Plan Review Details - Permit 06050904
Plan Review Stops For Permit 06050904
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-08-07 Cont ID  
Sent By alange Date 2006-08-07 Time 11:27 Rev Time 0.75
Received By alange Date 2006-08-07 Time 11:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-07-19 Cont ID  
Sent By alange Date 2006-07-19 Time 11:09 Rev Time 1.00
Received By alange Date 2006-07-19 Time 11:09 Sent To  
Notes
2006-07-19 00:00:00DENIED
  
 4. DATE AND COMPLETE ENERGY CALCS.
  
  
 10.SUBMIT TWO ORIGONAL SIGNED AND
 SEALED SURVEYS.FS 472.025
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE . A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-06-19 Cont ID  
Sent By alange Date 2006-06-19 Time 09:07 Rev Time 2.00
Received By alange Date 2006-06-19 Time 09:07 Sent To  
Notes
2006-06-19 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.BASED ON ICC BUILDING VALUATION DATA
 THE PERMIT VALUE HAS BEEN REVISED TO
 $71,670.00.ADDITIONAL PERMIT FEES ARE
 DUE.
  
 4. SIGN AND COMPLETE ENERGY CALCS.
  
 5.PRODUCT APPROVALS REQUIRED FOR
 IMPACT PROTECTION, STRAPS AND TIE-DOWNS
 AND LINTELS.
 PRODUCT APPROVALS SUBMITTED FOR GLAS
 BLOCK AND ACRILIC GLASS BLOCK WINDOWS
 YET NONE ARE SHOWN ON THE PLANS.
 PRODUCT APPROVALS ARE INCOMPLETE, SUBMIT
 TWO COMPLETE SETS OF PRODUCT APPROVALS
 WITH THE FOLLWOING STATE PRODUCT
 APPROVALS ATTACHED.
  
 6.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 7.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 8.SUBMIT TWO SETS OF TRUSS DRAWINGS
 FOR REVIEW PER 2004 FBC R-802.10.1
  
 9.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 10.SUBMIT TWO ORIGONAL SIGNED AND
 SEALED SURVEYS.FS 472.025
  
 NOTE; ONLY TWO SETS OF PLANS REQUIRED
 FOR REVIEW.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE . A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-07-15 Cont ID  
Sent By dpalmer Date 2006-07-15 Time 08:25 Rev Time 0.00
Received By dpalmer Date 2006-07-15 Time 08:09 Sent To B
Notes
2006-07-15 00:00:00******* PROVISO/ REVISION *********
  
 1) NOTE: PLEASE SEE THE SD'S IN THE
 EXISTING DWELLING INSIDE AND OUTSIDE ALL
 BEDRMS SHALL BE SHOWN ON A LAYOUT OF
 FLOOR PLAN SHOWING EITHER ALL NEW OR
 EXISTING MEETING THE CURRENT NFPA-72
 11.5.1.1. R-313
 PLANS MAY NOT QUOTE REQUIREMENTSIN
 LEIU OF SHOWING THE DETAILS.
  
 2) NOTE: PLEASE SEE GEN/LTS AND RECEPTS
 ARE STILL SHOWING VA'S OVER THE MAX
 PERMITTED. THIS WAS NOTED ON PREVIOUS
 REVIEW. PLEASE KNOW, MAX OF 1440VA IS
 PERMITTED. NOTE #4 PREVIOUS REVIEW.
  
 3) NOTE: PLEASE SEE ALL RECEPTS WITHIN
 6' OF WETBAR SINKS SHALL BE GFI/ GFI
 PROTECTED.
 210.8A7, PLEASE INDICATE THESE AS GFI.
  
 ** PLEASE KNOW, THE ABOVE SHALL BE
 REVISED SNA SUBMITTED ALONG WITH ANY
 OTHER REVISIONS BEFORE THE ROUGH
 ELECTRICAL INSPECTION IS CALLED IN.
 ** PLANS REVIEWED AND STAMPED BY THIS
 DEPT SHALL BE ON THE JOBSITE FOR
 INSPECTION.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-13 Cont ID  
Sent By dpalmer Date 2006-06-13 Time 20:58 Rev Time 0.00
Received By dpalmer Date 2006-06-13 Time 20:28 Sent To P
Notes
2006-06-13 00:00:00****** UNSAT *****
  
 1) NOTE: PLEASE SEE ZONING NOTES AS
 FRONT COVER SHEETS ARE COLORED
 PHOTO-COPIES OF OLDER SURVEYS FOR OTHER
 WORK.
  
 2) NOTE: PLEASE SEE FBC 2004 R 313 WHICH
 REQUIRES SD'S IN NEWAND EXISTING.
 PLEASE INDICATE EITHER EXISTING SD'S
 WHICH MEET CURRENT CODES IN EXISTING
 DWELLING AREAS, OR SHOW NEW SD'S.
 NFPA-72 11.5.1.1, 11.8.3.5
  
 3) NOTE: PLEASE SEE PANEL SCHEDULE SAHLL
 INDICATE THE CIRCUITS TO THE SPECIFIC
 NEW AREAS. 408.4
 IE; BATH RECEPT, LIV AREA LTS, ETC
  
 4) NOTE: PLEASE CLARIFYLT CIRCUIT, SA
 THE MAX VA ON A 15AMP CIRCUIT IS 1440
 VA, AND PANEL SCHEDULE SHOWS 2200
 PLEASE ADJUST.
  
 5) NOTE: PLEASE SEE MISSING FOOTER STEEL
 AS PART OF THE GROUNDING ELECTRODE
 SYSTEM. THIS IS NEW FOOTER STEEL.
 250.50
  
 6) NOTE: PLEASE CORRELATE RISER AND
 PLANS. PLEASE SEE RISER SHOWS A MAIN
 DISCONNECT, YET PLANS DO NOT INDICATE
 THIS?
 215.5
  
 7) NOTE: PLEASE SEE PANEL INSIDE DOES
 NOT MEET 110.26 FOR MIN CLEARENCES.
 PLEASE RELOCATE.
  
 8) NOTE: PLEASE VERIFY THE KW SHOWN FOR
 THE EXISTING RANGE AS 15KW EXCEEDS THE
 RATING OF THE 50A BRKR BY 12.5AMPS.
 PLEASE SEE 240.4,310.16,422.11
  
 9) NOTE: PLEASE SEE WASHER AND DRYER ARE
 BEING SHOWN BEING FED FROM EXISTING
 PANEL, HOWEVER THIS IS THE NEW PANEL?
 PLEASE PROVIDE A PANEL SCHEDULE FOR ALL
 AS IT SEEMS THE NEW PANEL BEING PROPOSED
 WILL FEED THE NEW AND EXISTING
 CIRCUITING.
 408.4,215.5
  
 10) NOTE: PLEASE SEE SOME NOTES ON LEFT
 WHICH DO NOT SEEM TO APPLY.
 PLEASE SEE NOTE WHICH MENTIONS ALL
 BRNACH CIRCUITS BRKRS SHALL HAVE SURGE
 PROTECTION?
 PLEASE SEE NOTE FOR LANDSCAPE LTS?
  
 11) NOTE: PLEASE SEE PLANS SHALL
 INDICATE THE FOLLOWING CURRENT CODES AT
 A MIN FOR ELECTRICAL REVIEW.
 FBC 2004, NFPA-72 2002, NFPA-70 2002
  
 12) NOTE: PLEASE SEE BUILDING REVIEW
 COMMENTS AS VALUE SHALL BE ADJUSTED PER
 FBC 2004 108.3 ADMINISTRATIVE SECTION AS
 ADOPTED BY THE CITY OF WEST PALM BEACH
  
 PLEASE SEE ANY COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-07-31 Cont ID  
Sent By adarroug Date 2006-07-31 Time 10:55 Rev Time 0.00
Received By adarroug Date 2006-07-31 Time 10:54 Sent To B
Notes
2006-07-31 00:00:00TO "ALANGE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-07-28 Cont ID  
Sent By adarroug Date 2006-07-28 Time 13:58 Rev Time 0.00
Received By adarroug Date 2006-07-28 Time 13:58 Sent To E
Notes
2006-07-28 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-07-14 Cont ID  
Sent By adarroug Date 2006-07-14 Time 18:24 Rev Time 0.00
Received By adarroug Date 2006-07-14 Time 18:24 Sent To E
Notes
2006-07-14 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-07-03 Cont ID  
Sent By adarroug Date 2006-07-03 Time 16:44 Rev Time 0.00
Received By adarroug Date 2006-07-03 Time 16:44 Sent To Z
Notes
2006-07-03 00:00:00SUBMITTAL TO "Z" BOX W/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-07-03 Cont ID  
Sent By adarroug Date 2006-07-03 Time 10:56 Rev Time 0.00
Received By adarroug Date 2006-07-03 Time 10:56 Sent To Z
Notes
2006-07-03 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-12 Cont ID  
Sent By adarroug Date 2006-06-12 Time 11:21 Rev Time 0.00
Received By adarroug Date 2006-06-12 Time 11:21 Sent To E
Notes
2006-06-12 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-19 Cont ID  
Sent By alange Date 2006-06-19 Time 09:08 Rev Time 0.00
Received By alange Date 2006-05-25 Time 10:22 Sent To  
Notes
2006-05-25 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-06-16 Cont ID  
Sent By tgordon Date 2006-06-16 Time 11:42 Rev Time 0.25
Received By tgordon Date 2006-06-16 Time 11:42 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-06-16 Cont ID  
Sent By jleech Date 2006-06-16 Time 07:38 Rev Time 0.00
Received By jleech Date 2006-06-16 Time 07:38 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2006-07-29 Cont ID  
Sent By mmclean Date 2006-07-29 Time 08:59 Rev Time 0.00
Received By mmclean Date 2006-07-29 Time 08:59 Sent To I
Notes
2006-07-29 00:00:00NOTE: THE PROPOSED ADDITION IS 6FT FROM
 THE EXISTING SHED.
  
 NOTE: THE 30" REF/FREEZER IS A U/C
 REF/FREEZER.
  

Review Stop Z ZONING
Rev No 2 Status F Date 2006-07-12 Cont ID  
Sent By mmclean Date 2006-07-12 Time 08:04 Rev Time 0.00
Received By mmclean Date 2006-07-12 Time 08:04 Sent To I
Notes
2006-07-12 00:00:00DENIED,
 1. NEED TO PROVIDE THE DISTANCE OF THE
 PROPOSED ADDITION FROM THE EXISTING
 SHED ON TWO COPY OF SURVEY/SITEPLAN.
  
 SEC 94/304(B)3 - BUILDING SEPERATION
  
 NOTE: THE 30"REF/FREEZER (MUST BE U/C
 REF.)
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2006-06-09 Cont ID  
Sent By mmclean Date 2006-06-09 Time 16:08 Rev Time 0.00
Received By mmclean Date 2006-06-09 Time 16:08 Sent To I
Notes
2006-06-14 00:00:006/14/06 *COLOR PHOTO COPY OF SURVEY WAS
 SUBMITTED FOR OTHER PROJECT THAT WAS
 APPROVED BY ZONING* NOT FOR THE CURRENT
 PROJECT.
2006-06-09 00:00:00DENIED,
 1. NEED TO PROVIDE TWO COPY OF CURRENT
 SURVEY SHOWING THE PROPOSED ADDITION
 WITH SETBACKS FROM PROPERTY LINE.
 2. MUST PROVIDE A COMPLETE FLOOR PLAN OF
 THE EXISTING STRUCTURE (IDENTIFY ALL
 ROOMS) AND THE INTERIOR ACCESS OF THE
 PROPOSED.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720