Plan Review Details - Permit 06051039
Plan Review Stops For Permit 06051039
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-05-25 Cont ID  
Sent By jgomez Date 2006-05-25 Time 15:22 Rev Time 0.50
Received By jgomez Date 2006-05-25 Time 15:22 Sent To PC
Notes
2006-05-25 00:00:00PERMIT UNDER "B".

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-25 Cont ID  
Sent By jgomez Date 2006-05-25 Time 07:50 Rev Time 0.33
Received By jgomez Date 2006-05-25 Time 07:50 Sent To  
Notes
2006-05-25 00:00:00BUILDING REVIEW CHECKLIST:
 1- ACCORDING TO THE DADE COUNTY NOA
 PRODUCT APPROVAL THE MAXIMUM DESIGN
 PRESSURE FOR THIS METAL ROOFING SYSTEM
 IS -57.5PSF. SEE PAGE 2 OF 5 OF DADE
 COUNTY NOA SUBMITTED.
 ROOF SYSTEM NEEDS TO RESIST AT LEAST
 -68.1PSF ACCORDING TO TABLE 1609.6B OF
 FBC 2004. THE DESIGN PRESSURES OF THIS
 SYSTEM MAY BE INCREASED BY RATIONAL
 ANALYSIS BY PROVIDING SIGNED AND SEALED
 CALCULATIONS PREPARED BY A FLORIDA
 PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF CONSULTANT
 AS REQUIRED BY SYSTEM LIMITATION #1 ON
 PAGE 5 OF 5 OF DADE COUNTY NOA. OR
 PROVIDE PRODUCT APPROVAL FOR ANOTHER
 METAL ROOF SYSTEM WITH DESIGN PRESSURES
 THAT MATCH OR EXCEED THE DESIGN
 PRESSURES CALCULATED IN THE TABLE
 1609.6B OF FBC 2004.
  
 2- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved