Plan Review Details - Permit 06051230
Plan Review Stops For Permit 06051230
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-08-17 Cont ID  
Sent By alange Date 2006-08-17 Time 13:12 Rev Time 0.75
Received By alange Date 2006-08-17 Time 13:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-08-11 Cont ID  
Sent By alange Date 2006-08-11 Time 14:16 Rev Time 1.00
Received By alange Date 2006-08-11 Time 14:16 Sent To  
Notes
2006-08-11 00:00:00DENIED
 FOURTH REVIEW, SAME COMMENTS...
  
 2.ALL PRODUCT APPROVALS SHALL HAVE THE
 FOLLOWING STATE PRODUCT APPROVAL
 ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 3. THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 4.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE . A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-08-07 Cont ID  
Sent By alange Date 2006-08-07 Time 10:50 Rev Time 0.75
Received By alange Date 2006-08-07 Time 10:43 Sent To  
Notes
2006-08-07 00:00:00DENIED
 THIRD REVIEW, SAME COMMENTS...
  
 2.ALL PRODUCT APPROVALS SHALL HAVE THE
 FOLLOWING STATE PRODUCT APPROVAL
 ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 3. THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 4.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE . A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-07-24 Cont ID  
Sent By alange Date 2006-07-24 Time 09:51 Rev Time 1.00
Received By alange Date 2006-07-24 Time 09:51 Sent To  
Notes
2006-07-24 00:00:00DENIED
  
 1.SUBMIT TWO COPIES PRODUCT APPROVALS
 FOR WINDOWS, ROOFING AND GLASS BLOCK.
  
 2.ALL PRODUCT APPROVALS SHALL HAVE THE
 FOLLOWING STATE PRODUCT APPROVAL
 ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 3. THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 4.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE . A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-06-21 Cont ID  
Sent By alange Date 2006-06-21 Time 09:03 Rev Time 1.00
Received By alange Date 2006-06-21 Time 09:03 Sent To  
Notes
2006-06-21 00:00:00DENIED
  
 1.SUBMIT PRODUCT APPROVALS FOR
 WINDOWS, ROOFING AND GLASS BLOCK.
  
 2.ALL PRODUCT APPROVALS SHALL HAVE THE
 FOLLOWING STATE PRODUCT APPROVAL
 ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 3. THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 4.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE . A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-08-03 Cont ID  
Sent By dpalmer Date 2006-08-03 Time 12:52 Rev Time 0.00
Received By dpalmer Date 2006-08-03 Time 12:46 Sent To B
Notes
2006-08-03 00:00:00CONSULTING "ENGINEERS" HAS BEEN CROSSED
 OUT.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-07-20 Cont ID  
Sent By dpalmer Date 2006-07-20 Time 15:38 Rev Time 0.00
Received By dpalmer Date 2006-07-20 Time 13:47 Sent To B
Notes
2006-07-20 00:00:00** UNSAT **
 ]
 ** PLEASE KNOW, PLANS ARE NOW BEING
 SUBMITTED FOR REVIEW.
 PLEASE SEE COMMENTS BELOW.
  
 1) NOTE: PLEASE CORRELATE ALL CIRCUITING
 ON PLANS WITH PANEL SCHEDULE SUBMITTED.
 PLEASE SEE AHU SHOWN ON THE SAME AS
 DRYER.
 PLEASE SEE BATH NOT SHOWING CIRCUIT.
 PLEASE SEE WP GFI. ETC
 PLEASE SEE REDLINED PLANS.
  
 2) NOTE: PLEASE SEE MISSING GFI RECEPT
 FOR A/C CU. 210.63
  
 3) NOTE: PLEASE SEE THAT PANEL SCHEDULE
 PROVIDES LABLELING SPECIFIC TO ROOMS AND
 AREAS IN WHICH THEY FEED.
 IE: BEDRM LTS, HALL LTS ETC.
 408.4
  
 4) NOTE: PLEASE SEE CIRCUITING FOR
 DISHWASHER / DISPOSAL. PLEASE SEE BOTH
 SEEM TO BE FEEDING THE SAME DEVICE ,
 HOWEVER EACH CIRCUIT IS SHOWN AS A SP
 BRKR. PLEASE SEE A SINGLE DEVICE, IF FED
 BY TWO CIRCUITS SHALL BE ON A 2-POLE
 BRKR.
 PLEASE ADJUST.
 210.23,210.4
  
 5) NOTE: PLEASE KNOW, IF ENGINEERING
 FIRM IS BEING DECLARED, PLEASE OBTAIN
 AND PLCE CERITIFICATE OF AUTHORIZATION #
 ON TITLE BLOCKS.
 61G15-23.002, FS 471.023
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-14 Cont ID  
Sent By dpalmer Date 2006-06-14 Time 19:05 Rev Time 0.00
Received By dpalmer Date 2006-06-14 Time 18:55 Sent To B
Notes
2006-06-14 00:00:00******** UNSAT *********
  
 1) NOTE: PLEASE SEE PLAN COVER SHEETS
 MENTIONS NEW ALTERATIONS AND ADDITION,
 YET PLANS DO NOT INDICATE THE SAME??
 PLEASE SEE PERMIT APPLICATION ONLY
 MENTIONS FIRE RESTORATION.?
 PLEASE CORRELATE SCOPE OF WORK FOR
 PROJECT.
 215.5
  
 2) NOTE: PLEASE SUBMIT ELECTRICAL
 DETAIL/PLAN FOR ELECTRICAL WORK IN
 AFFECTED AREA AND OR NEW WORK BEING DONE
 INCLUDING ALL ELECTRICAL PER THE 2002
 NEC, NFPA-72
 PLEASE SEE PLANS SHALL REFLECT CODES IN
 EFFECT.
 215.5,
 FBC 106.2.1
  
 ** PLEASE SEE MECH COMMENTS FOR MIN
 ENERGY CALCS TO BE PROVIDED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-08-15 Cont ID  
Sent By adarroug Date 2006-08-15 Time 11:48 Rev Time 0.00
Received By adarroug Date 2006-08-15 Time 11:48 Sent To B
Notes
2006-08-15 00:00:00TO "ALANGE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-08-11 Cont ID  
Sent By adarroug Date 2006-08-11 Time 09:38 Rev Time 0.00
Received By adarroug Date 2006-08-11 Time 09:38 Sent To B
Notes
2006-08-11 00:00:00TO "ALANGE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-08-01 Cont ID  
Sent By adarroug Date 2006-08-01 Time 15:25 Rev Time 0.00
Received By adarroug Date 2006-08-01 Time 15:25 Sent To E
Notes
2006-08-01 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-07-19 Cont ID  
Sent By adarroug Date 2006-07-19 Time 11:06 Rev Time 0.00
Received By adarroug Date 2006-07-19 Time 11:06 Sent To E
Notes
2006-07-19 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-07-12 Cont ID  
Sent By adarroug Date 2006-07-12 Time 15:09 Rev Time 0.00
Received By adarroug Date 2006-07-12 Time 15:09 Sent To Z
Notes
2006-07-12 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-12 Cont ID  
Sent By adarroug Date 2006-06-12 Time 10:21 Rev Time 0.00
Received By adarroug Date 2006-06-12 Time 10:16 Sent To E
Notes
2006-06-12 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-21 Cont ID  
Sent By alange Date 2006-06-21 Time 09:07 Rev Time 0.00
Received By alange Date 2006-05-31 Time 14:21 Sent To  
Notes
2006-05-31 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-06-15 Cont ID  
Sent By tgordon Date 2006-06-15 Time 09:19 Rev Time 0.15
Received By tgordon Date 2006-06-15 Time 09:19 Sent To P
Notes
2006-06-15 00:00:00NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-06-19 Cont ID  
Sent By jleech Date 2006-06-19 Time 08:29 Rev Time 0.00
Received By jleech Date 2006-06-19 Time 08:29 Sent To B
Notes
2006-06-19 00:00:00NOT ENOUGH INFORMATION TO DO A
 PLUMBING PLAN REVIEW.
 1.IS NEW FLOOR PLAN THE SAME AS OLD?
 2.SANITARY RISER DIAGRAM REQUIRED
 SHOWING THE SCOOP OF PLUMBING WORK TO BE
 DONE.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status N Date 2006-07-18 Cont ID  
Sent By mmclean Date 2006-07-18 Time 14:18 Rev Time 0.00
Received By mmclean Date 2006-07-18 Time 14:18 Sent To I
Notes
2006-07-18 00:00:00NO REVIEW REQUIRED FOR ZONING, NO CHANGE
 IN THE EXISTING FOOTPRINT OF STRUCTURE
 SHEET A-1

Review Stop Z ZONING
Rev No 1 Status F Date 2006-06-10 Cont ID  
Sent By mmclean Date 2006-06-10 Time 10:50 Rev Time 0.00
Received By mmclean Date 2006-06-10 Time 10:50 Sent To I
Notes
2006-06-10 00:00:00DENIED,
 1. ALL WORK SEEMS TO BE INTERIOR NO
 CHANGE TO STRUCTURE SETBACKS.
 2. NEED TO INDICATE ON TWO COPY OF
 CURRENT SURVEY IF THE PROPOSED WORK
 CHANGES THE EXISTING FOOTPRINT OF
 STRUCTURE.
 3. IF THE SAME FOOTPRINT, PLEASE
 INDICATE ON SURVEY
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720