Plan Review Details - Permit 06051228
Plan Review Stops For Permit 06051228
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-07-13 Cont ID  
Sent By rmcdouga Date 2006-07-13 Time 10:10 Rev Time 0.00
Received By rmcdouga Date 2006-07-13 Time 10:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-06-21 Cont ID  
Sent By rmcdouga Date 2006-06-21 Time 13:00 Rev Time 0.00
Received By rmcdouga Date 2006-06-21 Time 12:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-07-15 Cont ID  
Sent By dpalmer Date 2006-07-15 Time 13:09 Rev Time 0.00
Received By dpalmer Date 2006-07-15 Time 12:41 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-12 Cont ID  
Sent By dpalmer Date 2006-06-12 Time 07:31 Rev Time 0.00
Received By dpalmer Date 2006-06-12 Time 07:12 Sent To  
Notes
2006-06-12 00:00:00**** UNSAT ****
  
 PLANS ARE GENERALLY IN GOOD SHAPE,
 HOWEVER PLEASE SEE THE FOLLOWING FOR
 SOME CORRECTIONS.
  
 1) NOTE: PLEASE SEE RISER MENTIONS, FOR
 CONDUCTORS TO BE VERIFIED ON SITE. THIS
 SHOULD BE DONE AT THIS TIME.
 PLEASE VERIFY THE #2 SHOWN FOR THE
 EQUIPMENT GROUNDING CONDUCTOR. THIS SIZE
 SEEMS MUCH LARGER THAN WHAT WOULD BE
 REQUIRED. IF SHOWN AS THIS SIZE, THIS IS
 WHAT WILL BE REQUIRED. EXISTING
 CONDITION TO BE VERIFIED.
 215.5,250.122,310.16.240.4
  
 2) NOTE: PLEASE SEE FBC
 13-415.1.ABC.1.1,.1.2,.1.3 FOR ALL AREAS
 AND LOCATIONS WHICH REQUIRE CONTROLS.
 PLEASE SEE BATH RM, SEE WHEN THE EGRESS
 PATH IS FROM THE FRONT OF THE STORE A
 DEVICE IS REQUIRED EITHER AUTOMATICALLY
 OR MANUAL OVER RIDE BY OCCUPANT. PLEASE
 SEE A MOTION SENSOR IS SHOWN AT THE REAR
 OF THE STORE, HOWEVER PLEASE PROVIDE
 SPECS FOR THIS DEVICE AS, THE DISTANCE
 AND LOCATION MAY REQUIRE ONE ADDITIONAL
 DEVICE EITHER BY MOTION OR TIME SWITCH.
 PLEASE ALSO SEE DIPLAY/ ACCENT
 LTS(TRACK) LTS SHALL CONTAIN CONTROLS
 ALSO.
  
 3) NOTE: PLEASE SEE PANEL "A" ON PLANS
 INDICATES "RELOCATE". PLEASE SHOW NEW
 LOCATION OR IS THIS THE NEW LOCATION.?
 215.5
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-07-14 Cont ID  
Sent By mwennerg Date 2006-07-14 Time 11:11 Rev Time 0.00
Received By mwennerg Date 2006-07-14 Time 11:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-06-15 Cont ID  
Sent By mwennerg Date 2006-06-15 Time 11:17 Rev Time 0.00
Received By mwennerg Date 2006-06-15 Time 11:17 Sent To  
Notes
2006-06-15 00:00:00WHEN PLANS ARE RESUBMITTED FOR OTHER
 REVIEW COMMENTS, PLEASE INDICATE MINIMUM
 INTERIOR FINISH CLASSIFICATION FOR WALLS
 AND CEILING THAT IS SPECIFIC TO THIS
 PROJECT. NOTE ON PLANS IS GENERAL CODE
 REQUIREMENT.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-09-23 Cont ID  
Sent By adarroug Date 2006-09-23 Time 14:26 Rev Time 0.00
Received By adarroug Date 2006-09-23 Time 14:26 Sent To M
Notes
2006-09-23 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-07 Cont ID  
Sent By adarroug Date 2006-07-07 Time 16:55 Rev Time 0.00
Received By adarroug Date 2006-07-07 Time 16:55 Sent To  
Notes
2006-07-12 00:00:00TO "BOB"#3
2006-07-07 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-21 Cont ID  
Sent By rmcdouga Date 2006-06-21 Time 13:00 Rev Time 0.00
Received By rmcdouga Date 2006-05-31 Time 15:09 Sent To  
Notes
2006-05-31 00:00:00TO "BOB"#9

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-09-29 Cont ID  
Sent By tgordon Date 2006-09-29 Time 14:16 Rev Time 0.25
Received By tgordon Date 2006-09-29 Time 14:16 Sent To  
Notes
2006-09-29 00:00:00REVISION TO MECHANICAL PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-07-13 Cont ID  
Sent By tgordon Date 2006-07-13 Time 13:46 Rev Time 0.15
Received By tgordon Date 2006-07-13 Time 13:46 Sent To  
Notes
2006-07-13 00:00:00RE-STAMP MECH. PLAN.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-06-01 Cont ID  
Sent By tgordon Date 2006-06-01 Time 08:49 Rev Time 0.20
Received By tgordon Date 2006-06-01 Time 08:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-07-13 Cont ID  
Sent By jleech Date 2006-07-13 Time 12:45 Rev Time 0.00
Received By jleech Date 2006-07-13 Time 12:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-06-12 Cont ID  
Sent By jleech Date 2006-06-12 Time 14:47 Rev Time 0.00
Received By jleech Date 2006-06-12 Time 14:47 Sent To  
Notes
2006-06-12 00:00:00DENIED;
 1.PLANS MUST BE REVIEWED AND APPROVED BY
 THE DEPARTMENT OF BUSINESS AND
 PROFESSIONAL REGULATION, DEVISION OF
 HOTELS AND RESTAURANTS. PLEASE SUBMIT
 APPROVAL PAPER WORK. WEB SITE
 WWW.MYFLORIDA.COM/DBPR/HR/FORMS/INDEX.SH
 WW.MYFLORIDA.COM/DBPR/HR/FORMS/INDEX.SHT
 W.MYFLORIDA.COM/DBPR/HR/FORMS/INDEX.SHTM
 .MYFLORIDA.COM/DBPR/HR/FORMS/INDEX.SHTML
 2.PLEASE CONTACT THE WEST PALM BEACH
 UTILITY DEPARTMENT TO DETERMINE IS A
 GREASE TRAP IS REQUIRED AT THIS
 LOCATION. ORD.#3434. WHAT TYPE OF FOOD
 IS TO BE PREPARED?
 3.HOW IS CONDENSATE FOR COOLER TO DRAIN?
 FLOOR DRAIN TO SANITARY OR TO A DRY WELL
 PLEASE SHOW ON PLANS.
 4.BRANCH DRAIN FOR AUTOMATIC CLOTHES
 WASHER IS REQUIRED TO BE 3" PER FBC-2004
 PLUMBING SEC 406.3. A CLEANOUT IS
 REQUIRED AT 48" AFF.
 5.WATER HEATER IS REQUIRED TO HAVE A
 MEANS OF EXPANTION CONTROL SEE
 SEC.607.3. SHOW WERE HEATER PLAN IS TO
 DRAIN.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  