| Plan Review Stops For Permit 06050897 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2006-05-30 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-05-30 |
Time |
11:20 |
Rev Time |
0.75 |
| Received By |
btrobaug |
Date |
2006-05-30 |
Time |
11:20 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-05-24 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-05-24 |
Time |
16:16 |
Rev Time |
0.75 |
| Received By |
btrobaug |
Date |
2006-05-24 |
Time |
15:44 |
Sent To |
PC |
|
| Notes |
| 2006-05-24 00:00:00 | | | | | | | 1} OUR RECORDS INDICATE AN APARTMENT ON | | | THE PROPERTY. PLEASE SUBMIT LOAD | | | CALCULATIONS FOR THE RESIDENCE PER | | | 220.30 OR 220. PART II. | | | | | | 2} PER 110.9 AND 110.10: OBTAIN THE | | | AVAILABLE FAULT CURRENT AT THE UTILITY | | | AND CALCULATE THE SAME AT THE EQUIPMENT. | | | INDICATE THE AIC RATING FOR THE | | | EQUIPMENT IS EQUAL TO OR GREATER THAN | | | THE AVAILABLE FAULT. | | | | | | 3} THE PERSON TAKING RESPONSIBILITY FOR | | | THE DESIGN MUST PRINT AND SIGN THEIR | | | NAME TO SAME PER 106.3.4.2. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-05-24 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-05-24 |
Time |
15:44 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2006-05-24 |
Time |
14:17 |
Sent To |
E |
|
| Notes |
| 2006-05-24 00:00:00 | TO "E" BOX |
|
|
|