Plan Review Details - Permit 06050911
Plan Review Stops For Permit 06050911
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-08-21 Cont ID  
Sent By amorse Date 2006-08-21 Time 08:53 Rev Time 0.00
Received By amorse Date 2006-08-21 Time 08:53 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-08-03 Cont ID  
Sent By amorse Date 2006-08-03 Time 16:22 Rev Time 0.00
Received By amorse Date 2006-08-03 Time 16:22 Sent To PC
Notes
2006-08-03 00:00:00 
  
 DENIED
  
 1) STRUCTURAL MULLION DESIGN REQUIRES
 MORE INFORMATION.
 A) HOW PLATE IS CONNECTED TO POST (NO
 WELD SPECIFIED)
 B) NO ELEVATION DETAIL, SHOW WHERE THE
 MULLION IS ATTACHED TOP AND BOTTOM AND
 THE STRUCTURE TO WHICH IT IS ATTACHED
 C) PROVIDE WIND DESIGN CRITERIA PER
 1603.1.4 FBC
 D) PROVIDE INFORMATION THAT DESIGN WILL
 MEET ALL LOAD CONDITIONS AND IS
 COMPATIBLE WITH A CURRENT STORE FRONT
 PRODUCT APPROVAL
 E) ENGINEER'S STAMP AND SIGNATURE IS ON
 THE BACK OF THE DRAWING
  
 ****NOTE DUE TO THE MANY DEFICIENCIES
 ONE COPY OF THIS DRAWING HAS BEEN
 RETAINED AND WILL BE FORWARDED TO THE
 FLORIDA BOARD OF PROFSIONAL ENGINEERS***
  
 2) PROVIDE STORE FRONT PRODUCT APPROVALS
 PLEASE BE SURE THAT THEY ARE LARGE
 MISSLE RATED (SOME ARE ONLY SMALL MISSLE
 RATED FOR USE ABOVE 30 FT)
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-06-21 Cont ID  
Sent By amorse Date 2006-06-21 Time 15:39 Rev Time 1.00
Received By amorse Date 2006-06-21 Time 15:39 Sent To PC
Notes
2006-06-21 00:00:00 
  
 DENIED
  
 1) PRODUCT APPROVALS FOR PGT FIXED
 WINDOWS DO NOT COVER THE WINDOW SIZES
 FOR FAMILY ROOM OR DINING ROOM IN THE
 TABLES OF NOA
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-06-02 Cont ID  
Sent By amorse Date 2006-06-02 Time 11:22 Rev Time 1.00
Received By amorse Date 2006-06-02 Time 11:22 Sent To PC
Notes
2006-06-02 00:00:00 
  
 DENIED
  
 1) PROVIDE NEW UPDATED PRODUCT APPROVALS
 FOR SINGLE HUNG WINDOWS AND SG. PLEASE
 NOTE THAT THEIR ARE SEPARATE NOA'S FOR
 THE SGD'S DEPENDING ON THE CONFIGURATION
 OX OR XO AND OXXO IF USING BOTH SUBMIT
 BOTH NOA'S WITH THE NEW FLORIDA COVER
  
 2) PROVIDE MORE INFORMATION FOR STORM
 PANELS, PLEASE MARK NOA WITH THE TYPE OF
 MOUNTING METHOD BEING USED ( DIRECT, H
 HEADER, STUDDED ANCHOR,ETC) TYPE OF
 FASTENER, TYPE OF CONSTRUCTION. PLEASE
 SEE ATTACHED PROCEDURES AND INSTALLATION
 SCHEDULE
  
 3) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-08-17 Cont ID  
Sent By adarroug Date 2006-08-17 Time 14:53 Rev Time 0.00
Received By adarroug Date 2006-08-17 Time 14:53 Sent To B
Notes
2006-08-17 00:00:00TO "AMORSE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-03 Cont ID  
Sent By adarroug Date 2006-08-03 Time 11:28 Rev Time 0.00
Received By adarroug Date 2006-08-03 Time 11:28 Sent To B
Notes
2006-08-03 00:00:00TO "AMORSE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-21 Cont ID  
Sent By adarroug Date 2006-06-21 Time 10:54 Rev Time 0.00
Received By adarroug Date 2006-06-21 Time 10:54 Sent To B
Notes
2006-06-21 00:00:00TO "AMORSE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-02 Cont ID  
Sent By adarroug Date 2006-06-02 Time 10:54 Rev Time 0.00
Received By rbrown Date 2006-05-24 Time 17:49 Sent To  
Notes
2006-05-24 00:00:00TO "MISC" BOX#1