Plan Review Details - Permit 06051226
Plan Review Stops For Permit 06051226
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-09-07 Cont ID  
Sent By alange Date 2006-09-07 Time 09:35 Rev Time 0.50
Received By alange Date 2006-09-07 Time 09:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-08-07 Cont ID  
Sent By alange Date 2006-08-07 Time 09:40 Rev Time 0.75
Received By alange Date 2006-08-07 Time 09:29 Sent To  
Notes
2006-08-07 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 NOTE:BUILDING REVIEW OK. SEE
 ELECTRICAL NOTE #12 AND THE FOLLOWING
 BEFORE RESUBMITTING.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE . A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-06-29 Cont ID  
Sent By alange Date 2006-06-29 Time 14:24 Rev Time 1.50
Received By alange Date 2006-06-29 Time 14:18 Sent To  
Notes
2006-06-29 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.DESIGN SHALL BE TO ASCE 7-02.
  
 3.SHOE DOUBLE ROOF UNDERLAYMENT PER
 R-905.2.7
  
 4.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 5.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE . A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-09-20 Cont ID  
Sent By dpalmer Date 2006-09-20 Time 19:24 Rev Time 0.00
Received By dpalmer Date 2006-09-20 Time 18:58 Sent To PC
Notes
2006-09-20 00:00:00REDLINED TWO GRND RODS MIN PER 250.56

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-08-27 Cont ID  
Sent By dpalmer Date 2006-08-27 Time 11:38 Rev Time 0.00
Received By dpalmer Date 2006-08-27 Time 11:28 Sent To M
Notes
2006-08-27 00:00:00** UNSAT 3RD REVIEW **
  
 1) NOTE: PLEASE SUBMIT THE AIC RATINGS
 FOR ALL SERVICE EQUIPMENT AS PREVIOUSLY
 REQUESTED. 110.9, 106.1.2 FBC ADMIN
 SECT.
  
 2) NOTE: PLEASE INDICATE THE SEC'S ARE
 PREVIOUSLY REQUESTED. NO SEC'S ARE SHOWN
 FOR RISER. IF EXISTING, PLEASE SHOW
 SIZE, IF NEW SHOW SIZES.
 310.16, 310.15B6, 240.4 ETC
 FBC 106.1.2
  
 3) NOTE: PLEASE SEE A FEE IS NOW
 ASSESSEDTO THE DEISGN PROFESSIONSL FOR
 THE PLAN REVIEW PORTION OF THE PERMIT
 FEE AS PREVIOUSLY NOTED FOR REPEAT
 COMMENTS AFTER THIRD REVIEW.
 FS 553.80(2)(B).
 PLEASE SEE A FEE OF $1680.00 IS NOW DUE
 AND MUST BE PAID BEFORE RESUBMITTING
 PLANS.
 PLEASE KNOW, ONE SET OF EACH OF THE
 ELECTRICAL PLANS ARE BEING RETAINED BY
 THIS OFFICE.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-07-26 Cont ID  
Sent By dpalmer Date 2006-07-26 Time 15:06 Rev Time 0.00
Received By dpalmer Date 2006-07-26 Time 14:53 Sent To M
Notes
2006-07-26 00:00:00******** UNSAT2ND REVIEW *********
  
  
 ** PLEASE SEE SOME COMMENTS FROM
 PREVIOUS REVIEW STILL NEED TO BE
 ADDRESSED ALONG WITH NEW COMMENTS.
  
 1) NOTE: NO, NOT DONE.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2) NOTE: OK.
  
 3) NOTE: NO, NOT DONE. NEED TO SHOW TO
 VERIFY IF THESE ARE SIZED CORRECTLY.
 RISER ONLY SHWOS FEEDERS FROM MAIN TO
 SUB PANEL.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING SEC'S PER
 310.15B6,310.16,240.4,240.6,215.5
  
 4) NOTE: OK. HOWVER SEE ABOVE.
  
 5) NOTE: OK.
  
  
 6) NOTE: OK.
  
 7) NOTE: OK, HOWEVER SEE NEW ARC FAULT
 NOTE.
  
 8) NOTE: OK.
  
 9) NOTE: OK.
  
 10) NOTE:OK.
  
  
 11) NOTE: OK.
  
 12) NOTE:NO, NOT DONE, THIS IS STILL
 REQUIRED FOR ALL TRADES AND FOR ALL
 SHEETS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING REQUIRED
 LICENSE INFORMATION ON TITLE BLOCKS OF
 SAID PLANS.
 PLEASE SEE FAC 61G1-16.004, FS481.219.
 PLEASE KNOW, THIS IS REQUIRED OF ALL
 SHEETS AND FOR ALL TRADES WHETHER OR NOT
 COMMENTS IS MADEBY OTHER TRADES.
  
 13) NOTE:OK.
  
 14) NOTE: OK.
  
 15) NOTE: OK.
  
 ** NEW NOTES **
  
 16) NOTE: PLEASE MISSING COLD WATER PIPE
 FOR GE SYSTEM.
 250.50.
  
 17) NOTE: PLEASE SEE ARC FAULT NOTE #3
 WAS ADDED TO PLANS AND PANEL SCHEDULE,
 HOWEVER PLEASE SEE NOT ALL REQUIRED
 CIRCUITS SHOW THE #3 NOTE.
 210.12B
  
 18) NOTE: PLEASE SEE ATTACHED SHEET WITH
 RESPECT TO DESIGN PROFESSIONALS AND
 REPEAT CODE COMPLIANT COMMENTS.
 FS 553.80(2)(B).
  
 19) NOTE: IMPORTANT**
 BEFORE RESUBMITTING PLANS, PLEASE
 COMPLETELY REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 TWO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 PLEASE SUBMIT ONE COPY OF ALL OLD/VOIDED
 PREVIOUSLY REVIEWED SHEETS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-14 Cont ID  
Sent By dpalmer Date 2006-06-14 Time 18:27 Rev Time 0.00
Received By dpalmer Date 2006-06-14 Time 18:19 Sent To P
Notes
2006-06-14 00:00:00******** UNSAT **********
  
  
 1) NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2) NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52
  
 3) NOTE: PLEASE SEE MISSING SEC'S PER
 310.15B6,310.16,240.4,240.6,215.5
  
 4) NOTE: PLEASE SEE FEEDERS ARE NOT
 LAREGE ENOUGH FOR 200A SERVICE AS SHOWN
 FROM MAIN TO PANEL.
 310.16, 240.4
  
 5) NOTE: PLEASE CORRELATE ALL CIRCUTING
 ON PANEL SCHEDULE WITH LOADS ON LOAD
 CALCS.
 PLEASE SEE RANGE, WATER HEATER, DRYER
 ETC.
 215.5
  
 6) NOTE: PLEASE SEE WH IS SHOWNAS 1-15A
 BRKR WITH 4500VA LOAD??
 240.4,310.16,240.6
  
 7) NOTE: PLEASE SEE MANY CIRUITS NOTED
 AS ARC FAULT WHICH ARE IN QUESTION??
 WATER HEATER , DRYER ETC??
 PLEASE EXPLAIN.
 215.5
  
 8) NOTE: PLEASE SHOW THE LOCATION ON
 PLAN FOR SERVICE LOCATION.
 215.5
  
 9) NOTE: PLEASE SEE MIN CLEARENCES PER
 110.26 FOR AHU AND WH.
  
 10) NOTE: PLEASE SEE MIN OCP FOR STOVE
 SHOUDL CORRELATE WITH THE KW RATING.
 PLEASE SEE LOAD EXCEEDS RATING OF THE
 OCP/BREAKER.
 240.4,310.16 ETC
 215.5
  
 11) NOTE: PLEASE SEE PLANS SHALL
 INDICATE THE CURRENT CODE IN EFFECT.
 2002 NEC.
 FBC ADMIN SECTION AS AOPTED BY THE CITY
 OF WEST PALM BEACH 106.2.1
  
 12) NOTE: PLEASE SEE MISSING REQUIRED
 LICENSE INFORMATION ON TITLE BLOCKS OF
 SAID PLANS.
 PLEASE SEE FAC 61G1-16.004, FS481.219.
 PLEASE KNOW, THIS IS REQUIRED OF ALL
 SHEETS AND FOR ALL TRADES WHETHER OR NOT
 COMMENTS IS MADEBY OTHER TRADES.
  
 13) NOTE: PLEASE SEE MIN GEC SHALL BE
 SIZED PER 250.66.
  
 14) NOTE: PLEASE SEE PANEL SCHEDULE
 SHOWS TWO BATH RECEPT CIRCUITS??
 PLEASE SEE BOTH ARE SHOWN AS 20A #12,
 ONE FOR LT AND ONE FOR RECEPT.
  
 15) NOTE: PLEASE SEE MISSING
 WASHER/LAUNDRY CIRCUIT PER 210.11C1,
 220.16SHALL BE A MIN OF 1500VA
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-10-17 Cont ID  
Sent By btrobaug Date 2006-10-17 Time 16:25 Rev Time 0.00
Received By btrobaug Date 2006-10-17 Time 16:24 Sent To M
Notes
2006-10-17 16:25:58 
 TOMM GORDONS DESK./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-09-20 Cont ID  
Sent By adarroug Date 2006-09-20 Time 10:27 Rev Time 0.00
Received By adarroug Date 2006-09-20 Time 10:27 Sent To E
Notes
2006-09-20 00:00:00TO "DPALMER" DESK/RESUB-PER "LMARTINEZ"

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-09-06 Cont ID  
Sent By adarroug Date 2006-09-06 Time 11:15 Rev Time 0.00
Received By rbrown Date 2006-08-24 Time 11:15 Sent To E
Notes
2006-09-06 00:00:00*CITY PROJECT*
 *EXPEDITED PLAN REVIEW PER NEIL MELICK*
  
  
2006-08-24 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-25 Cont ID  
Sent By adarroug Date 2006-07-25 Time 13:59 Rev Time 0.00
Received By adarroug Date 2006-07-25 Time 13:59 Sent To E
Notes
2006-07-25 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-29 Cont ID  
Sent By alange Date 2006-06-29 Time 14:31 Rev Time 0.00
Received By alange Date 2006-05-31 Time 16:21 Sent To  
Notes
2006-05-31 00:00:00TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2006-10-20 Cont ID  
Sent By tgordon Date 2006-10-20 Time 11:51 Rev Time 0.20
Received By tgordon Date 2006-10-20 Time 11:51 Sent To  
Notes
2006-10-20 11:52:39REVISION TO MECH. PLANS PAGE 4.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2006-10-18 Cont ID  
Sent By tgordon Date 2006-10-18 Time 11:54 Rev Time 0.45
Received By tgordon Date 2006-10-18 Time 11:54 Sent To  
Notes
2006-10-18 11:59:09REVISION TO MECHANICAL PLANS
 *** DENIED ***
 1) 9" RETURN AIR DUCT FROM 24X12 GRILL TO AHU IS TO
 SMALL FOR 1000 CFM'S, PLEASE CORRECT.
  
 2) 9" RETURN AIR DUCTS TO BEDROOMS MAY BE TO SMALL IF
 THEY ARE TRANSFER DUCTS, CORRECT IF NEEDED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-08-31 Cont ID  
Sent By tgordon Date 2006-08-31 Time 08:49 Rev Time 0.30
Received By tgordon Date 2006-08-31 Time 08:49 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-07-27 Cont ID  
Sent By tgordon Date 2006-07-27 Time 10:25 Rev Time 0.35
Received By tgordon Date 2006-07-27 Time 10:25 Sent To P
Notes
2006-07-27 00:00:00*** DENIED ***
 1) SEE TITLE BLOCK BELOW FIRM'S NAME IS
 ARCHITECT'S REGISTRATION NUMBER, BUT
 NEEDS TO SHOW FIRM'S LICENSE NUMBER, PER
 FAC 61G1-16.004, PLEASE CORRECT.
  
 2) MECHANICAL PLANS AT AHU DETAIL, SHOW
 OVERFLOW DEVICE, PER 2004 FBC/R
 M1411.3.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-06-19 Cont ID  
Sent By tgordon Date 2006-06-19 Time 08:41 Rev Time 0.30
Received By tgordon Date 2006-06-19 Time 08:41 Sent To B
Notes
2006-06-19 00:00:00*** DENIED ***
 1) PLEASE SUBMITMANUAL J CALCULATIONS,
 PER 2004 FBC 13-607.1.ABC.1 .
  
 2) PLEASE CHECK A/C EQUIPMENT LISTING ON
 MECHANICAL PLANS AND CORRECT, AS THE
 ENERGY CALCULATIONS ARE CALLING FOR A 2
 TON A/C SYSTEM.
  
 3) PLEASE SHOW THE SIZE OF ALL RETURN
 AIR TRANSFER GRILLS ON THE MECH. PLANS.
  
 4) PLEASE SEE ELECTRICAL REVIEW NOTE #
 12.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-09-07 Cont ID  
Sent By jleech Date 2006-09-07 Time 07:57 Rev Time 0.00
Received By jleech Date 2006-09-07 Time 07:57 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-08-07 Cont ID  
Sent By jleech Date 2006-08-07 Time 10:04 Rev Time 0.00
Received By jleech Date 2006-08-07 Time 10:04 Sent To  
Notes
2006-08-07 00:00:00DENIED;
 1.SEE ELECTRICAL PLAN REVIEW NOTE # 12.
 2.AUTOMATIC CLOTHES WASHER BRANCH DRAIN
 IS REQUIRED TO BE 3" FBC-2004 PLUMBING
 SEC. 406.3
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-06-19 Cont ID  
Sent By jleech Date 2006-06-19 Time 07:37 Rev Time 0.00
Received By jleech Date 2006-06-19 Time 07:37 Sent To M
Notes
2006-06-19 00:00:00DENIED;
 1.LICENSE INFORMATION MISSING FROM TITLE
 BLOCK.
 2.SANITARY RISER DIAGRAM REQUIRED. SEE
 FBC-2004 CHAPTER 1 ADMINISTRATION CODE
 SEC.106.3.5.4(9).
 3.PAGE 4 A/C CLOSET INSTALLATION IS NOT
 CORRECT. NO ROOM FOR WATER HEATER,
 RETURN AIR SHOULD NOT BE DUCTED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved