Plan Review Details - Permit 06051007
Plan Review Stops For Permit 06051007
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-04-12 Cont ID  
Sent By kconrad Date 2007-04-12 Time 19:18 Rev Time 0.00
Received By kconrad Date 2007-04-12 Time 18:35 Sent To I
Notes
2007-04-12 19:18:00REVIEWED AS-BUILT PLANS/SURVEY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-10-27 Cont ID  
Sent By jwitmer Date 2006-10-27 Time 15:13 Rev Time 0.55
Received By jwitmer Date 2006-10-27 Time 15:13 Sent To PC
Notes
2006-10-27 15:14:14PERMIT READY TO ISSUE.JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-09-21 Cont ID  
Sent By jwitmer Date 2006-09-21 Time 16:49 Rev Time 0.77
Received By jwitmer Date 2006-09-21 Time 16:49 Sent To  
Notes
2006-09-21 00:00:00PLANS APPEAR CODE COMPLIANT, UNTIL
 IMPACT FEES ARE PAID PLANS WILL CONTINUE
 TO STAY IN THE FAILED STATIS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-08-04 Cont ID  
Sent By jwitmer Date 2006-08-04 Time 10:38 Rev Time 2.22
Received By jwitmer Date 2006-08-04 Time 10:38 Sent To M
Notes
2006-08-04 00:00:00PERMIT: 06051007
 ADD: 2001 PALM BCH LAKES BLVD.
 CONT: RIZNICK CONSTRUCTION
 TEL: ( )584-0363
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
 --- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1)COMPLIED.
  
 2) 2ND REQUEST: MISSING SOILS REPORT,
 1802.2.1 QUESTIONABLE SOIL.
 WHERE THE SAFE-SUSTAINING POWER OF THE
 SOIL IS IN DOUBT, OR WHERE A
 LOAD-BEARING VALUE SUPERIOR TO THAT
 SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL REQUIRE THAT THE
 NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE
 PROVISIONS OF SECTIONS 1802.4 THROUGH
 1802.6 .
  
 3) COMPLIED.
  
 3B) COMPLIED.
  
 3C)MISSING MINIMUM DESIGN CRITERIA:
 3C)(B) PROPOSED USE: SHEET A-1
 PROJECT DATA SUMMARY, THE DESIGNER IS
 NOT DISTINGIUSHING BETWEEN THE ZONING
 AND BUILDING TERMINOLOGY. ONCE THE
 DESIGNER STARTS TO LIST BUILDING CODE
 EDITION, THE TERMINOLOGY WILL BE AS WHAT
 IS REQUIRED IN SECTION 110.1.2*PROPOSED
 USE BUSINESS "GROUP B" SEE 304.1.
  
 3D) OCCUPANT LOAD: SEE TABLE 1004.1.4
 BUISINESS AREAS/ 100 GROSS
  
 3B)(E-I) COMPLIED.
  
 3D) 2ND REQUEST:
 3D) MISSING THE WIND DESIGN INTERNAL
 PRESSURE COEFFICIENT WHEN DESIGNED TO
 ASCE 7-02. 1603.1.4(4) THE APPLICABLE
 ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE
 COEFFICIENT.
 THE STATEMENT ABOVE MAY BE ABIT
 MISLEADING. THE FIRST REVIEW THE PLANS
 CAME INDICATING THEY ERE DESIGNED TO
 ASCE 7-98. THE STATEMENT THAT I WAS
 TRYINF TO MAKE IS (2) FOLD.
 (I) THE DESIGNER HAS THE OPTION TO
 DESIGN TO EITHER ASCE 7-02 OR TSKE THE
 EXCEPTION (1) AND DESIGN TO 1609.6.
 (II) IF THE DESIGNER DOES DESIGN TO
 ASCE 7-02 THE TERM THAT SHOULD OF BEEN
 USED IS "ENCLOSURE CLASSIFICATION"NOT
 INTERNAL PRESSURE COEFFICIENT.
 THIS BUILDING WHEN DESIGNED TO ASCE
 7-02 SHALL BE CLASSIFIED AS EITHER
 PARTIALLY OPEN OR OPEN.
 SEE SECTION 6.5.12 FOR PARTIALLY OPEN
 AND THE COEFFICIENT, IF THE OPEN
 CLASSIFICATION (SEE 6.5.13) IS
 APPLICABLE USE THE CORRECT COEFFICIENT.
  
 4) 2ND REQUEST, 4) PROVIDE ADDITIONAL
 INFORMATION, PERMIT APPLICATION PROJECT
 DESCRIPTION, IS ONLY FOR DRIVE THROUGH
 AND NOT LANDSCAPING, REPAVING OR CURBING
 OR STRIPING OF THE CURRENT SITE? IF SO
 INCLUDE UNDER PERMIT DESCPTION.
  
 5) COMPLIED.
  
 6) 2ND REQUEST,A-2/ A-3 BOTH INDICATE
 THE USE OF (2), NOW(4) SCUPPERS ON THE
 EAST AND WEST ELEVATIONS, PLANS DO NOT
 INDICATE OVERFLOW SCUPPERS. 1503.4.3
 WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW
 WATER IS NOT PROVIDED, OVERFLOW SCUPPERS
 SHALL BE PLACED IN WALLS OR PARAPETS NOT
 LESS THAN 2 INCHES (51 MM) NOR MORE THAN
 4 INCHES (102 MM) ABOVE THE FINISHED
 ROOF COVERING AND SHALL BE LOCATED AS
 CLOSE AS PRACTICAL TO REQUIRED VERTICAL
 LEADERS OR DOWNSPOUTS OR WALL AND
 PARAPET SCUPPERS. AN OVERFLOW SCUPPER
 SHALL BE SIZED IN ACCORDANCE WITH THE
 FLORIDA BUILDING CODE, PLUMBING.
 A-4 NOW INDICATES THERE ARE (4)
 THROUGH THE WALL SCUPPERS SHOWN ON A-4.
 I BELIEVE THERE IS A DIFFERENCE IN
 UNDERSTANDING OF TERMINOLGY IN THIS CODE
 SECTION.
 SEE 1503.4.2 SCUPPERS: WHERE REQUIRED
 FOR ROOF DRAINAGE, A SCUPPER SHALL BE
 PLACED "LEVEL" WITH THE ROOF SURFACE IN
 A WALL OR PARAPET. THE SCUPPER SHALL BE
 LOCATED AS DETERMINED BY THE SLOPE AND
 THE CONTRIBUTING AREA OF THE ROOF. THE
 EXTERIOR FACING OR LINING OF A SCUPPER,
 IF METAL, SHALL BE THE SAME AS FLASHING
 MATERIAL REQUIRED BY SECTIONS 1503
 THROUGH 1510 FOR THE PARTICULAR TYPE OF
 COVERING SPECIFIED FOR THE BUILDING. FOR
 OTHER TYPE MATERIALS, FOLLOW
 MANUFACTURER?S SPECIFICATIONS.
 THE CODE SECTION STATED IN 1503.4.3
 IS THE REQUIREMENT FOR ADDITIONAL
 OVERFLOW SCUPPERS IN CASE THE SCUPPERS
 LOCATED AT THE ROOF LEVEL ARE BLOCKED.
 FOR EACH SCUPPER AN ADDITIONAL OVERFLOW
 SCUPPER WILL BE REQUIRED, LOCATED WITH
 THE BOTTOM OF THE SCUPPER LOCATED
 BETWEEN 2"-4" ABOVE THE FINISHED ROOF.
  
 7) COMPLIED.
  
 8) 2ND REQUEST, SHEET A-3 NOTE FOR USE
 OF ALTERNATE MATERIALS FOR CEILING
 APPLICATION.
 PROVIDE ADDTIONAL INFORMATION ON THE
 TYPE OF WIRE LATH TO BE USED?
 2510.3INSTALLATION OF THESE MATERIALS
 SHALL BE IN COMPLIANCE WITH ASTM C 926
 AND ASTM C 1063.
 RULE 9B-72 PRODUCT APPROVAL FOR "PROROC
 EXTERIOR SOFFIT BOARD W/ FLORIDA STATE
 APPROVAL.
 104.1.1* ALTERNATE MATERIALS, DESIGN
 & METHODS OF CONSTRUCTION & EQUIPMENT.
 THE PROVISIONS OF THIS CODE ARE NOT
 INTENDED TO PREVENT THE INSTALLATION OF
 ANY MATERIAL OR TO PROHIBIT ANY DESIGN
 OR METHOD OF CONSTRUCTION NOT
 SPECIFICALLY PRESCRIBED BY THIS CODE,
 PROVIDED THAT ANY SUCH ALTERNATIVE HAS
 BEEN APPROVED. AN ALTERNATE MATERIAL,
 DESIGN OR METHOD OF CONSTRUCTION SHALL
 BE APPROVED WHERE THE BUILDING OFFICIAL
 FINDS THAT THE PROPOSED DESIGN IS
 SATISFACTORY AND COMPLIES WITH THE
 INTENT OF THE PROVISIONS OF THIS CODE,
 AND THAT THE MATERIAL, METHOD OR WORK
 OFFERED IS, FOR THE PURPOSE INTENDED, AT
 LEAST THE EQUIVALENT OF THAT PRESCRIBED
 IN THIS CODE IN QUANITY, STRENGTH,
 EFFECTIVENESS FIRE RESISTANCE,
 DURABILITY AND SAFETY. WHEN ALTERNATE
 LIFE SAFETY SYSTEMS ARE DESIGNED, THE
 SFPE ENGINEERING GUIDE TO
 PERFORMANCE-BASED FIRE PROTECTION
 ANALYSIS AND DESIGN OF BUILDINGS , OR
 OTHER METHODS APPROVED BY THE BUILDING
 OFFICIAL MAY BE USED. THE BUILDING
 OFFICIAL SHALL REQUIRE THAT SUFFICIENT
 EVIDENCE OR PROOF BE SUBMITTED TO
 SUBSTANTIATE ANY CLAIM MADE REGARDING
 THE ALTERNATIVE.
 SHEET A-3 STILL INDICATES AN
 ALTERNATE SYSTEM, EVEN THOUGH DESIGN
 TEAM COMMENT SHEET INDICATES 2.5#
 GALVANIZED EXPANDED METAL DIAMOND MESH.
 SHEET S1OF 2 DETAIL SECTION1/S-1,
 INDICATES THE USE OF 1X FURRING AT 2'-0"
 O.C. SEE ASTM C1063 TABLE 3 TYPES AND
 WEIGHTS OF METAL PLASTER BASES AND
 CORRESPONDING MAXIMUM PERMISSIBLE
 SPACING OF SUPPORTS.CEILINGS, WOOD
 ASSEMBLIES ARE NOT TO SPAN MORE THAN 12"
 O.C.
  
 9)2ND REQUEST, FL BLD CODE 1609.6.2.1:
 COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) TRUSS ANCHORS
 B) PANEL WALLS- SOFFITS- PROROC
 EXTERIOR SOFFIT BOAARD.
 C) ROOFING ASSEMBLIES
  
 NOTE: WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
 NOTE ROOFING NOA, SYSTEMS LIMITATIONS VS
 ENHANCED FASTENING!!!!!
  
 10) 2ND REQUEST, PRODUCT APPROVALS
 SUBMITTED WITH PERMIT APPLICATION AFTER
 OCTOBER 1, 2003 ARE REQUIRED TO COMPLY
 WITH THE FLORIDA PRODUCT APPROVAL
 SYSTEM. FOR INFORMATION PLEASE SEE THE
 STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 11) COMPLIED.
  
 12) COMPLIED.
  
 13) COMPLIED.
  
 14) COMPLIED.
  
 15) COMPLIED.
  
 16) 2ND REQUEST,
 BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-06-20 Cont ID  
Sent By jwitmer Date 2006-06-20 Time 12:34 Rev Time 3.33
Received By jwitmer Date 2006-06-20 Time 12:34 Sent To  
Notes
2006-06-20 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06051007
 ADD: 2001 PALM BCH LAKES BLVD.
 CONT: RIZNICK CONSTRUCTION
 TEL: ( )584-0363
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 2) MISSING SOILS REPORT,
 1802.2.1 QUESTIONABLE SOIL.
 WHERE THE SAFE-SUSTAINING POWER OF THE
 SOIL IS IN DOUBT, OR WHERE A
 LOAD-BEARING VALUE SUPERIOR TO THAT
 SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL REQUIRE THAT THE
 NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE
 PROVISIONS OF SECTIONS 1802.4 THROUGH
 1802.6 .
  
 3) S2-2: STRUCTURAL DESIGN CRITERIA,
 3A) THE PLANS STATE THEY ARE DESIGNED
 UNDER FBC 2001, PERMIT APPLICATIONS
 SUBMITTED AFTER SEPT30, 2005 REQUIRED
 DESIGN TO BE THE 2004 FLORIDA BUILDING
 CODE.
  
 3B) WIND DESIGN CRITERIA, DESIGN TO BE
 UNDER THE ASCE 7-02 SEE REFRENCE
 STANDARD CHAPTER 35.
  
 3C) MISSING MINIMUM BUILDINGDESIGN
 CRITERIA,110.2* W. P. B.
 ADMINISTRATIVE CODE, INFORMATION THAT IS
 REQUIRED FOR RECORD KEEPING & FOR
 CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 G) FLOOD ZONE
 H) FLOOD ELEVATION
 I)L.O.M.R.
  
 3D) MISSING THE WIND DESIGN INTERNAL
 PRESSURE COEFFICIENT WHEN DESIGNED TO
 ASCE 7-02. 1603.1.4(4) THE APPLICABLE
 ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE
 COEFFICIENT.
  
 4) PROVIDE ADDITIONAL INFORMATION,
 PERMIT APPLICATION PROJECT DESCRIPTION,
 IS ONLY FOR DRIVE THROUGH AND NOT
 LANDSCAPING, REPAVING OR CURBING OR
 STRIPING OF THE CURRENT SITE? IF SO
 INCLUDE UNDER PERMIT DESCPTION.
  
 5) PROVIDE CUT SECTION THROUGH DRIVE
 THROUGH INDICATING COMPLIANCE WITH AN
 ACCISSIBLE ATM AND NEW ROMOTE TELLAR
 STATIONS.11-4.2/ 11-7.2(2).
  
 6) A-2/ A-3 BOTH INDICATE THE USE OF (2)
 SCUPPERS ON THE EAST AND WEST
 ELEVATIONS, PLANS DO NOT INDICATE
 OVERFLOW SCUPPERS. 1503.4.3
 WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW
 WATER IS NOT PROVIDED, OVERFLOW SCUPPERS
 SHALL BE PLACED IN WALLS OR PARAPETS NOT
 LESS THAN 2 INCHES (51 MM) NOR MORE THAN
 4 INCHES (102 MM) ABOVE THE FINISHED
 ROOF COVERING AND SHALL BE LOCATED AS
 CLOSE AS PRACTICAL TO REQUIRED VERTICAL
 LEADERS OR DOWNSPOUTS OR WALL AND
 PARAPET SCUPPERS. AN OVERFLOW SCUPPER
 SHALL BE SIZED IN ACCORDANCE WITH THE
 FLORIDA BUILDING CODE, PLUMBING.
  
 7) A-2/ A-3 BOTH INDICATE THE USE OF
 SCUPPERS.1503.6 PROTECTION AGAINST DECAY
 AND TERMITES.
 CONDENSATE LINES AND ROOF DOWNSPOUTS
 SHALL DISCHARGE AT LEAST 1 FOOT (305 MM)
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL
 EXTENSIONS, OR SPLASH BLOCKS. GUTTERS
 WITH DOWNSPOUTS ARE REQUIRED ON ALL
 BUILDINGS WITH EAVES OF LESS THAN 6
 INCHES (152 MM) HORIZONTAL PROJECTION
 EXCEPT FOR GABLE END RAKES OR ON A ROOF
 ABOVE ANOTHER ROOF.
  
 8) SHEET A-3 NOTE FOR USE OF ALTERNATE
 MATERIALS FOR CEILING APPLICATION.
 PROVIDE ADDTIONAL INFORMAATION ON THE
 TYPE OF WIRE LATH TO BE USED?
 2510.3INSTALLATION OF THESE MATERIALS
 SHALL BE IN COMPLIANCE WITH ASTM C 926
 AND ASTM C 1063.
 RULE 9B-72 PRODUCT APPROVAL FOR "PROROC
 EXTERIOR SOFFIT BOARD W/ FLORIDA STATE
 APPROVAL.
 ) 104.1.1* ALTERNATE MATERIALS, DESIGN
 & METHODS OF CONSTRUCTION & EQUIPMENT.
 THE PROVISIONS OF THIS CODE ARE NOT
 INTENDED TO PREVENT THE INSTALLATION OF
 ANY MATERIAL OR TO PROHIBIT ANY DESIGN
 OR METHOD OF CONSTRUCTION NOT
 SPECIFICALLY PRESCRIBED BY THIS CODE,
 PROVIDED THAT ANY SUCH ALTERNATIVE HAS
 BEEN APPROVED. AN ALTERNATE MATERIAL,
 DESIGN OR METHOD OF CONSTRUCTION SHALL
 BE APPROVED WHERE THE BUILDING OFFICIAL
 FINDS THAT THE PROPOSED DESIGN IS
 SATISFACTORY AND COMPLIES WITH THE
 INTENT OF THE PROVISIONS OF THIS CODE,
 AND THAT THE MATERIAL, METHOD OR WORK
 OFFERED IS, FOR THE PURPOSE INTENDED, AT
 LEAST THE EQUIVALENT OF THAT PRESCRIBED
 IN THIS CODE IN QUANITY, STRENGTH,
 EFFECTIVENESS FIRE RESISTANCE,
 DURABILITY AND SAFETY. WHEN ALTERNATE
 LIFE SAFETY SYSTEMS ARE DESIGNED, THE
 SFPE ENGINEERING GUIDE TO
 PERFORMANCE-BASED FIRE PROTECTION
 ANALYSIS AND DESIGN OF BUILDINGS , OR
 OTHER METHODS APPROVED BY THE BUILDING
 OFFICIAL MAY BE USED. THE BUILDING
 OFFICIAL SHALL REQUIRE THAT SUFFICIENT
 EVIDENCE OR PROOF BE SUBMITTED TO
 SUBSTANTIATE ANY CLAIM MADE REGARDING
 THE ALTERNATIVE.
  
 9) FL BLD CODE 1609.6.2.1: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) TRUSS ANCHORS
 B) PANEL WALLS- SOFFITS- PROROC
 EXTERIOR SOFFIT BOAARD.
 C) ROOFING ASSEMBLIES
  
 NOTE: WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
 NOTE ROOFING NOA, SYSTEMS LIMITATIONS VS
 ENHANCED FASTENING!!!!!
  
 10)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 11) A3 PLANS DO NOT INDICATE TERMITE
 TREATMENT OF SLAB.
 1816.1 TERMITE PROTECTION.
 TERMITE PROTECTION SHALL BE PROVIDED BY
 REGISTERED TERMITICIDES, INCLUDING SOIL
 APPLIED PESTICIDES, BAITING SYSTEMS, AND
 PESTICIDES APPLIED TO WOOD, OR OTHER
 APPROVED METHODS OF TERMITE PROTECTION
 LABELED FOR USE AS A PREVENTATIVE
 TREATMENT TO NEW CONSTRUCTION. SEE
 SECTION 202 , REGISTERED TERMITICIDE.
 UPON COMPLETION OF THE APPLICATION OF
 THE TERMITE PROTECTIVE TREATMENT, A
 CERTIFICATE OF COMPLIANCE SHALL BE
 ISSUED TO THE BUILDING DEPARTMENT BY THE
 LICENSED PEST CONTROL COMPANY THAT
 CONTAINS THE FOLLOWING STATEMENT: ?THE
 BUILDING HAS RECEIVED A COMPLETE
 TREATMENT FOR THE PREVENTION OF
 SUBTERRANEAN TERMITES. TREATMENT IS IN
 ACCORDANCE WITH RULES AND LAWS
 ESTABLISHED BY THE FLORIDA DEPARTMENT OF
 AGRICULTURE AND CONSUMER SERVICES.?
  
 12) VENTING:1203.2 ATTIC SPACES.
 ENCLOSED ATTICS AND ENCLOSED RAFTER
 SPACES FORMED WHERE CEILINGS ARE APPLIED
 DIRECTLY TO THE UNDERSIDE OF ROOF
 FRAMING MEMBERS SHALL HAVE CROSS
 VENTILATION FOR EACH SEPARATE SPACE BY
 VENTILATING OPENINGS PROTECTED AGAINST
 THE ENTRANCE OF RAIN. BLOCKING AND
 BRIDGING SHALL BE ARRANGED SO AS NOT TO
 INTERFERE WITH THE MOVEMENT OF AIR. A
 MINIMUM OF 1 INCH (25 MM) OF AIRSPACE
 SHALL BE PROVIDED BETWEEN THE INSULATION
 AND THE ROOF SHEATHING. THE NET FREE
 VENTILATING AREA SHALL NOT BE LESS THAN
 1 / 150 OF THE AREA OF THE SPACE
 VENTILATED, WITH 50 PERCENT OF THE
 REQUIRED VENTILATING AREA PROVIDED BY
 VENTILATORS LOCATED IN THE UPPER PORTION
 OF THE SPACE TO BE VENTILATED AT LEAST 3
 FEET (914 MM) ABOVE EAVE OR CORNICE
 VENTS WITH THE BALANCE OF THE REQUIRED
 VENTILATION PROVIDED BY EAVE OR CORNICE
 VENTS.
  
 13)STRUCTURAL SHEETS: SEALED BY
 ARCHITECT, IF CONSULTING ENGINEER
 DESIGNED THIS STRUCTURE, PLANS SHOULD BE
 SEALED BY ENGINEER.FL S. S. 471,
 OTHERWISE WHY IS HIS TITLEBLOCK ON THIS
 SHEET.
  
 14) ARCHITECTS TITLE BLOCK:
 ) 61G1-16.004FL. ADMIN. CODE.PLANS
 PREPARED BY A REGISTERED ARCHITECT SHALL
 INCLUDE A TITLE BLOCK WHICH MUST:
 - STATE THE FIRM NAME, ADDRESS AND
 TELEPHONE NUMBER
 - STATE THE FIRM LICENSE NUMBER
 - STATE PROJECT NAME OR IDENTIFICATION
 - STATE DATE PREPARED
 - INCLUDE AN ORIGINAL SIGNATURE AND
 DATED SEAL
 - INCLUDE THE PRINTED NAME OF THE
 ARCHITECT SEALING THE PLANS
  
 15) ARCHITECTURAL & STRUCTURAL SHEETS:
 ARCHITECT BUSINESS: OXIOS ARCHITECTS,
 P.A. ON SOME SHEETS USES THE FIRMS
 LICENSE NUMBER ON OTHER SHEETSOVIDIO
 OXIOS LICENSE NUMBER, NOT THE FIRMS
 LICENSE NUMBER. ) 481.219 F.S.
 CERTIFICATE OF AUTHORIZATION.THE TITLE
 BLOCK FOR ANY SHEET BEARING THE NAME OF
 AN ARCHITECT PRACTICING UNDER A
 FICTITIOUS NAME, A CORPORATION, OR A
 PARTNERSHIP, OFFERING ARCHITECTURAL
 SERVICES, SHALL INCLUDE THE CERTIFICATE
 OF AUTHORIZATION
 NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 16) BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH CO.,THE PERMIT PLANS STAMPED BY
 THEM AND THE RECEIPT ATTACHED TO THE
 PERMIT APPLICATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-09-28 Cont ID  
Sent By dpalmer Date 2006-09-28 Time 13:25 Rev Time 0.00
Received By dpalmer Date 2006-09-28 Time 13:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-07-19 Cont ID  
Sent By dpalmer Date 2006-07-19 Time 21:21 Rev Time 0.00
Received By dpalmer Date 2006-07-19 Time 21:16 Sent To M
Notes
2006-08-07 00:00:00** NOTE: PLEASE SEE SHEETS CONTAINING
 THE AIR/REMOTE DRIVE UP SYSTEM SHALL
 CONTAIN THE SIGNATURE OF THE PERSON
 RESPONSIBLE FOR PLANS AND DESIGNS.
 FBC 106.1.2
2006-07-19 00:00:00********* UNSAT ********
  
 1) NOTE: PLEASE SUBMIT COMPLETE SETS OF
 PLANS FOR REVIEW. PLEASE SEE ONLY SHEET
 E-2 IS IN TWO OF THE THREE SETS
 SUBMITTED AND THE SET #3 DOES NOT
 CONTAIN ANY ELECTRICAL SHEETS?
 PLEASE SEE COVER SHEET INDICATES SHEETS
 1 OF 3, 2 OF 3 AND 3 OF 3.
  
 2) NOTE: PLEASE SEE PREVIOUS REVIEW, AS
 REQUESTED TO SEE THE FAC 61G1-16.004 AND
 FS 481.219, 221. PLEASE SEE THE FAC
 REQUIRES THE "PRINTED NAME AND PRINTED
 LICENSE # OF SAID ARCHITECT ON TITLE
 BLOCKS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-15 Cont ID  
Sent By dpalmer Date 2006-06-15 Time 17:27 Rev Time 0.00
Received By dpalmer Date 2006-06-15 Time 15:52 Sent To  
Notes
2006-06-15 00:00:00******** UNSAT *********
  
 1) NOTE: PLEASE SEE MISSING GROUNDING
 ELECTRODE SYSTEM AT DETACHED BUILDING AS
 REQUIRED PER 250.32
  
 2) NOTE: COULD NOT LOCATE RELEVANT
 ADOPTED CODES ON SAID PLANS.
 106.2.1
 PLEASE SEE AT A MIN , THE 2004 FBC AND
 NFPA-70 2002 SHALL BE INDICATED.
  
 3) NOTE: PLEASE SEE THE "PLAN COMPLIANCE
 AFFIDAVIT" AND THE ""PLAN REVIEW SERVICE
 AGREEMENT" IS INVALID AS NEITHER
 DOCUMENT CONTAINS AN ORIGINAL
 SIGNATURE BY SAID ENGINEER MR. R.
 KENNETH DERICK.
 ** PLEASE KNOW, AFFIDAVITS ARE BEING
 RETAINED BY THIS OFFICE.
 PLANS AND PAPERWORK IS BEING TURNED OVER
 TO THE ASSISTANT BUILDING AND BUILDING
 OFFICAL FOR REVIEW. OTHER TRADES TO
 REVIEW PLANS FOR CODE COMPLIANCE.
 PLEASE SEE FS 553.791
  
 4) NOTE:PLEASE SEE FS 553.791(4)(G)
 WHICH DEFINES "PROVIDE PROVIDER" AND
 SERVICE WHICH IS LIMITED TO RESIDENTIAL
 BUILDINGS, 1000 SQ FTETC.
  
 5) NOTE: PLEASE SEE FLORIDA
 ADMINISTRATIVE CODE 61G1-16.004 WHICH
 REQUIRES THE PRINTED NAME AND LICENSE
 NUMBER OF SAID ARCHITECT ON TITLE
 BLOCKS. PLEASE ALSO SEE THE CERTIFICATE
 OF AUTHORIZATION IS ALSO REQUIRED ON
 EACH OF THE TITLE BLOCKS.
 PLEASE SEE SOME TITLE BLOCKS CONTAIN THE
 PRINTED LICENSE NUMBER OF ARCHITECT AND
 SOME CONTAIN THE PRINTED CA #.
 PLEASE SEE BOTH ARE REQUIRED AND THE
 PRINTED NAME COULD NOT BE LOCATED ON ANY
 SHEETS.
 PLEASE KNOW, THIS IS REQUIRED OF ALL
 SHEETS AND FOR ALL TRADES WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
 6) NOTE: PLEASE KNOW, THE CERTIFICATE OF
 LIABILITY FOR UNIVERSAL ENGINEERING
 SERVICES WHICH WAS SUBMITTED TO THE CITY
 OF WEST PALM BEACH WAS MADE OUT TO "PALM
 BEACH COUNTY" WHICH IS ANOTHER
 JURISTICTION.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-06-16 Cont ID  
Sent By mcarsill Date 2006-06-16 Time 14:35 Rev Time 0.00
Received By mcarsill Date 2006-06-16 Time 14:31 Sent To  
Notes
2006-06-16 00:00:001. ALL ELECTRICAL WORK TO ACCOMPLISH THE
 PERMITTED WORK SHALL MEET ACCEPTABLE
 STANDARDS AND NFPA 70, THE NATIONAL
 ELECTRICAL CODE.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-10-25 Cont ID  
Sent By adarroug Date 2006-10-25 Time 19:41 Rev Time 0.00
Received By adarroug Date 2006-10-25 Time 19:41 Sent To B
Notes
2006-10-25 19:42:01TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-09-12 Cont ID  
Sent By adarroug Date 2006-09-12 Time 11:40 Rev Time 0.00
Received By adarroug Date 2006-09-12 Time 11:40 Sent To  
Notes
2006-09-25 00:00:00TO "COMM" BD#20
2006-09-12 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-18 Cont ID  
Sent By adarroug Date 2006-07-18 Time 14:30 Rev Time 0.00
Received By adarroug Date 2006-07-18 Time 14:30 Sent To E
Notes
2006-07-18 00:00:00TO "DPALMER" DESK/RESUB
2006-07-17 00:00:00PRIVATE PROVIDER PROJECT:
 INFORM LUIS OR ROBERT WHEN PLANS ARE
 RE-SUBMITTED
 *************************

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-26 Cont ID  
Sent By pkrauss Date 2006-06-26 Time 06:57 Rev Time 0.00
Received By pkrauss Date 2006-05-25 Time 11:21 Sent To  
Notes
2006-06-12 00:00:00TO "COMM" BD#51
2006-05-25 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-10-10 Cont ID  
Sent By pkrauss Date 2006-10-10 Time 16:19 Rev Time 0.00
Received By pkrauss Date 2006-10-10 Time 15:31 Sent To  
Notes
2006-10-10 16:22:41MECHANICAL PERMIT REQUIRED

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2006-08-07 Cont ID  
Sent By pkrauss Date 2006-08-07 Time 07:30 Rev Time 0.00
Received By pkrauss Date 2006-08-07 Time 07:30 Sent To  
Notes
2006-08-07 00:00:00NO MECHANICAL PLANS OR CONTRACTOR
 SUBMITTED WITH PERMIT APPLICATION.
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 WITH A MECHANICAL PERMIT APPLICATION.
  
 PLAN SHEET E-2 INDICATES A PTAC UNIT
 PLEASE INDICATE ON THE PLAN WHERE THE
 PTACT WILL BE INSTALLED.
  
 PLEASE INDICATE CONDENSATE TERMINATION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-06-26 Cont ID  
Sent By pkrauss Date 2006-06-26 Time 06:50 Rev Time 0.00
Received By pkrauss Date 2006-06-26 Time 06:50 Sent To  
Notes
2006-06-26 00:00:00DENIED:
 PLEASE PROVIDE MANUFACTURE INSTALLATION
 INSTRUCTIONS FOR THE PNEUMATIC TRANSFER
 TERMINAL INDICATED ON PLAN SHEET E1.
  
 PLAN SHEET E2 INDICATES A PTAC UNIT.
 MECHANICAL PERMIT REQUIRED.

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-06-26 Cont ID  
Sent By pkrauss Date 2006-06-26 Time 06:57 Rev Time 0.00
Received By pkrauss Date 2006-06-26 Time 06:57 Sent To  
Notes
2006-06-26 00:00:00NO PLUMBING WORK INDICATED

Review Stop Z ZONING
Rev No 2 Status P Date 2006-09-29 Cont ID  
Sent By mmclean Date 2006-09-29 Time 16:03 Rev Time 0.00
Received By mmclean Date 2006-09-29 Time 16:03 Sent To  
Notes
2006-09-29 00:00:00SHIRLEY, DID THE INFORMATION, WHICH WAS
 APPROVED.

Review Stop Z ZONING
Rev No 1 Status P Date 2006-06-22 Cont ID  
Sent By mmclean Date 2006-06-22 Time 11:03 Rev Time 0.00
Received By mmclean Date 2006-06-22 Time 11:03 Sent To  
Notes
2006-06-22 00:00:00INFORMAL WAS APPROVED.