| 2006-06-02 00:00:00 | ******DENIED****** |
| | REFERENCE: FBC-2004 FUEL GAS |
| | |
| | THE FOLLOWING INFORMATION IS REQUIRED |
| | FOR PLAN REVIEW FOR A GAS PERMIT: |
| | |
| | 1. THE MASTER PERMIT #05120685 INDICATES |
| | A PROPOSED GENERATOR. NOTE: GAS PERMIT |
| | CAN NOT BE ISSUED UNTIL A GEN/RES PERMIT |
| | APPLICATION HAS BEEN APPLIED FOR AND |
| | APPROVED BY ZONING FOR GENERATOR |
| | LOCATION. THE GENERATOR COULD BE |
| | INDICATED ON THE DRAWING AS A FUTURE |
| | GENERATOR, WITH PIPING AT OWN RISK. |
| | 2. PLEASE INDICATE THE MATERIAL TYPE IN |
| | THE DROP TO THE FIREPLACE, DRYER, AND |
| | THE RUN TO THE BBQ. |
| | 3. THE GAS REGULATOR INDICATED FOR THE |
| | POOL IS UNDER SIZED. THE INDIVIDUAL LOAD |
| | CAPACITY FOR A MAXITROL 325-5 IS ONLY |
| | 300,000 BTU/HR, POOL HEATER INDICATED ON |
| | DRAWING IS 400,000 BTU/HR, A MAXITROL |
| | 325-7 IS REQUIRED. PLEASE SEE CORRECTED |
| | DRAWING IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | 4. THE GAS REGULATOR INDICATED FOR THE |
| | THE HOUSE IS THE WRONG PIPE SIZE, A |
| | MAXITROL 325-3 IS 1/2", A 3/4", 325-5A |
| | REGULATOR IS REQUIRED. PLEASE SEE |
| | CORRECTED DRAWING IN RED INK FOR |
| | REFERENCE FOR RESUBMITTAL. |
| | 5. THE CSST TO THE WATER HEATER IS UNDER |
| | SIZED PER TABLE 402.4(14) PLEASE SEE |
| | ATTACHED TABLE AND CORRECTED DRAWING FOR |
| | REFERENCE FOR RESUBMITTAL. |
| | 6. PLEASE NOTE ON THE CORRECTED DRAWING |
| | THE SYSTEMS BREAK DOWN BETWEEN 2LB AND |
| | 12" W.C. WITH THE LONGEST LENGTH AND THE |
| | TOTAL BTU'S INDICATED FOR EACH SYSTEM. |
| | IN THE FUTURE IN ORDER TO EXPIDITE PLAN |
| | REVIEW PLEASE HAVE THIS ON THE DRAWING. |
| | 7. ONLY ONE CORRECTED DRAWING IN RED |
| | INK. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | UNDER SUPERVISION OF K.STEVENS |
| | (561) 805-6721 |
| | |
| | |