| 2006-06-20 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 06051259 |
| | ADD: 5407 N HAVERHILL RD |
| | CONT: GABCO |
| | TEL: (561)644-1434 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1STREVIEW |
| | ACTION: DENIED |
| | --- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 1) AS STATED BY OTHER REVIEWERS, THE |
| | LICENSE HOLDER GABCO REMODELING IS A |
| | GENERAL CONTRACTOR AND NOT LICENSED TO |
| | INSTALL COOLERS AND FREEZERS. THE PLANS |
| | ONLY INDICATE COOLER AND FREEZERS NO |
| | OTHER WORK IS SHOWN. |
| | |
| | 2603.4.1.2 COOLER AND FREEZER WALLS. |
| | FOAM PLASTIC INSTALLED IN A MAXIMUM |
| | THICKNESS OF 10 INCHES (254 MM) IN |
| | COOLER AND FREEZER WALLS SHALL: |
| | 1.HAVE A FLAME SPREAD INDEX OF 25 |
| | OR LESS AND A SMOKE-DEVELOPED INDEX OF |
| | NOT MORE THAN 450, WHERE TESTED IN A |
| | MINIMUM 4 INCH (102 MM) THICKNESS. |
| | 2.HAVE FLASH IGNITION AND |
| | SELF-IGNITION TEMPERATURES OF NOT LESS |
| | THAN 600?F AND 800?F (316?C AND 427?C), |
| | RESPECTIVELY. |
| | 3.HAVE A COVERING OF NOT LESS THAN |
| | 0.032-INCH (0.8 MM) ALUMINUM OR |
| | CORROSION-RESISTANT STEEL HAVING A BASE |
| | METAL THICKNESS NOT LESS THAN 0.0160 |
| | INCH (0.4 MM) AT ANY POINT. |
| | 4.BE PROTECTED BY AN AUTOMATIC |
| | SPRINKLER SYSTEM. WHERE THE COOLER OR |
| | FREEZER IS WITHIN A BUILDING, BOTH THE |
| | COOLER OR FREEZER AND THAT PART OF THE |
| | BUILDING IN WHICH IT IS LOCATED SHALL BE |
| | SPRINKLERED. |
| | |
| | 2603.4.1.3 WALK-IN COOLERS. |
| | IN NONSPRINKLERED BUILDINGS, FOAM |
| | PLASTIC HAVING A THICKNESS THAT DOES NOT |
| | EXCEED 4 INCHES (102 MM) AND A MAXIMUM |
| | FLAME SPREAD INDEX OF 75 IS PERMITTED IN |
| | WALK-IN COOLERS OR FREEZER UNITS WHERE |
| | THE AGGREGATE FLOOR AREA DOES NOT EXCEED |
| | 400 SQUARE FEET (37 M 2 ) AND THE FOAM |
| | PLASTIC IS COVERED BY A METAL FACING NOT |
| | LESS THAN 0.032-INCH-THICK (0.81 MM) |
| | ALUMINUM OR CORROSION-RESISTANT STEEL |
| | HAVING A MINIMUM BASE METAL THICKNESS OF |
| | 0.016 INCH (0.41 MM). A THICKNESS OF UP |
| | TO 10 INCHES IS PERMITTED WHERE |
| | PROTECTED BY A THERMAL BARRIER. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | |