Plan Review Details - Permit 06051022
Plan Review Stops For Permit 06051022
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-07-19 Cont ID  
Sent By jwitmer Date 2006-07-19 Time 11:54 Rev Time 1.55
Received By jwitmer Date 2006-07-19 Time 11:07 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-06-21 Cont ID  
Sent By jwitmer Date 2006-06-21 Time 10:38 Rev Time 2.22
Received By jwitmer Date 2006-06-21 Time 10:38 Sent To PC
Notes
2006-06-21 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06051022
 ADD: 831 VILLAGE BLVD# 25
 CONT: PEMBERTON BUILDING
 TEL: (561)744-3399
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) 481.219 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING
 ARCHITECTURAL SERVICES, SHALL INCLUDE
 THE CERTIFICATE OF AUTHORIZATION
 NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 3) WOMENS RESTROOM 11-4.19.3 CLEAR FLOOR
 SPACE.
 A CLEAR FLOOR SPACE 30 INCHES BY 48
 INCHES (760 MM BY 1219 MM) COMPLYING
 WITH SECTION 11-4.2.4 SHALL BE PROVIDED
 IN FRONT OF A LAVATORY TO ALLOW FORWARD
 APPROACH. SUCH CLEAR FLOOR SPACE SHALL
 ADJOIN OR OVERLAP AN ACCESSIBLE ROUTE
 AND SHALL EXTEND A MAXIMUM OF 19 INCHES
 (485 MM) UNDERNEATH THE LAVATORY (SEE
 FIGURE 11-32 ).
  
 4) G1.0 CODE ANALYSIS
 4A) PLANS INDICATE TYPE IV, UNPROTECTED,
 SPRINKLERED, CORRECT TO THE 2004
 BUILDING TYPES2004 FBC IV IS HEAVY
 TIMBER.
  
 4B) CORRECT USE GROUP:303.1.1/309.1
 RESTAURANTS AND DRINKING ESTABLISHMENTS
 WITH AN OCCUPANT LOAD OF LESS THAN 50
 PERSONS SHALL BE CLASSIFIED AS GROUP M,
 MERCANTILE .
  
 5) 11-5.2 COUNTERS AND BARS.
 WHERE FOOD OR DRINK IS SERVED AT
 COUNTERS EXCEEDING 34 INCHES (865 MM) IN
 HEIGHT FOR CONSUMPTION BY CUSTOMERS
 SEATED ON STOOLS OR STANDING AT THE
 COUNTER, A PORTION OF THE MAIN COUNTER
 WHICH IS 60 INCHES (1525 MM) IN LENGTH
 MINIMUM SHALL BE PROVIDED IN COMPLIANCE
 WITH SECTION 11-4.32 OR SERVICE SHALL BE
 AVAILABLE AT ACCESSIBLE TABLES WITHIN
 THE SAME AREA.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-10-31 Cont ID  
Sent By btrobaug Date 2006-10-31 Time 11:25 Rev Time 0.75
Received By btrobaug Date 2006-10-31 Time 09:49 Sent To  
Notes
2006-10-31 11:24:54REVISION #32- 10/17/06
  
 MOP SINK, HAND SINK AND FILTER SYSTEM SWITCHED WALLS IN
 WORK ROOM(NORTH WEST CORNER).

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-09-26 Cont ID  
Sent By btrobaug Date 2006-09-26 Time 16:44 Rev Time 0.50
Received By btrobaug Date 2006-09-26 Time 16:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-07-14 Cont ID  
Sent By btrobaug Date 2006-07-14 Time 17:59 Rev Time 1.00
Received By btrobaug Date 2006-07-14 Time 17:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-09 Cont ID  
Sent By btrobaug Date 2006-06-09 Time 13:29 Rev Time 1.00
Received By btrobaug Date 2006-06-09 Time 12:26 Sent To  
Notes
2006-06-09 00:00:00 
 NONCOMPLIANT
  
 1} SHOW THE SERVICE MAIN DISCONNECT
 LOCATION ON A SITE PLAN.
  
 2} PROVIDE A LOAD CALCULATION FOR THE
 SERVICE SUPPLYING THESE SUB-PANELS.
  
 3} PLEASE PROVIDE CONDUCTOR SIZES ON THE
 PANEL SCHEDULE SO THAT BRANCH/FEEDER
 CIRCUIT CONDUCTOR AND OVER CURRENT
 PROTECTION COMPLIANCE MAY BE REVIEWED
 PER 106.3.5.4 FBC AS AMENDED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-07-17 Cont ID  
Sent By mcarsill Date 2006-07-17 Time 12:19 Rev Time 0.00
Received By mcarsill Date 2006-07-17 Time 12:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-06-14 Cont ID  
Sent By mwennerg Date 2006-06-14 Time 10:21 Rev Time 0.00
Received By mwennerg Date 2006-06-14 Time 10:21 Sent To  
Notes
2006-06-14 00:00:00***PROVISO***
  
 1) FIRE EXTINGUISHER(S) SHALL BE
 2A-10B,C RATED .
  
 2) LIFE SAFETY TO COMPLY WITH NFPA 101,
 2003 EDITION.
  
 3) CONSTRUCTION, ALTERATION AND
 DEMOLITION SHALL COMPLY WITH NFPA 241.
  
  
 IN ADDITION TO FIRE SPRINKLER, SEPARATE
 SHOP DRAWINGS AND PERMIT REQUIRED FOR
 FIRE ALARM REMODEL IF APPLICABLE.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-10-20 Cont ID  
Sent By adarroug Date 2006-10-20 Time 14:54 Rev Time 0.00
Received By adarroug Date 2006-10-20 Time 14:54 Sent To  
Notes
2006-10-27 13:44:32TO "BOB"#2
2006-10-20 14:54:38WAITING FOR "BOB"--REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-09-18 Cont ID  
Sent By adarroug Date 2006-09-18 Time 11:16 Rev Time 0.00
Received By adarroug Date 2006-09-18 Time 11:16 Sent To P
Notes
2006-09-18 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-09-18 Cont ID  
Sent By adarroug Date 2006-09-18 Time 11:11 Rev Time 0.00
Received By adarroug Date 2006-09-18 Time 11:11 Sent To  
Notes
2006-09-20 00:00:00TO "COMM' BD#11
2006-09-18 00:00:00WAITING FOR "BOB"-REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-07-31 Cont ID  
Sent By adarroug Date 2006-07-31 Time 10:43 Rev Time 0.00
Received By adarroug Date 2006-07-31 Time 10:43 Sent To  
Notes
2006-08-09 00:00:00TO "BOB"#13
2006-07-31 00:00:00WAITING FOR "BOB"--NEW STRUCTURAL SHEETS
 ADDED

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-06 Cont ID  
Sent By adarroug Date 2006-07-06 Time 14:32 Rev Time 0.00
Received By adarroug Date 2006-07-06 Time 14:32 Sent To  
Notes
2006-07-07 00:00:00TO "BOB"#2
2006-07-06 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-21 Cont ID  
Sent By jwitmer Date 2006-06-21 Time 10:38 Rev Time 0.00
Received By jwitmer Date 2006-05-25 Time 11:15 Sent To  
Notes
2006-05-25 00:00:00TO "BOB"#15

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2006-10-31 Cont ID  
Sent By tgordon Date 2006-10-31 Time 08:24 Rev Time 0.30
Received By tgordon Date 2006-10-31 Time 08:24 Sent To  
Notes
2006-10-31 08:25:21REVISION TO MECH. PLANS PAGE M-2.0.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-09-26 Cont ID  
Sent By rregueir Date 2006-09-26 Time 17:23 Rev Time 0.00
Received By rregueir Date 2006-09-26 Time 17:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-08-09 Cont ID  
Sent By tgordon Date 2006-08-09 Time 15:31 Rev Time 1.30
Received By tgordon Date 2006-08-09 Time 15:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-07-12 Cont ID  
Sent By tgordon Date 2006-07-12 Time 10:35 Rev Time 0.45
Received By tgordon Date 2006-07-12 Time 10:35 Sent To  
Notes
2006-07-12 00:00:00*** DENIED ***
 1) AS REQUESTED IN LAST REVIEW 5-31-06
 NOTE #1, PLEASE SHOW DETAILED
 INFORMATION ON, ANCHORING A/C CONDENSER
 UNIT "STAND" TO THE ROOF, AND STATE THAT
 IT WILL WITHSTAND 140 MPH WINDS, PER
 2004 FBC 1609. (SEE MECHANICAL PLAN PAGE
 M3.0).
  
 2) SEE MECHANICAL PLAN PAGE M3.0 .
 CABLES ARE NOT PERMITED TO OVERLAP
 CONDENSER UNITS, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-05-31 Cont ID  
Sent By tgordon Date 2006-05-31 Time 16:08 Rev Time 1.30
Received By tgordon Date 2006-05-31 Time 16:08 Sent To  
Notes
2006-05-31 00:00:00*** DENIED ***
 1) PLEASE SHOW DETAILED INFORMATION ON,
 ANCHORING A/C CONDENSER UNIT STAND TO
 THE ROOF, AND STATE THAT IT WILL
 WITHSTAND 140 MPH WINDS, PER 2004 FBC
 1609.
  
 2) A/C CONDENSATE DRAIN CAN NOT
 TERMINATE IN A MOP SINK, PER CITY CODE
 SEC. 90-125 (B) (5). PLEASE CORRECT.
  
 3) DUCT BOARD, AND DUCT INSULATION 1",
 PLEASE COMPLY WITH 2004 FBC
 13-410.ABC.2.2 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-10-31 Cont ID  
Sent By jleech Date 2006-10-31 Time 07:22 Rev Time 0.00
Received By jleech Date 2006-10-31 Time 07:22 Sent To  
Notes
2006-10-31 07:23:51REVISION;RELOCATED SOME EQUIPMENT OK

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-10-06 Cont ID  
Sent By jleech Date 2006-10-06 Time 08:33 Rev Time 0.00
Received By jleech Date 2006-10-06 Time 08:33 Sent To  
Notes
2006-10-06 00:00:00REVISION;
 DELETED GREASE TRAP. LETTER WITH PLANS
 FROM UTILITIES DEPARTMENT.

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-07-15 Cont ID  
Sent By jleech Date 2006-07-15 Time 11:05 Rev Time 0.00
Received By jleech Date 2006-07-15 Time 11:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-06-01 Cont ID  
Sent By jleech Date 2006-06-01 Time 12:46 Rev Time 3.00
Received By jleech Date 2006-06-01 Time 12:46 Sent To  
Notes
2006-06-01 00:00:00DENIED;
 1.SANITARY RISER DIAGRAM; MOP SINK TO GO
 TO GREASY WASTE NOT SANITARY.
 2.WATER RISER DIAGRAM; WATER HAMMER
 ARRESTORS TO BE INSTALLED PER. FBC-2004
 PLUMBING SEC. 604.9 AND MANUFATURE"S
 INSTALLATION INSRUCTIONS, AS CLOSE TO
 THE SOURCE OF HAMMER AS POSSIBLE.
 3.PAGE A0.0 AND P3.0, ADD TO NOTES "NO
 DEAD ENDS ARE PROHIBITED PER SEC. 704.5
 DEMO PLUMBING INSPECTION REQUIRED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695