Plan Review Details - Permit 06051084
Plan Review Stops For Permit 06051084
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-06-29 Cont ID  
Sent By alange Date 2006-06-29 Time 13:06 Rev Time 0.50
Received By alange Date 2006-06-29 Time 13:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-22 Cont ID  
Sent By dpalmer Date 2006-06-22 Time 20:17 Rev Time 0.00
Received By dpalmer Date 2006-06-22 Time 20:04 Sent To M
Notes
2006-06-22 00:00:00********** UNSAT ************
  
 1) NOTE: PLEASE SEE ZONING COMMENTS,A ND
 PLEASE KNOW, THIS GENERARTOR IS LOCATED
 IN A FLOOD ZONE "A" AND WILL REQUIRED
 ELEVATION OF EXSITING BFE AND NEW
 EQUIPMENT ELEVATION.
  
 **PLEASE KNOW, AN ELEVATION CERTIFICATE
 WILL BE REQUIRED BEFORE FINAL
 INSPECTION.
  
 2) NOTE: PLEASE PROVIDE SIZE OF NEW
 METER CAN SHOWN.
 215.5
  
 3) NOTE: PLEASE COMPLETE GROUNDING
 ELECTRODE AND GROUNDING ELECTRODE RISER.
  
 250.50,250.66
  
 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 PLEASE ALSO INDICATE THE RATING FOR ATS.
  
 5) NOTE: PLEASE RE-CONFIGURE A/C LOADS
 WHICH ARE SHOWN AT 40%??
 PLEASE KNOW, A/C LOADS SHALL BE BASED ON
 HEAT LOADS UNLESS, AUTOMATIC LOAD
 SHEDDING IS PROVIDED. EITHER REFIGURE
 LOAD CALCS OR PROVIDE DETAIL FOR THE
 LOAD SHEDDING.
 702.5,,220,225.35 ETC.
  
 6) NOTE: PLEASE SEE THAT THE RESPONSIBLE
 LICENSE CONTRACTOR SHALL PRINT NAME AND
 SIGN PLANS.
 FBC 106.2.1, 106.3.2.1 ADMIN SECT AS
 ADOPTED BY THE CITY OF WEST PALM BEACH
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-06-23 Cont ID  
Sent By mperson Date 2006-06-23 Time 13:07 Rev Time 0.15
Received By mperson Date 2006-06-23 Time 13:07 Sent To B
Notes
2006-06-23 00:00:00NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL GEN/RES INSPECTION.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-22 Cont ID  
Sent By adarroug Date 2006-06-22 Time 11:32 Rev Time 0.00
Received By adarroug Date 2006-06-22 Time 11:32 Sent To E
Notes
2006-06-22 00:00:00TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-29 Cont ID  
Sent By alange Date 2006-06-29 Time 13:06 Rev Time 0.00
Received By alange Date 2006-05-26 Time 15:31 Sent To  
Notes
2006-05-26 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-06-23 Cont ID  
Sent By tgordon Date 2006-06-23 Time 09:37 Rev Time 0.15
Received By tgordon Date 2006-06-23 Time 09:38 Sent To P
Notes
2006-06-23 00:00:00*** DENIED ***
 1) PLEASE SEE ZONING REVIEW AND CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-06-23 Cont ID  
Sent By tgordon Date 2006-06-23 Time 09:38 Rev Time 0.00
Received By mperson Date 2006-06-23 Time 13:06 Sent To G
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2006-06-21 Cont ID  
Sent By mmclean Date 2006-06-21 Time 14:41 Rev Time 0.00
Received By mmclean Date 2006-06-21 Time 14:39 Sent To I
Notes
2006-06-21 00:00:00RECEIVED PLANS 6/21/06 FROM INCOMING
 (1ST REVIEW)
  
  
 DENIED.
 1. NEED TO PROVIDE THE DISTANCE OF THE
 PROPOSED GENERATOR FROM THE SIDE
 PROPERTY LINE AND FRONT PROPERTY LINE.
  
 SEC 94-303 MECHANICAL/POOL
 EQUIPMENT/GENERATOR MAY NOT PROJECT MORE
 THAN FOUR FEET INTO A SETBACK.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720
  
  