Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-07-11 Cont ID  
Sent By btrobaug Date 2006-07-11 Time 13:21 Rev Time 0.50
Received By btrobaug Date 2006-07-11 Time 12:43 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-02 Cont ID  
Sent By btrobaug Date 2006-06-02 Time 15:08 Rev Time 0.50
Received By btrobaug Date 2006-06-02 Time 14:58 Sent To PC
Notes
2006-06-02 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1}PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 2} NOTE THAT THE SIGNATURE OF THE EN-
 GINEER IS REQUIRED ON HIS/HER SEAL PER
 471.025 FS & 61G15-23.002 FLORIDA
 ADMINISTRATIVE CODE INITIALS ARE NOT
 ACCEPTABLE PER F.B.P.E.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH, FL
 561/805-6718
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-03 Cont ID  
Sent By adarroug Date 2006-07-03 Time 11:02 Rev Time 0.00
Received By adarroug Date 2006-07-03 Time 11:02 Sent To E
Notes
2006-07-03 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-02 Cont ID  
Sent By btrobaug Date 2006-06-02 Time 14:57 Rev Time 0.00
Received By btrobaug Date 2006-05-27 Time 15:42 Sent To E
Notes
2006-05-27 00:00:00TO "E" BOX