| Plan Review Stops For Permit 06051226 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2006-09-07 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-09-07 |
Time |
09:35 |
Rev Time |
0.50 |
| Received By |
alange |
Date |
2006-09-07 |
Time |
09:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2006-08-07 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-08-07 |
Time |
09:40 |
Rev Time |
0.75 |
| Received By |
alange |
Date |
2006-08-07 |
Time |
09:29 |
Sent To |
|
|
| Notes |
| 2006-08-07 00:00:00 | DENIED | | | | | | | | | 1. 713.13 F.S.A NOTICE OF COMMENCEMENT | | | SHALL BE RECORDED AT PALM BEACH COUNTY | | | COURTHOUSE AND A COPY SUBMITTED TO THIS | | | OFFICE BEFORE A PERMIT CAN BE ISSUED. | | | BLANK FORMS ARE AVAILABLE FROM THIS | | | OFFICE. | | | NOTE: THE NOTICE OF COMMENCEMENT MUST BE | | | RE-RECORDED IF THE DESCRIBED IMPROVEMENT | | | OR CONSTRUCTION IS NOT COMMENCED WITHIN | | | 90 DAYS OF RECORDING. | | | | | | NOTE:BUILDING REVIEW OK. SEE | | | ELECTRICAL NOTE #12 AND THE FOLLOWING | | | BEFORE RESUBMITTING. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. SUBMIT ONE COPY OF | | | OLD PAGES FOR REFERENCE . A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF | | | THE REVISION MADE, IDENTIFYING THE SHEET | | | OR SPECIFICATION PAGE WHERE THE CHANGES | | | CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | ART LANGE | | | CONSTRUCTION SERVICES DEPARTMENT | | | BUILDING PLANS EXAMINER | | | 561-805-6672 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-06-29 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-06-29 |
Time |
14:24 |
Rev Time |
1.50 |
| Received By |
alange |
Date |
2006-06-29 |
Time |
14:18 |
Sent To |
|
|
| Notes |
| 2006-06-29 00:00:00 | DENIED | | | | | | | | | 1. 713.13 F.S.A NOTICE OF COMMENCEMENT | | | SHALL BE RECORDED AT PALM BEACH COUNTY | | | COURTHOUSE AND A COPY SUBMITTED TO THIS | | | OFFICE BEFORE A PERMIT CAN BE ISSUED. | | | BLANK FORMS ARE AVAILABLE FROM THIS | | | OFFICE. | | | NOTE: THE NOTICE OF COMMENCEMENT MUST BE | | | RE-RECORDED IF THE DESCRIBED IMPROVEMENT | | | OR CONSTRUCTION IS NOT COMMENCED WITHIN | | | 90 DAYS OF RECORDING. | | | | | | 2.DESIGN SHALL BE TO ASCE 7-02. | | | | | | 3.SHOE DOUBLE ROOF UNDERLAYMENT PER | | | R-905.2.7 | | | | | | 4.THOSE PRODUCT APPROVALS WHICH ARE | | | REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL | | | FOR JURISDICTIONAL APPROVAL.WPB | | | AMENDMENT TO FBC 106.3.3. | | | | | | 5.A DESIGN PROFESSIONAL OR AN OWNER | | | MUST ELECT ONE OR A COMBINATION OF | | | LEVELS OF ALTERATION PURSUANT TO | | | SECTIONS 303, 304 AND 305 OF THIS CODE. | | | SHOW HOW PLANS WILL COMPLY WITH THE | | | SECTION(S) SELECTED.2004 FBC EXISTING | | | BUILDING 301.5 | | | | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. SUBMIT ONE COPY OF | | | OLD PAGES FOR REFERENCE . A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF | | | THE REVISION MADE, IDENTIFYING THE SHEET | | | OR SPECIFICATION PAGE WHERE THE CHANGES | | | CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | ART LANGE | | | CONSTRUCTION SERVICES DEPARTMENT | | | BUILDING PLANS EXAMINER | | | 561-805-6672 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2006-09-20 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-09-20 |
Time |
19:24 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-09-20 |
Time |
18:58 |
Sent To |
PC |
|
| Notes |
| 2006-09-20 00:00:00 | REDLINED TWO GRND RODS MIN PER 250.56 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2006-08-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-08-27 |
Time |
11:38 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-08-27 |
Time |
11:28 |
Sent To |
M |
|
| Notes |
| 2006-08-27 00:00:00 | ** UNSAT 3RD REVIEW ** | | | | | | 1) NOTE: PLEASE SUBMIT THE AIC RATINGS | | | FOR ALL SERVICE EQUIPMENT AS PREVIOUSLY | | | REQUESTED. 110.9, 106.1.2 FBC ADMIN | | | SECT. | | | | | | 2) NOTE: PLEASE INDICATE THE SEC'S ARE | | | PREVIOUSLY REQUESTED. NO SEC'S ARE SHOWN | | | FOR RISER. IF EXISTING, PLEASE SHOW | | | SIZE, IF NEW SHOW SIZES. | | | 310.16, 310.15B6, 240.4 ETC | | | FBC 106.1.2 | | | | | | 3) NOTE: PLEASE SEE A FEE IS NOW | | | ASSESSEDTO THE DEISGN PROFESSIONSL FOR | | | THE PLAN REVIEW PORTION OF THE PERMIT | | | FEE AS PREVIOUSLY NOTED FOR REPEAT | | | COMMENTS AFTER THIRD REVIEW. | | | FS 553.80(2)(B). | | | PLEASE SEE A FEE OF $1680.00 IS NOW DUE | | | AND MUST BE PAID BEFORE RESUBMITTING | | | PLANS. | | | PLEASE KNOW, ONE SET OF EACH OF THE | | | ELECTRICAL PLANS ARE BEING RETAINED BY | | | THIS OFFICE. | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2006-07-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-07-26 |
Time |
15:06 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-07-26 |
Time |
14:53 |
Sent To |
M |
|
| Notes |
| 2006-07-26 00:00:00 | ******** UNSAT2ND REVIEW ********* | | | | | | | | | ** PLEASE SEE SOME COMMENTS FROM | | | PREVIOUS REVIEW STILL NEED TO BE | | | ADDRESSED ALONG WITH NEW COMMENTS. | | | | | | 1) NOTE: NO, NOT DONE. | | | | | | ** PREVIOUS REVIEW NOTE** | | | PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | PER 110.9/215.5 | | | | | | 2) NOTE: OK. | | | | | | 3) NOTE: NO, NOT DONE. NEED TO SHOW TO | | | VERIFY IF THESE ARE SIZED CORRECTLY. | | | RISER ONLY SHWOS FEEDERS FROM MAIN TO | | | SUB PANEL. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE MISSING SEC'S PER | | | 310.15B6,310.16,240.4,240.6,215.5 | | | | | | 4) NOTE: OK. HOWVER SEE ABOVE. | | | | | | 5) NOTE: OK. | | | | | | | | | 6) NOTE: OK. | | | | | | 7) NOTE: OK, HOWEVER SEE NEW ARC FAULT | | | NOTE. | | | | | | 8) NOTE: OK. | | | | | | 9) NOTE: OK. | | | | | | 10) NOTE:OK. | | | | | | | | | 11) NOTE: OK. | | | | | | 12) NOTE:NO, NOT DONE, THIS IS STILL | | | REQUIRED FOR ALL TRADES AND FOR ALL | | | SHEETS. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE MISSING REQUIRED | | | LICENSE INFORMATION ON TITLE BLOCKS OF | | | SAID PLANS. | | | PLEASE SEE FAC 61G1-16.004, FS481.219. | | | PLEASE KNOW, THIS IS REQUIRED OF ALL | | | SHEETS AND FOR ALL TRADES WHETHER OR NOT | | | COMMENTS IS MADEBY OTHER TRADES. | | | | | | 13) NOTE:OK. | | | | | | 14) NOTE: OK. | | | | | | 15) NOTE: OK. | | | | | | ** NEW NOTES ** | | | | | | 16) NOTE: PLEASE MISSING COLD WATER PIPE | | | FOR GE SYSTEM. | | | 250.50. | | | | | | 17) NOTE: PLEASE SEE ARC FAULT NOTE #3 | | | WAS ADDED TO PLANS AND PANEL SCHEDULE, | | | HOWEVER PLEASE SEE NOT ALL REQUIRED | | | CIRCUITS SHOW THE #3 NOTE. | | | 210.12B | | | | | | 18) NOTE: PLEASE SEE ATTACHED SHEET WITH | | | RESPECT TO DESIGN PROFESSIONALS AND | | | REPEAT CODE COMPLIANT COMMENTS. | | | FS 553.80(2)(B). | | | | | | 19) NOTE: IMPORTANT** | | | BEFORE RESUBMITTING PLANS, PLEASE | | | COMPLETELY REMOVE ALL OLD/VOIDED SHEETS | | | AND ONLY INSERT NEW REVISED SHEETS INTO | | | TWO COMPLETE SETS FOR REVIEW AND | | | STAMPING. | | | PLEASE SUBMIT ONE COPY OF ALL OLD/VOIDED | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-06-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-06-14 |
Time |
18:27 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-06-14 |
Time |
18:19 |
Sent To |
P |
|
| Notes |
| 2006-06-14 00:00:00 | ******** UNSAT ********** | | | | | | | | | 1) NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | PER 110.9/215.5 | | | | | | 2) NOTE: PLEASE SEE MISSING RECEPTS PER | | | 210.52 | | | | | | 3) NOTE: PLEASE SEE MISSING SEC'S PER | | | 310.15B6,310.16,240.4,240.6,215.5 | | | | | | 4) NOTE: PLEASE SEE FEEDERS ARE NOT | | | LAREGE ENOUGH FOR 200A SERVICE AS SHOWN | | | FROM MAIN TO PANEL. | | | 310.16, 240.4 | | | | | | 5) NOTE: PLEASE CORRELATE ALL CIRCUTING | | | ON PANEL SCHEDULE WITH LOADS ON LOAD | | | CALCS. | | | PLEASE SEE RANGE, WATER HEATER, DRYER | | | ETC. | | | 215.5 | | | | | | 6) NOTE: PLEASE SEE WH IS SHOWNAS 1-15A | | | BRKR WITH 4500VA LOAD?? | | | 240.4,310.16,240.6 | | | | | | 7) NOTE: PLEASE SEE MANY CIRUITS NOTED | | | AS ARC FAULT WHICH ARE IN QUESTION?? | | | WATER HEATER , DRYER ETC?? | | | PLEASE EXPLAIN. | | | 215.5 | | | | | | 8) NOTE: PLEASE SHOW THE LOCATION ON | | | PLAN FOR SERVICE LOCATION. | | | 215.5 | | | | | | 9) NOTE: PLEASE SEE MIN CLEARENCES PER | | | 110.26 FOR AHU AND WH. | | | | | | 10) NOTE: PLEASE SEE MIN OCP FOR STOVE | | | SHOUDL CORRELATE WITH THE KW RATING. | | | PLEASE SEE LOAD EXCEEDS RATING OF THE | | | OCP/BREAKER. | | | 240.4,310.16 ETC | | | 215.5 | | | | | | 11) NOTE: PLEASE SEE PLANS SHALL | | | INDICATE THE CURRENT CODE IN EFFECT. | | | 2002 NEC. | | | FBC ADMIN SECTION AS AOPTED BY THE CITY | | | OF WEST PALM BEACH 106.2.1 | | | | | | 12) NOTE: PLEASE SEE MISSING REQUIRED | | | LICENSE INFORMATION ON TITLE BLOCKS OF | | | SAID PLANS. | | | PLEASE SEE FAC 61G1-16.004, FS481.219. | | | PLEASE KNOW, THIS IS REQUIRED OF ALL | | | SHEETS AND FOR ALL TRADES WHETHER OR NOT | | | COMMENTS IS MADEBY OTHER TRADES. | | | | | | 13) NOTE: PLEASE SEE MIN GEC SHALL BE | | | SIZED PER 250.66. | | | | | | 14) NOTE: PLEASE SEE PANEL SCHEDULE | | | SHOWS TWO BATH RECEPT CIRCUITS?? | | | PLEASE SEE BOTH ARE SHOWN AS 20A #12, | | | ONE FOR LT AND ONE FOR RECEPT. | | | | | | 15) NOTE: PLEASE SEE MISSING | | | WASHER/LAUNDRY CIRCUIT PER 210.11C1, | | | 220.16SHALL BE A MIN OF 1500VA | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2006-10-17 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-10-17 |
Time |
16:25 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2006-10-17 |
Time |
16:24 |
Sent To |
M |
|
| Notes |
| 2006-10-17 16:25:58 | | | | TOMM GORDONS DESK./WRT. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2006-09-20 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-09-20 |
Time |
10:27 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-09-20 |
Time |
10:27 |
Sent To |
E |
|
| Notes |
| 2006-09-20 00:00:00 | TO "DPALMER" DESK/RESUB-PER "LMARTINEZ" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-09-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-09-06 |
Time |
11:15 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2006-08-24 |
Time |
11:15 |
Sent To |
E |
|
| Notes |
| 2006-09-06 00:00:00 | *CITY PROJECT* | | | *EXPEDITED PLAN REVIEW PER NEIL MELICK* | | | | | | | | 2006-08-24 00:00:00 | TO "DPALMER" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-07-25 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-07-25 |
Time |
13:59 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-07-25 |
Time |
13:59 |
Sent To |
E |
|
| Notes |
| 2006-07-25 00:00:00 | TO "DPALMER" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-06-29 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-06-29 |
Time |
14:31 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2006-05-31 |
Time |
16:21 |
Sent To |
|
|
| Notes |
| 2006-05-31 00:00:00 | TO "E" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2006-10-20 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-10-20 |
Time |
11:51 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2006-10-20 |
Time |
11:51 |
Sent To |
|
|
| Notes |
| 2006-10-20 11:52:39 | REVISION TO MECH. PLANS PAGE 4. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2006-10-18 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-10-18 |
Time |
11:54 |
Rev Time |
0.45 |
| Received By |
tgordon |
Date |
2006-10-18 |
Time |
11:54 |
Sent To |
|
|
| Notes |
| 2006-10-18 11:59:09 | REVISION TO MECHANICAL PLANS | | | *** DENIED *** | | | 1) 9" RETURN AIR DUCT FROM 24X12 GRILL TO AHU IS TO | | | SMALL FOR 1000 CFM'S, PLEASE CORRECT. | | | | | | 2) 9" RETURN AIR DUCTS TO BEDROOMS MAY BE TO SMALL IF | | | THEY ARE TRANSFER DUCTS, CORRECT IF NEEDED. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2006-08-31 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-08-31 |
Time |
08:49 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2006-08-31 |
Time |
08:49 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2006-07-27 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-07-27 |
Time |
10:25 |
Rev Time |
0.35 |
| Received By |
tgordon |
Date |
2006-07-27 |
Time |
10:25 |
Sent To |
P |
|
| Notes |
| 2006-07-27 00:00:00 | *** DENIED *** | | | 1) SEE TITLE BLOCK BELOW FIRM'S NAME IS | | | ARCHITECT'S REGISTRATION NUMBER, BUT | | | NEEDS TO SHOW FIRM'S LICENSE NUMBER, PER | | | FAC 61G1-16.004, PLEASE CORRECT. | | | | | | 2) MECHANICAL PLANS AT AHU DETAIL, SHOW | | | OVERFLOW DEVICE, PER 2004 FBC/R | | | M1411.3.1 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2006-06-19 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-06-19 |
Time |
08:41 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2006-06-19 |
Time |
08:41 |
Sent To |
B |
|
| Notes |
| 2006-06-19 00:00:00 | *** DENIED *** | | | 1) PLEASE SUBMITMANUAL J CALCULATIONS, | | | PER 2004 FBC 13-607.1.ABC.1 . | | | | | | 2) PLEASE CHECK A/C EQUIPMENT LISTING ON | | | MECHANICAL PLANS AND CORRECT, AS THE | | | ENERGY CALCULATIONS ARE CALLING FOR A 2 | | | TON A/C SYSTEM. | | | | | | 3) PLEASE SHOW THE SIZE OF ALL RETURN | | | AIR TRANSFER GRILLS ON THE MECH. PLANS. | | | | | | 4) PLEASE SEE ELECTRICAL REVIEW NOTE # | | | 12. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2006-09-07 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-09-07 |
Time |
07:57 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-09-07 |
Time |
07:57 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2006-08-07 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-08-07 |
Time |
10:04 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-08-07 |
Time |
10:04 |
Sent To |
|
|
| Notes |
| 2006-08-07 00:00:00 | DENIED; | | | 1.SEE ELECTRICAL PLAN REVIEW NOTE # 12. | | | 2.AUTOMATIC CLOTHES WASHER BRANCH DRAIN | | | IS REQUIRED TO BE 3" FBC-2004 PLUMBING | | | SEC. 406.3 | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2006-06-19 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-06-19 |
Time |
07:37 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-06-19 |
Time |
07:37 |
Sent To |
M |
|
| Notes |
| 2006-06-19 00:00:00 | DENIED; | | | 1.LICENSE INFORMATION MISSING FROM TITLE | | | BLOCK. | | | 2.SANITARY RISER DIAGRAM REQUIRED. SEE | | | FBC-2004 CHAPTER 1 ADMINISTRATION CODE | | | SEC.106.3.5.4(9). | | | 3.PAGE 4 A/C CLOSET INSTALLATION IS NOT | | | CORRECT. NO ROOM FOR WATER HEATER, | | | RETURN AIR SHOULD NOT BE DUCTED. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|