADJUSTED
  
 3) THE STATE OF FLORIDA REQUIRES
 COLLECTION OF A RADON SURCHARGE ON ALL
 NEW CONSTRUCTION COMPUTED ON UNDER ROOF
 FLOOR SPACE PER 10D-91 FAC VALUE WILL BE
 ADJUSTED
  
 4) SUBMIT ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT
 APPLICATION OR BEFORE INSTALLATION
  
 5) PROVIDE ENERGY CALC'S AND MANUEL J
  
 6)THOSE PRODUCTS WHICH ARE REGULATED BY
 DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 7) THE FOLLOWING IS A LIST OF REQUIRED
 INFORMATION IN REGUARDS TO THE PRODCT
 APPROVALS
  
 A) PRODUCT APPROVAL FOR SGD AND FIXED
 WINDOWS ARE NOT AS YET APPROVED BY THE
 STATE.
 B) NO USAGE OF PRODUCT APPROVALS FOR PGT
 MULLIONS OR TRACO FIXED WINDOWS CAN BE
 FOUND, NOT LISTED ON WINDOW SCHEDULE,
 ONLY POSSIBLE APPLICATION AS TRANSOM FOR
 DOORS ON REAR ELEVATION?
 C) PRODUCT APPROVAL FOR METALTECH
 SHUTTERS HAS NO DRAWING SUBMITTED
 D) PRODUCT APPROVAL FOR CAST-CRETE
 LINTELS HAS CORRECT FLORIDA COVER SHEET
 BUT THE NOA IS FOR 4,6 AND 12" LINTELS
 SUBMIT NOA FOR 8" AS REQUIRED BY
 DRAWINGS. (03-0605.05)
 E) PRODUCT APPROVAL FOR GAF SHINGLES HAS
 CORRECT COVER BUT OUTDATED NOA, SUBMIT
 CORRECT NOA.(04-0820.01)
 F) PRODUCT APPROVALS FOR PGT SH WINDOWS
 REQUIRE UPDATED COVER AND NOA
 G) PRODUCT APPROVALS FOR JELD-WEN DOORS
 ARE FOR DOUBLE DOORS WITHOUT GLAZING, IF
 THIS IS FOR ENTRY DOOR THE SCHEDULE ON
 A/1 STATES GLAZED SINGLE DOOR
 H) NO PRODUCT APPROVAL WAS SUBMITTED FOR
 HARDIPLANK SIDING
 I) ALL THAT IS REQUIRED FOR WOOD
 CONNECTORS IS SCHEDULE WITH CONNECTOR
 TYPES USED, FL#S, ETC. AS SHOWN ON TRUSS
 ANCHOR SCHEDULE ON A/3
  
 8) DETAIL H AS CALLED FOR ON S/1 AND
 SHOWN ON S/2 DETAILS A WOOD GABLE END
 BUT SECTION "B" ON A/4 SHOWS CONCRETE
 PLEASE CLARIFY
  
 9) DETAIL THE ATTACHMENT OF THE
 HARDIPLANK SIDING IF ATTACHED TO
 CONCRETE OR BLOCK GABLE ENDS
  
 10) A RERECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO A
 PERMIT BEING ISSUED. PER 713.13(2) F.S.
 IF THE IMPROVEMENT DESCRIBED IN THE NOC
 HAS NOT COMMENCED WITHIN 90 DAYS OF
 RECORDING THE NOTICE IS VOID
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-06-10 Cont ID  
Sent By dpalmer Date 2006-06-10 Time 14:23 Rev Time 0.00
Received By dpalmer Date 2006-06-10 Time 14:04 Sent To M
Notes
2006-06-10 00:00:00**** PLANS REDLINED.
  
  
 ** SD'S STILL BE SHOWN NOT CIRCUITED TO
 AN AFCI PROTECTED CIRCUIT AS REQUIRED
 PER 210.12B 2002 NEC.
 PLEASE SEE EITHER CIRCUIT #2 BECOMES
 AFCI, OR SD'S SHALL BE MOVED TO ANOTHER
 AFCI CIRCUIT.
  
 ** PLEASE SEE POSSIBLE MISSING RECEPT
 PER 210.52 ON WALL OFF KITCHEN.
  
 ** PLEASE SEE RECEPT IN BEDRM MISSING
 CIRCUIT.
  
 *** PLEASE KNOW, THE ABOVE SHALL BE
 REVISED IF AND WHEN REVISING PLANS
 BEFORE ROUGH ELECTRICAL INSPECTION.

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2006-06-02 Cont ID  
Sent By ptjomsto Date 2006-06-02 Time 09:38 Rev Time 0.00
Received By ptjomsto Date 2006-06-02 Time 09:38 Sent To  
Notes
2006-06-02 00:00:00HISTORIC APPROVED BY J PAPA

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-08-23 Cont ID  
Sent By adarroug Date 2007-08-23 Time 15:18 Rev Time 0.00
Received By adarroug Date 2007-08-23 Time 15:18 Sent To B
Notes
2007-08-23 15:19:10TO "AMORSE" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-05-10 Cont ID  
Sent By adarroug Date 2007-05-10 Time 16:03 Rev Time 0.00
Received By adarroug Date 2007-05-10 Time 16:03 Sent To B
Notes
2007-05-10 16:03:39TO "LMARTINEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-07-31 Cont ID  
Sent By adarroug Date 2006-07-31 Time 11:30 Rev Time 0.00
Received By adarroug Date 2006-07-31 Time 11:30 Sent To B
Notes
2006-07-31 00:00:00TO "AMORSE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-22 Cont ID  
Sent By adarroug Date 2006-06-22 Time 10:56 Rev Time 0.00
Received By adarroug Date 2006-06-22 Time 10:56 Sent To B
Notes
2006-06-22 00:00:00TO "AMORSE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-06-13 Time   Rev Time 0.00
Received By adarroug Date 2006-06-05 Time 10:31 Sent To  
Notes
2006-06-05 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-06-12 Cont ID  
Sent By hmoser Date 2006-06-12 Time 11:10 Rev Time 0.00
Received By hmoser Date 2006-06-12 Time 13:15 Sent To B
Notes
2006-06-12 00:00:00PASS PRIVISO
 PLEASE REFER TO SECTION 402.301
 BATHROOMS.2004 FBC(M)
 PLEASE REFER TO SECTION M1411.3.1
 AUXILIARY AND SECONDARY SYSTEMS. 2004
 FBC RESIDENTIAL CODE.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-06-12 Cont ID  
Sent By jleech Date 2006-06-12 Time 07:47 Rev Time 0.00
Received By jleech Date 2006-06-12 Time 07:47 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2006-06-10 Cont ID  
Sent By mmclean Date 2006-06-10 Time 13:00 Rev Time 0.00
Received By mmclean Date 2006-06-10 Time 13:00 Sent To E
Notes
2006-06-10 00:00:00ROUTED ON THE SFR RACK (ELECTRICAL)
  
 SEC 94-303 MECHANICAL/POOL
 EQUIPMENT/GENERATOR MAY NOT PROJECT MORE
 THAN FOUR FEET INTO A SETBACK.
  