Plan Review Details - Permit 06051131
Plan Review Stops For Permit 06051131
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-06-12 Cont ID  
Sent By jgomez Date 2006-06-12 Time 10:35 Rev Time 0.33
Received By jgomez Date 2006-06-12 Time 10:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-06-08 Cont ID  
Sent By jgomez Date 2006-06-08 Time 17:48 Rev Time 0.50
Received By jgomez Date 2006-06-08 Time 17:48 Sent To  
Notes
2006-06-08 00:00:00BUILDING REVIEW SECOND CHECKLIST:
 1- PRODUCT APPROVAL FOR FLAT ROOF SYSTEM
 WAS NOT SUBMITTED IN THIS PACKAGE. SEE
 ATTACHED COPY OF CITY POLICY FOR
 RE-ROOFING PERMITS AND INFORMATION
 REQUIRED TO BE SUBMITTED. CLEARLY
 IDENTIFY SPECIFIC APPROVED ASSEMBLY TO
 BE INSTALLED AND SPECIFIC BASE SHEET
 FASTENING. PROVIDE CALCULATIONS FOR
 ENHANCED FASTENING AT CORNER AND
 PERIMETER AREAS IF SELECTED ASSEMBLY IS
 LIMITED BY GENERAL LIMITATION #7. SEE
 GENERAL LIMITATION #7. NOTE: SYSTEMS
 LIMITED BY GENERAL LIMITATION #9 MAY NOT
 WORK IN THIS AREA.
 MAKE SURE FLAT ROOF SYSTEM HAS UPDATED
 FLORIDA PRODUCT APPROVAL 2004 CODE
 VERSION.
  
 2- SPECIFY MEAN ROOF HEIGHT.
  
 3- SPECIFY ROOF PITCH.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-31 Cont ID  
Sent By jgomez Date 2006-05-30 Time 18:01 Rev Time 0.75
Received By jgomez Date 2006-05-30 Time 18:01 Sent To  
Notes
2006-05-31 00:00:00BUILDING REVIEW CHECKLIST:
 1- ENGLERT SERIES 1300 METAL PANELS
 (DADE COUNTY NOA #03-0108.03):
 A) MAXIMUM DESIGN PRESSURES FOR THIS
 SYSTEM IS -60PSF. DESIGN PRESSURES FOR
 CORNER AND PERIMETER AREAS ARE HIGHER
 FOR THIS AREA. SEE TABLE 1609.6B FBC
 2004. NEED TO PROVIDE CALCULATIONS FOR
 INCREASED DESIGN PRESSURES AT THESE
 ZONES. ALL CALCULATIONS TO BE PERFORMED
 SIGNED AND SEALED BY ANY ONE OF THE
 PROFESSIONALS LISTED IN SYSTEM
 LIMITATION NUMBER 1. SEE PAGE 5 OF 6.
 B) CLEARLY IDENTIFY APPROVED ASSEMBLY
 TO BE INSTALLED. SEE ATTACHED COPY OF
 CITY POLICY FOR RE-ROOFING PERMITS AND
 REQUIRED INFORMATION TO BE SUBMITTED.
 C) SPECIFY MEAN ROOF HEIGHT.
 D) SPECIFY ROOF PITCH.
  
 2- FLAT ROOF SYSTEM:
 A) CLEARLY IDENTIFY APPROVED ASSEMBLY
 TO BE INSTALLED AND SPECIFIC FASTENING
 OPTION TO BE USED AS REQUIRED BY CITY
 POLICY FOR RE-ROOFING PERMITS.
 B) PROVIDE FLORIDA PRODUCT APPROVAL
 UPDATED COVER PAGE WITH FBC 2004 CODE
 VERSION.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712
  
  