| 2006-08-11 00:00:00 | *** UNSAT 2ND REVIEW **** |
| | |
| | ** PLEASE SEE COMMENTS BELOW WHICH STILL |
| | NEED TO BE ADDRESSED. |
| | NOTES AR TAKEN DIRECTLY FROM THE |
| | PREVIOUS REVIEW. |
| | |
| | 1) NOTE:NO, PLEASE SEE PLANS/DRAWINGS |
| | SUBMITTED ARE NOT ACCEPTABLE FOR MIN |
| | REQUIRED PLANS/DRAWING WHICH SHALL BE |
| | DONE IN "DRAFTMAN QUALITY". |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE FBCADMINISTRATIVE |
| | SECTION 106.1.3 WHICH REQUIRES PLANS TO |
| | BE SUBMITTED WITH MIN 1/8" SCALE AND |
| | CLARITY. ETC. |
| | PLEASE SEE ONE OF THE SHEETS SUBMITTED |
| | ARE SIGNED, DATED AND SEALED ON THE BACK |
| | OF THE SHEET WHICH IS BLANK.??? |
| | PLEASE SEE FS 471.025 |
| | |
| | 2) NOTE;?? RESPONSE ON CITY'S COMMENTS |
| | MENTIONS RELOCATE, HOWEVER PLANS |
| | MENTIONS TO ADDED NEW WASHER AND DRYER. |
| | PLEASE SEE CONDUCTOR SIZES ARE NOT |
| | MENTIONED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE WASHER AND DRYER |
| | SEEM TO BE MOVED TO SOME SORT OF NEW |
| | ROOM, HOWEVER IS UNCLEAR. |
| | PLEASE VERIFY IF THESE ARE JUST EXISITNG |
| | RELOCATED OR NEW? IF NEW PLEASE PROVIDE |
| | LOAD CALCULATIONS FOR ADDED LOADS TO THE |
| | THE EXISTING SERVICE AND INDICATE SIZE |
| | OF EXISTING SERVICE/PANEL. |
| | 215.5,220 |
| | |
| | 3) NOTE:NO?? WHERE IS LT REQUIRED? |
| | NEW? EXISTING? |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE IF THIS IS A NEW |
| | ROOM, A LIGHTING OUTLET AND CONTROL |
| | SHALL BE REQUIRED. |
| | 210.70 |
| | |
| | 4) NOTE: OK, HOWEVER PLEASE BE SURE |
| | APPLICATION IS NOTARIZED BEFORE |
| | RESUBMITTING. |
| | |
| | ** PREIVOUS REVIEW NOTE |
| | PLEASE SEE PERMIT APPLICATION |
| | WAS NOT SIGNED BY THE CONTRACTOR. |
| | PLEASE DO SO. |
| | |
| | ** NEW NOTE ** |
| | |
| | 5) NOTE: PLEASE SEE FS 553.80 (2)(B) |
| | WITH RESPECTTO DESIGN PROFESSIONALS |
| | AND REPEAT COMMENTS. |
| | |
| | |
| | ** PLEASE KNOW, ONE SET OF THE SUBMITTED |
| | SHEETS ARE BEING RETAINED. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |