Plan Review Details - Permit 06051158
Plan Review Stops For Permit 06051158
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-01-23 Cont ID  
Sent By mjacobs Date 2007-01-23 Time 14:31 Rev Time 0.00
Received By mjacobs Date 2007-01-23 Time 11:21 Sent To PC
Notes
2007-01-23 13:47:29BUILDING PLAN REVIEW
 PERMIT:
 ADD:
 CONT:
 TEL: (561)###-####
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: PASS
  
 SHEETS A-2 / A-4 AND A-5 ARE OKAND HAVE BEEN PLACED
 IN THE ORIGINAL PACKAGE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-08-11 Cont ID  
Sent By amorse Date 2006-08-11 Time 06:34 Rev Time 0.00
Received By amorse Date 2006-08-11 Time 06:34 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-06-19 Cont ID  
Sent By amorse Date 2006-06-01 Time 09:50 Rev Time 0.75
Received By amorse Date 2006-06-01 Time 09:50 Sent To  
Notes
2006-06-01 00:00:00 
  
 DENIED
  
 1) OWNER OF RECORD ON PERMIT APPLICATION
 NOT CORRECT (SEE ATTACHED PROPERTY
 APPRAISER SHEET) PLEASE CLARIFY
  
 2) SHOW REMOVAL OF BREAK ROOM DOOR AND
 CLOSET DOORS AND WALLS ON DEMO PLAN A/2
  
 3)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-01-04 Cont ID  
Sent By btrobaug Date 2007-01-04 Time 17:43 Rev Time 0.75
Received By btrobaug Date 2007-01-04 Time 17:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-09-20 Cont ID  
Sent By btrobaug Date 2006-09-20 Time 12:28 Rev Time 1.00
Received By btrobaug Date 2006-09-20 Time 07:12 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-08-07 Cont ID  
Sent By btrobaug Date 2006-08-07 Time 07:20 Rev Time 0.75
Received By btrobaug Date 2006-08-07 Time 06:38 Sent To  
Notes
2006-08-07 00:00:00 
  
  
 NONCOMPLIANT
  
 THESE COMMENTS ARE THE SAME AS THE
 PREVIOUS REVIEW.
  
 1} PROVIDE THE NUMBERS OF THE POWER POLE
 THE CIRCUITS ARE SERVING ON THE PANEL
 SCHEDULE, AND AT THE POLES.
  
 3} INDICATE CIRCUIT NUMBERS AT LIGHT
 HOME RUN LOCATIONS.
  
 4} SHOW COMPLIANCE WITH 13.415 FBC
 ENERGY CODE.
  
 COMMENT #4 WAS ADDRESSED IN A NOTE ONLY.
 THE COMMENT NEEDS TO BE ADDRESSED
 DIAGRAMATICALLY. SHOW LOCATIONS OF
 DEVICES AND TIMERS, INDICATE SYSTEM
 USED.
  
 THE TITLE BLOCK OF THE ARCHITECTURAL
 FIRM MUST CONTAIN THE CERTIFICATE OF
 AUTHORIZATION NUMBER REQUIRED BY THE
 STATE PER 61G1-16.004(2).
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-09 Cont ID  
Sent By btrobaug Date 2006-06-09 Time 14:52 Rev Time 0.75
Received By btrobaug Date 2006-06-09 Time 14:01 Sent To  
Notes
2006-06-09 00:00:00 
  
 NONCOMPLIANT
  
 1} PROVIDE THE NUMBERS OF THE POWER POLE
 THE CIRCUITS ARE SERVING ON THE PANEL
 SCHEDULE, AND AT THE POLES.
  
 2} PROVIDE A LOAD CALCULATION FOR PANEL
 "10LA". 215.5 NEC.
  
 3} INDICATE CIRCUIT NUMBERS AT LIGHT
 HOME RUN LOCATIONS.
  
 4} SHOW COMPLIANCE WITH 13.415 FBC
 ENERGY CODE.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2007-01-11 Cont ID  
Sent By mwennerg Date 2007-01-11 Time 10:48 Rev Time 0.00
Received By mwennerg Date 2007-01-11 Time 10:48 Sent To  
Notes
2007-01-11 10:51:37***DENIED***
  
 1) PLEASE SEE THAT SPRINKLER NOTE #1 STILL REFERENCES
 NFPA 13R SYSTEMS. THIS COMMENT WAS MADE DURING LAST
 REVIEW. PLEASE MAKE CORRECTION TO READ NFPA 13.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 (561) 805-6722 OR 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-08-10 Cont ID  
Sent By mwennerg Date 2006-08-10 Time 14:45 Rev Time 0.00
Received By mwennerg Date 2006-08-10 Time 14:45 Sent To  
Notes
2006-08-10 00:00:00***APPROVED***
  
 1) PLEASE SEE FIRE SPRINKLER NOTE (1) ON
 M-2 REFERENCING NFPA 13R, RESIDENTIAL UP
 TO AND INCLUDING (4) STORIES IS
 INCORRECT. FIRE SPRINKLER WORK SHALL
 COMPLY WITH NFPA 13, 2002 EDITION.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-06-14 Cont ID  
Sent By mwennerg Date 2006-06-14 Time 14:23 Rev Time 0.00
Received By mwennerg Date 2006-06-14 Time 14:23 Sent To  
Notes
2006-06-14 00:00:00***PROVISO***
  
 1) LIFE SAFETY SHALL COMPLY WITH NFPA
 101, 2003 EDITION. THE INCORRECT CODE
 EDITION IS REFERENCED ON A-1, PROJECT
 INFORMATION NOTE 1.
  
 2) SEPARATE SHOP DRAWINGS AND PERMITS
 REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-02-02 Cont ID  
Sent By adarroug Date 2007-02-02 Time 14:12 Rev Time 0.00
Received By adarroug Date 2007-02-02 Time 14:12 Sent To FIRE
Notes
2007-02-02 14:12:57TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-12-17 Cont ID  
Sent By adarroug Date 2006-12-17 Time 15:50 Rev Time 0.00
Received By adarroug Date 2006-12-17 Time 15:50 Sent To  
Notes
2007-01-03 17:45:59TO "BOB"#12
2006-12-17 15:51:12WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-09-15 Cont ID  
Sent By adarroug Date 2006-09-15 Time 09:18 Rev Time 0.00
Received By adarroug Date 2006-09-15 Time 09:18 Sent To E
Notes
2006-09-15 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-05 Cont ID  
Sent By dpalmer Date 2006-08-05 Time 12:57 Rev Time 0.00
Received By dpalmer Date 2006-08-05 Time 12:57 Sent To  
Notes
2006-08-05 00:00:00TO BOB #14

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-26 Cont ID  
Sent By adarroug Date 2006-07-26 Time 15:46 Rev Time 0.00
Received By adarroug Date 2006-07-26 Time 15:46 Sent To  
Notes
2006-07-26 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-19 Cont ID  
Sent By pschmitz Date 2006-05-27 Time 08:49 Rev Time 0.00
Received By pschmitz Date 2006-05-27 Time 15:14 Sent To  
Notes
2006-05-30 00:00:00TO "BOB"#6
2006-05-27 00:00:00WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-01-04 Cont ID  
Sent By tgordon Date 2007-01-04 Time 11:58 Rev Time 0.40
Received By tgordon Date 2007-01-04 Time 11:58 Sent To  
Notes
2007-01-04 11:59:48REVISION TO MECHANICAL PLANS PAGE M-1.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-06-01 Cont ID  
Sent By tgordon Date 2006-06-01 Time 07:46 Rev Time 0.20
Received By tgordon Date 2006-06-01 Time 07:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-06-18 Cont ID  
Sent By pschmitz Date 2006-06-18 Time 07:58 Rev Time 0.00
Received By pschmitz Date 2006-06-18 Time 07:58 Sent To  
Notes
2006-06-18 00:00:00PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC 2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
 NO CHANGES IN PLUMBING, SHOWN ON PLANS.
  
 QUESTIONS CONTACT 561-805-6692