Plan Review Details - Permit 06051043
Plan Review Stops For Permit 06051043
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-08-15 Cont ID  
Sent By alange Date 2006-08-15 Time 11:52 Rev Time 1.50
Received By alange Date 2006-08-15 Time 11:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-06-30 Cont ID  
Sent By alange Date 2006-06-30 Time 07:09 Rev Time 1.75
Received By alange Date 2006-06-30 Time 07:09 Sent To  
Notes
2006-06-30 00:00:00DENIED
  
  
 1. ALL PLANS SUBMITTED AFTER OCTOBER, 1,
 2005 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE.CHECK CODE
 SECTIONS MENTIONED.PLANS SHALL BE
 DESIGNED TO ASCE-7-02.
  
 2.SIGN ENERGY CALCS AND COMPLETE TOP
 OF APPLICATION ON ENERGY CALCS PER 2004
 FBC.
  
 3.PRODUCT APPROVALS REQUIRED FOR
 LINTELS AND STRAPS AND TIE-DOWNS.
  
 4.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 5.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 6.SUBMIT TWO SETS OF TRUSS DRAWINGS
 FOR REVIEW PER 2004 FBC R-802.10.1
  
 7.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 8.R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A
 STORM SEWER CONVEYANCE OR OTHER APPROVED
 POINT OF COLLECTION SO AS TO NOT CREATE
 A HAZARD. LOTS SHALL BE GRADED SO AS TO
 DRAIN SURFACE WATER AWAY FROM FOUNDATION
 WALLS. THE GRADE AWAY FROM FOUNDATION
 WALLS SHALL FALL A MINIMUM OF 6 INCHES
 WITHIN THE FIRST 10 FEET.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE . A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-03-15 Cont ID  
Sent By dpalmer Date 2007-03-15 Time 11:11 Rev Time 0.00
Received By dpalmer Date 2007-03-15 Time 11:07 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2007-03-10 Cont ID  
Sent By dpalmer Date 2007-03-10 Time 11:26 Rev Time 0.00
Received By dpalmer Date 2007-03-10 Time 10:41 Sent To PC
Notes
2007-03-10 11:27:30** UNSAT 2ND REVIEW **
  
 1) NOTE: PLEASE SEE PLANS INDICATE A NEW 200AMP
 DISCONNECT INSIDE THE EXISTING 200AMP MAIN BREAKER
 PANEL? THIS IS UNCLEAR WHAT THIS IS FOR AS THE RISER
 DOES NOT INCLUDE ANY INFORMATION FOR THIS AS NEW FEED?
 PLEASE CLARIFY.
 FBC ADMIN SECTION 106.1.2
  
 2) NOTE: PLEASE SEE MISSING FOOTER STEEL AS PART OF THE
 GROUNDING ELECTRODE SYSTEM. THIS WAS ON ORIGINAL PLANS
 AND NOTED ON PREVIOUS SET OF REVISIONS SUBMITTED AS IT
 WAS REMOVED.
 PLEASE SEE 250.50.
  
 3) NOTE: PLEASE SEE 210.4B AS THE DISHWASHER AND
 DISPOSAL IS REQUIRED TO BE ON A 2-POLE BREAKER WHEN
 FEEDING THE SAME DEVICE AND THE SAME YOKE.
  
 4) NOTE: PLEASE CLARIFY THE IG RECEPTACLE ON THE
 KITCHEN COUNTER SPACE?
 210.8A6
  
 5) NOTE: PLEASE SEE THE PANEL SCHEDULE FOR CIRCUITS
 SHALL BE SPECIFIC TO THE AREAS AND ROOMS THEY FEED.
 PLEASE SEE TEXT BELOW TAKEN DIRECTLY FROM THE
 COMMENTARY OF THE CODE.
 * TO REQUIRE THAT THE IDENTIFICATION FOR EVERY CIRCUIT
 SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND
 CLEARLY STATE THE SPECIFIC PURPOSE FOR WHICH THE
 CIRCUIT IS USED. CIRCUITS USED FOR THE SAME PURPOSE
 MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR EXAMPLE,
 SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY OUTLETS IN
 THE KITCHEN, DINING ROOM, AND KITCHEN COUNTERTOPS.
 IDENTIFYING THE CIRCUITS AS SMALL APPLIANCE BRANCH
 CIRCUITS IS NOT ACCEPTABLE; INSTEAD, THEY SHOULD BE
 IDENTIFIED AS ``KITCHEN WALL RECEPTACLES,'' ``DINING
 ROOM FLOOR RECEPTACLE,'' OR ``KITCHEN COUNTERTOP
 RECEPTACLES LEFT OF SINK.'' CIRCUIT DIRECTORIES
 CONTAINING MULTIPLE ENTRIES WITH ONLY ``LIGHTS'' OR
 ``OUTLETS'' DO NOT PROVIDE THE SUFFICIENT DETAIL
 REQUIRED BY THIS SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.1.2
  
 6) NOTE: PLEASE SEE WALL SPACE IN DINING ROOM AREA FOR
 RECEPTACLE TO BE WITHIN 6FT OF DOOR AND EACH PORTION
 THEREAFTER TO MEET 210.52.
 PLEASE SEE PLANS MENTIONS EXISTING AREA, HOWEVER PLANS
 ALSO INDICATE THE ENTIRE DWELLING BEING BROUGHT UP TO
 CODE.
  
 7) NOTE: WATER HEATER SHOWN TO HAVE A 220V RECEPTACLE
 AND IS REQUIRED TO CONTAIN DISCONNECT. 422.30, 422.31
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-02-18 Cont ID  
Sent By dpalmer Date 2007-02-18 Time 14:03 Rev Time 0.00
Received By dpalmer Date 2007-02-18 Time 13:39 Sent To PC
Notes
2007-02-18 14:04:14*** UNSAT ***
  
 1) NOTE: PLEASE PROVIDE REVISIONS TO THE DESIGNER OF
 RECORD AND HAVE PLANS RE-DRAWN WITH ALL CHANGES. PLEASE
 DO NOT SUBMIT PLANS DONE IN INK OR IN PENCIL AND HAND
 WRITTEN CHANGES.
 FBC 106.1.2, 106.3.1.
  
 2) NOTE: PLEASE SEE THE RISER NOW IS COMPLETELY REVISED
 WHICH NOW INDICATES MAIN SERVICE AS EXISTING?? PLEASE
 SEE PLANS STILL INDICATE A NEW SERVICE, NEW MAIN ETC.
 PLEASE CORRELATE AND REVISE ACCORDINGLY.
 215.5,
 FBC 106.1.2
  
 3) NOTE: PLEASE SEE A NEW SUB PANEL IS NOW SHOWN,
 HOWEVER NOW THAT THE RISER HAS BEEN REVISED, PLEASE
 INCLUDE THE OVER CURRENT PROTECTION FROM WHAT IS NOW
 BEING SHOWN AS AN EXISTING 200AMP PANEL FOR NEW SUB
 PANEL.
 240.4, 310.16, 215.5 ETC
  
 4) NOTE: PLEASE SUBMIT A NEW PANEL SCHEDULE FOR THE NEW
 SUB PANEL WHICH IS NOW SHOWN SHOWING ALL THE OVER
 CURRENT PROTECTION DEVICES ALONG WITH THE SIZE OF THE
 BRANCH CIRCUIT CONDUCTORS FOR REVIEW.
 310.16, 240.4, 408.4 ETC.
  
 5) NOTE: PLEASE SEE THE MASTER BATH ROOM GFI WHICH IS
 BEING SHOWN ON THE ONE SIDE OF THE LAV. PLEASE SEE
 210.52D WHICH REQUIRES THE GFI WITHIN 3FT OF SINK EDGE,
 HOWEVER MAY NOT CROSS OVER SINK TO PLUG IN AN
 APPLIANCE. PLEASE ADD AN ADDITIONAL GFI OR REVISE
 LOCATION.
  
 6) NOTE: PLEASE SHOW THE GROUNDING ELECTRODE SYSTEM PER
 250.50
 (SHOWN ON ORIGINAL RISER)
  
 7) NOTE: NOTES WRITTEN ON PLANS MENTIONS A 3-WAY
 SWITCHED REQUIRED AT MASTER BEDROOM AT THE EGRESS TO
 REAR PORCH; HOWEVER THE PLANS ALREADY SHOW THIS??
 210.70
  
 8) NOTE: PLEASE SEE THAT ALL OUTSIDE RECEPTACLES ARE TO
 BE GFI/ GFI PROTECTED. 210.8A3
  
 ** PLEASE KNOW THAT DUE TO SOME INFORMATION NOT YET
 SUBMITTED FOR REVIEW THERE MAY BE COMMENTS ON THE
 FOLLOWING REVIEW.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-09-05 Cont ID  
Sent By dpalmer Date 2006-09-05 Time 08:43 Rev Time 0.00
Received By dpalmer Date 2006-09-01 Time 16:42 Sent To PC
Notes
2006-09-05 00:00:00**** NOTES REDLINED ***
  
  
 1) NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN TO PANEL.
 250.110.25.24,250.122
 #6 MIN REQUIRED.
  
 2) NOTE: PLEASE SEE 250.66 FOR MIN SIZE
 FOR GROUNDING ELECTRODE CONDUCTOR.
 PLEASE SEE #4 MIN REQUIRED.
  
 3) NOTE: PLEASE SEE RISER SHOWS 1 1/2"
 CONDUIT FROM METER TO MAIN AND MAIN TO
 SUB PANEL. PLEASE SEE CHAPTER 9 TABLES
 FOR MIN SIZING. PLEASE SEE A 2" CONDUIT
 MIN IS REQUIRED.
  
 ** THE ABOVE WAS REDLINED, AND IF THERE
 ARE ANY REVISIONS BEFORE ROUGH, PLEASE
 REVISE.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-08-07 Cont ID  
Sent By dpalmer Date 2006-08-07 Time 17:54 Rev Time 0.00
Received By dpalmer Date 2006-08-07 Time 15:27 Sent To M
Notes
2006-08-07 00:00:00******* UNSAT 2ND REVIEW ************
  
 ** PLEASE SEE SOME COMMENTS BELOW ARE
 STILL IN NEED OF ADDRESSING AND PLEASE
 SEE NEW NOTES DUE TO CHANGES IN PLANS.
 NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW. NEW NOTES ADDED TO THE
 BOTTOM.
  
 1) NOTE: OK.
  
 2) NOTE:NO, PLEASE SEE MOST AREAS HAVE
 BEEN DONE HOWEVER PLEASE SEE MEANS OF
 EGREES FROM EXISTING KITCHEN/DINING AREA
 THROUGH THE LIVING RM TO OUTSIDE. PLEASE
 SEE THIS CAN BE POSSIBLY ADDRESSED BY
 MEANS OF A 3-WAY SWITCH TO THE 1/2 SW
 RECEPT. (THIS IS ONLY ONE OPTION).
 PLEASE SEE FAN/LT IS STILL ONLY SHOWN AS
 A "J" FOR JUNCTION BOX. PLEASE KNOW, THE
 "J" NEEDS TO BE REMOVED AS THIS FAN AND
 LT WILL BE REQUIRED IF THIS METHOD IS
 BEING USED FOR MEANS OF EGRESS.(FAMILY
 RM AND REAR PORCH)
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 210.70, LS 101 7.8,
 MANY LOCATIONS ON PLANS INDICATE A
 J-BOX, YET ALSO MENTIONS AFAN AND LT?
 PLEASE SEE IF A FAN LT IS NOTED, THEN
 THESE SHOULD BE SHOWN.
 **SEPARATE**
 ** THIS IS ONLY A NOTICED AS PLANS ONLY
 INDICATE ONE SWITCH FOR BOTH. THIS IS
 OK, HOWEVER ONLY NOTED.
  
 3) NOTE: OK.
  
 4) NOTE: OK.
  
 5) NOTE: NO/OK, PLEASE SEE ONLY ONE
 STILL MISSING. THIS COULD HAVE BEEN
 REDLINED, HOWEVER PLANS ARE COMING BACK
 FOR OTHER COMMENTS PLEASE ADRESS AT THIS
 TIME. (BEDRM #2)
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MANY RECEPTS MISSING
 PER 210.52
  
 6) NOTE: OK.
  
 7) NOTE: OK, HOWEVER PLEASE SEE NEW
 COMMENTS DUE TO THE RISER BEING REVISED
 FROM THE PREVIOUS SET OF PLANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 250.6 AND 250.24B
 FOR EQUIPMENT GROUNDING CONDUCTOR SHALL
 NOT BE INSTALLED BEFORE THE FIRST MEANS
 OF DISCONNECT FOR OBJECTIONAL CURRENTS.
  
 8) NOTE: NO, PLEASE SEE PLANS NOW ONLY
 SHOW AFCI PROTECTION FOR RECEPTS. PLEASE
 KNOW, AFCI (ARC FAULT ) PROTECTION IS
 REQUIRED FOR ALL "OUTLETS"IN BEDRMS.
 THIS INCLUDES THE ENTIRE BRANCH
 CIRCUITS. PLEASE SEE THIS INLCUDES SD'S,
 LTS, FANS ETC. PLEASE KNOW THE
 REQUIREMENT FOR ONLY RECEPTS WENT OUT
 WITH THE 1999 NEC.
 PLEASE LIST ON PANEL SCHEDULE AS
 PREVIOUSLY REQUESTED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING LISTED ARC
 FAULT CIRCUITS ON PANEL SCHEDULE.
 210.12B
  
 9) NOTE: NO, PLEASE SEE THIS WAS
 ADDRESSED AND ADDED AIC RATING TO MCB
 PANEL IN GARAGE, HOWEVER PLEASE SEE
 RISER NOW SHOWS A NEW MAIN DISCONNECT
 WHICH DOES NOT INDICATE RATINGS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING AIC RATING
 FOR NEW MAINS/PANEL.
 110.9,90.8
 FBC 106.1.2
  
 10) NOTE: NO? PLEASE SEE NO COMMENTS
 WERE MADE IF THIS IS FED UNDERGROUND AND
 NOW RISER HAS BEEN REVISED TO SHOW WHAT
 APPEARS TO BE A DISCONNECT ON THE LINE
 SIDE OF THE MCB [ANEL. PLEASE SEE NO
 INFORMATION WAS SUBMITTED FOR THIS NEW
 MAIN DISCONNECT AND PLEASE SEE PLANS DO
 NOT REFLECT A MAIN DISCONNECT NEXT TO
 METER CAN. SEE NEW COMMENTS ALSO AS THIS
 MAIN BEING ADDED CHANGES THE GROUNDING.
  
 ** PREVIUOUS REVIEW NOTE **
 PLEASE SPECIFY OF NEW FEED
 FROM METER TO MAIN IS UNDERGROUND?
 PLEASE SEE 230.70, NO MORE THAN 8' OF
 UNPROTECTED CONDUCTORS ARE PERMITTED
 INSIDE THE BUILDING WITH HAVING A
 DISCONNECT AND OCP ON THE OUTSIDE OF THE
 DWELLING.
 240.6
  
 11) NOTE: OK.
  
 12) NOTE: NO, PLEASE SEE NEC 220 FOR TWO
 POSSIBLE METHODS FOR CALCULATING LOADS
 FOR A SINGLE FAMILY DWELLING. PLEASE SEE
 CALCS AS SHOWN DO NOT MEET EITHER ONE.
 PLEASE SEE CODE DOES NOT PERMIT DERATING
 OF THE A/C/HEAT LOADS WITH THE GEN LTS
 NAD RECEPTS LOADS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE CALCULATIONS NEED
 TO MEET CODE.220,,215.5
  
 13) NOTE: OK, PLEASE BE SURE TO DO THIS
 ON REVISED PLANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THE PRINTED NAME
 AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR PLANS AND DESIGN IS MISSING.
 FBC 106.2.1 ADMIN SECT AS ADOPTED BY THE
 CITY OF WEST PALM BEACH.
  
 14) NOTE: NO/OK, PLEASE SEE TWO WERE
 ADDED ONE FOR MASTER AND ONE FOR NEW
 CABANNA BATH. PLEASE SEE OTHER BATH(S).
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING REQUIRED
 DEDICATED BATH(S) CIRCUITS PER
 210.52D,210.11C3
 MUST BE 20A AND #12.
 PLEASE SEE ONE BATH INDICATES THIS.
  
 15) NOTE: OK.
  
 ** NEW NOTES**
  
 16) NOTE: PLEASE SEE RISER DIAGRAM, IF A
 MAIN IS NOW ADDED TO THE LINE SIDE OF
 THE MCB PANEL, PLEASE SEE MISSING
 EQUIPMENT GROUNDING CONDUCTOR FROM MAIN
 TO THE PANEL.
 250.24B, 250.110,250.122
  
 17) NOTE: PLEASE SEE MISSING AHU #2 OR
 #1? PLEASE SEE PLANS ONLY SHOW ONE AHU??
 PLEASE CLARIFY AND SHOW LOCATION OF THIS
 AHU. PLEASE BE SURE TO INDICATE
 LT/RECEPTS. 210.70, 210.63
 DISCONNECT PER440.11
 PLEASE SEE MIN CLEARENCE FOR UC. 110.26
  
 18) NOTE: PLEASE SEE KITCHEN COUNTER
 SPACE AS THE GFI REQUIRED ALONG KITCHEN
 COUNTER IS BEING NOTED AS "UC". (UNDER
 CABINET).
 PLEASE ALSO SEE DISPOSAL IS BEING SHOWN
 AS A GFI RECEPT.
 210.52C1-5. (C-3) C-5)
  
 19) NOTE: PLEASE SEE SD NOW SHOWN
 OUTSIDEMASTER BEDRM IS REQUIRED TO BE
 WITH THE 12" OF THE HIGHEST POINT ON ANY
 FLAT OR TRAY CEILING. PLEASE SEE NFPA-72
 11.8.3
 PLEASE KNOW, IF TRAY IS LESS THAN 12"
 THEN IT IS OK WHERE IT IS. THIS ONE
 COMMENT WAS MISSED ON PREVIOUS REVIEW.
 THIS COULD HAVE BEEN REDLINED, HOWEVER
 PLANS ARE COMING BACK FOR OTHER
 COMMENTS.
  
 20) NOTE: PLEASE SEE FS 553.80(2)(B)
 WITH RESOECT TO REPEAT COMMENTS.
  
 ** IMPORTANT**
 WHEN RESUBMITTING PLANS , PLEASE
 COMPLETELY REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 TWO COMPLETE SETS FOR REVIEW.
 PLEASE ONLY SUBMIT ONE COPY OF THE
 OLD/VOIDED REMOVED SHEETS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-14 Cont ID  
Sent By dpalmer Date 2006-06-14 Time 17:13 Rev Time 0.00
Received By dpalmer Date 2006-06-14 Time 12:14 Sent To P
Notes
2006-06-14 00:00:00*********** UNSAT ************
  
 1) NOTE: PLEASE SEE PLANS NEED TO
 REFLECT AND MEET 2002 NEC.PLEASE SEE
 PLANS REFERENCE BOTH 2002 AND 2005
  
 2) NOTE: PLEASE SEE 210.70, LS 101 7.8,
 MANY LOCATIONS ON PLANS INDICATE A
 J-BOX, YET ALSO MENTIONS AFAN AND LT?
 PLEASE SEE IF A FAN LT IS NOTED, THEN
 THESE SHOULD BE SHOWN.
 **SEPARATE**
 ** THIS IS ONLY A NOTICED AS PLANS ONLY
 INDICATE ONE SWITCH FOR BOTH. THIS IS
 OK, HOWEVER ONLY NOTED.
  
 3) NOTE: PLEASE SEE MISSING FOOTER STEEL
 PER 250.50.
  
 4) NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52D, 210.11C3, 210.8A
  
 5) NOTE: PLEASE SEE MANY RECEPTS MISSING
 PER 210.52
  
 6) NOTE: PLEASE SEE SEC'S ARE TOO
 SMALL, 310.16,310.15B6,240.4,240.6 ETC
  
 7) NOTE: PLEASE SEE 250.6 AND 250.24B
 FOR EQUIPMENT GROUNDING CONDUCTOR SHALL
 NOT BE INSTALLED BEFORE THE FIRST MEANS
 OF DISCONNECT FOR OBJECTIONAL CURRENTS.
  
 8) NOTE: PLEASE SEE MISSING LISTED ARC
 FAULT CIRCUITS ON PANEL SCHEDULE.
 210.12B
  
 9) NOTE: PLEASE SEE MISSING AIC RATING
 FOR NEW MAINS/PANEL.
 215.5,110.9
  
 10) NOTE: PLEASE SPECIFY OF NEW FEED
 FROM METER TO MAIN IS UNDERGROUND?
 PLEASE SEE 230.70, NO MORE THAN 8' OF
 UNPROTECTED CONDUCTORS ARE PERMITTED
 INSIDE THE BUILDING WITH HAVING A
 DISCONNECT AND OCP ON THE OUTSIDE OF THE
 DWELLING.
 240.6
  
 11) NOTE: PLEASE SEE MIN AND MAX OCP FOR
 BOTH AHU'S NEEDS TO BE ADJUSTED.
 MIN 125%, MAX 150%.
 PLEASE SEE SIZE ON ONE IS TOO HIGH AND
 THE OTHER IS TOO LOW.
 PLEASE ALSO SEE CONDUCTORS FOR AHU#2
 NEED TO MEET 310.16, 240.4
  
 12) NOTE: PLEASE SEE CALCULATIONS NEED
 TO MEET CODE.220,,215.5
  
 13) NOTE: PLEASE SEE THE PRINTED NAME
 AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR PLANS AND DESIGN IS MISSING.
 FBC 106.2.1 ADMIN SECT AS ADOPTED BY THE
 CITY OF WEST PALM BEACH.
  
 14) NOTE: PLEASE SEE MISSING REQUIRED
 DEDICATED BATH(S) CIRCUITS PER
 210.52D,210.11C3
 MUST BE 20A AND #12.
 PLEASE SEE ONE BATH INDICATES THIS.
  
 15) NOTE: PLEASE SEE MISSING ELECTRICAL
 RECEPTS FOR RANGE/STOVE.
 215.5
  
 ** IMPORTANT**
 WHEN RESUBMITTING PLANS , PLEASE
 COMPLETELY REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 TWO COMPLETE SETS FOR REVIEW.
 PLEASE ONLY SUBMIT ONE COPY OF THE
 OLD/VOIDED REMOVED SHEETS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-03-08 Cont ID  
Sent By adarroug Date 2007-03-08 Time 16:02 Rev Time 0.00
Received By adarroug Date 2007-03-08 Time 16:02 Sent To E
Notes
2007-03-08 16:03:31TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-02-14 Cont ID  
Sent By adarroug Date 2007-02-14 Time 14:31 Rev Time 0.00
Received By adarroug Date 2007-02-14 Time 14:31 Sent To E
Notes
2007-02-14 14:32:13TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-02-14 Cont ID  
Sent By adarroug Date 2007-02-14 Time 10:14 Rev Time 0.00
Received By adarroug Date 2007-02-14 Time 10:14 Sent To M
Notes
2007-02-14 10:14:49TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-08-26 Cont ID  
Sent By adarroug Date 2006-08-26 Time 12:38 Rev Time 0.00
Received By adarroug Date 2006-08-26 Time 12:38 Sent To E
Notes
2006-08-26 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-08-07 Cont ID  
Sent By adarroug Date 2006-08-07 Time 14:37 Rev Time 0.00
Received By adarroug Date 2006-08-07 Time 14:37 Sent To E
Notes
2006-08-07 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-07-31 Cont ID  
Sent By adarroug Date 2006-07-31 Time 17:45 Rev Time 0.00
Received By adarroug Date 2006-07-31 Time 17:45 Sent To Z
Notes
2006-07-31 00:00:00TO Z BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-12 Cont ID  
Sent By adarroug Date 2006-06-12 Time 12:57 Rev Time 0.00
Received By adarroug Date 2006-06-12 Time 12:57 Sent To E
Notes
2006-06-12 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-30 Cont ID  
Sent By alange Date 2006-06-30 Time 07:14 Rev Time 0.00
Received By alange Date 2006-05-26 Time 12:23 Sent To  
Notes
2006-05-26 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-02-20 Cont ID  
Sent By tgordon Date 2007-02-20 Time 15:51 Rev Time 0.30
Received By tgordon Date 2007-02-20 Time 15:50 Sent To  
Notes
2007-02-20 15:51:37REVISION TO MECHANICAL PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-08-08 Cont ID  
Sent By tgordon Date 2006-08-08 Time 09:00 Rev Time 0.25
Received By tgordon Date 2006-08-08 Time 09:00 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-06-16 Cont ID  
Sent By tgordon Date 2006-06-16 Time 14:05 Rev Time 1.00
Received By tgordon Date 2006-06-16 Time 14:05 Sent To B
Notes
2006-06-16 00:00:00*** DENIED ***
 1) ENERGY CAL'S. AER CALLING FOR A 4 TON
 A/C SYSTEM, MANUAL J CAL'S. ARE CALLING
 FOR A 2.6 TON A/C SYSTEM, AND THE
 MECHANICAL PLANS ARE CALLING FOR A 4 TON
 A/C SYSTEM BUT THE MODEL NUMBERS AND
 BTU'S ARE FOR A 3 TON SYSTEM, PLEASE
 CORRECT.
  
 2) ENERGY CAL'S. ARE CALLING FOR A 12
 SEER A/C SYSTEM, AND THE MECHANICAL
 PLANS ARE CALLING FOR A 10.3 SEER A/C
 SYSTEM, THE PLANS CAN NOT CALL FOR LESS
 THAN THE ENERGY CAL'S. PLEASE CORRECT.
  
 3) ENERGY CAL'S. AER SHOWING NO HEAT,
 THE A/C PLANS AER SHOWING 10 KW HEATER
 PLEASE CORRECT, PLEASE NOTE 10 KW DOES
 NOT = 28,000 BTU'S PLEASE CORRECT ON
 PLANS.
  
 4) CORRECTED ENERGY CAL'S. NEED TO BE
 SIGNED IN TWO PLACES AT THE BOTTOM.
  
 5) MECHANICAL PLANS ARE NOT SHOWING THE
 SIZE OF THE SUPPLY AIR DUCT LEAVING THE
 AIR HANDLER.
  
 6) RETURN AIR DUCT LEAVING THE AIR
 HANDLER IS NOT SIZED.
  
 7) SHOW THE CFM'S AT EACH SUPPLY AIR
 GRILL.
  
 8) SHOW THE SIZE OF EACH RETURN AIR
 GRILL.
  
 9) SHOW THE CLOTHES DRYER VENT AND
 TERMINATION ON MECHANICAL PLANS, PLEASE
 NOTE: CLOTHES DRYER VENT TERMINATION
 MUST BE A MIN. OF 4 FT. FROM A/C
 CONDENSER UNIT, PER 2004 FBC/M 501.2 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-08-15 Cont ID  
Sent By jleech Date 2006-08-15 Time 07:38 Rev Time 0.00
Received By jleech Date 2006-08-15 Time 07:37 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-06-16 Cont ID  
Sent By jleech Date 2006-06-16 Time 08:26 Rev Time 0.00
Received By jleech Date 2006-06-16 Time 08:26 Sent To M
Notes
2006-06-16 00:00:00DENIED;
 1.RISER DIAGRAM NOT TO CODE, NOT
 PROPERLY VENTED.
 2.DELETE NOTE 15, AN ENGINEERED WATER
 HAMMER ARRESTOR IS REQUIRED WHERE QUICK
 CLOSING VALVES EXIST. SEE SEC.604.9.
 3.WASHING MACHINE DETAIL; DISCHARGE PIPE
 TO BE 3" SEC. 406.3, A CLEANOUT IS
 REQUIRED AT 48" AFF.,AND WATER HAMMER
 ARRESTORS ARE REQUIRED.
 ONE SET OF PLANS MARKED IN RED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2006-08-05 Cont ID  
Sent By mmclean Date 2006-08-05 Time 07:55 Rev Time 0.00
Received By mmclean Date 2006-08-05 Time 07:55 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2006-06-09 Cont ID  
Sent By mmclean Date 2006-06-09 Time 16:00 Rev Time 0.00
Received By mmclean Date 2006-06-09 Time 16:00 Sent To I
Notes
2006-06-09 00:00:00DENIED,
 1. THE SETBACK OF THE EIXSTING GARAGE
 SITS BACK ABOUT 27FT FROM THE PROPERTY
 LINE AND THE NEW WILL BE 25FT AS
 INDICATED ON THE SITEPLAN, BUT THE FLOOR
 PLANS/ROOF PLAN ETC SHOWS IT AT THE
 EXISTING SETBACK (AS SURVEY) ABOUT 27FT.
 PLEASE HAVE THE SITEPLAN TO REFLECT
 CORRECTLY AS SHOWN ON THE FLOOR PLAN.
 ALL MUST MATCH THE SETBACK.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720