Plan Review Details - Permit 06050868
Plan Review Stops For Permit 06050868
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-01-24 Cont ID  
Sent By lmartine Date 2007-01-24 Time 14:49 Rev Time 0.00
Received By lmartine Date 2007-01-24 Time 14:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-10-26 Cont ID  
Sent By alange Date 2006-10-26 Time 09:09 Rev Time 0.00
Received By alange Date 2006-10-26 Time 09:09 Sent To P
Notes
2006-10-26 09:16:54DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE RE-RECORDED IF
 THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.BASED ON ICC BUILDING VALUATION DATA
 THE PERMIT VALUE HAS BEEN REVISED TO
 $29,373.ADDITIONAL PERMIT FEES ARE
 DUE.
  
 6.PGT 701 SHHAS THE INCORRECT STATE PRODUCT
 APPROVAL ATTACHED.STATE PRODUCT APPROVAL PAGE SHOULD
 SHOW MANUFACTURER, MODEL AND APPROVAL STATUS.
 ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 7.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
  
 10.R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A
 STORM SEWER CONVEYANCE OR OTHER APPROVED
 POINT OF COLLECTION SO AS TO NOT CREATE
 A HAZARD. LOTS SHALL BE GRADED SO AS TO
 DRAIN SURFACE WATER AWAY FROM FOUNDATION
 WALLS. THE GRADE AWAY FROM FOUNDATION
 WALLS SHALL FALL A MINIMUM OF 6 INCHES
 WITHIN THE FIRST 10 FEET.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-06-16 Cont ID  
Sent By alange Date 2006-06-16 Time 08:05 Rev Time 2.00
Received By alange Date 2006-06-16 Time 08:02 Sent To  
Notes
2006-06-16 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE RE-RECORDED IF
 THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.BASED ON ICC BUILDING VALUATION DATA
 THE PERMIT VALUE HAS BEEN REVISED TO
 $29,373.ADDITIONAL PERMIT FEES ARE
 DUE.
  
 4.COMPLETE ENERGY CALCS FORM AND SIGN OWNER/AGENT.
  
 5.PRODUCT APPROVALS REQUIRED FOR
 ROOFING, LINTELS, EXTERIOR DOORS,
 WINDOWS, IMPACT PROTECTION AND STRAPS
 AND TIE-DOWNS.
  
 6.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 7.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 8.SUBMIT TWO SETS OF TRUSS DRAWINGS
 FOR REVIEW PER 2004 FBC R-802.10.1
  
 9.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 10.R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A
 STORM SEWER CONVEYANCE OR OTHER APPROVED
 POINT OF COLLECTION SO AS TO NOT CREATE
 A HAZARD. LOTS SHALL BE GRADED SO AS TO
 DRAIN SURFACE WATER AWAY FROM FOUNDATION
 WALLS. THE GRADE AWAY FROM FOUNDATION
 WALLS SHALL FALL A MINIMUM OF 6 INCHES
 WITHIN THE FIRST 10 FEET.
  
 11.SHOW EMERGENCY ESCAPE AND RESCUE
 OPENINGS FOR EXISTING WINDOW IN BEDROOMS
 ADJACENT TO ROOM ADDITION.SH 24 IS TOO
 SMALL.R310
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-10-25 Cont ID  
Sent By btrobaug Date 2006-10-25 Time 07:13 Rev Time 0.50
Received By btrobaug Date 2006-10-25 Time 06:28 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-06-08 Cont ID  
Sent By btrobaug Date 2006-06-08 Time 14:54 Rev Time 0.50
Received By btrobaug Date 2006-06-08 Time 14:54 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-12-15 Cont ID  
Sent By adarroug Date 2006-12-15 Time 14:21 Rev Time 0.00
Received By adarroug Date 2006-12-15 Time 14:21 Sent To P
Notes
2006-12-15 14:21:43TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-10-24 Cont ID  
Sent By adarroug Date 2006-10-24 Time 17:07 Rev Time 0.00
Received By adarroug Date 2006-10-24 Time 17:07 Sent To E
Notes
2006-10-24 17:08:50TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-10-16 Cont ID  
Sent By adarroug Date 2006-10-16 Time 16:24 Rev Time 0.00
Received By adarroug Date 2006-10-16 Time 16:24 Sent To Z
Notes
2006-10-16 16:25:07TO "Z" BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-07 Cont ID  
Sent By adarroug Date 2006-06-07 Time 18:45 Rev Time 0.00
Received By adarroug Date 2006-06-07 Time 18:45 Sent To E
Notes
2006-06-07 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-16 Cont ID  
Sent By alange Date 2006-06-16 Time 08:11 Rev Time 0.00
Received By alange Date 2006-05-23 Time 16:08 Sent To  
Notes
2006-05-23 00:00:00TO "Z' BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-06-14 Cont ID  
Sent By tgordon Date 2006-06-14 Time 14:18 Rev Time 0.15
Received By tgordon Date 2006-06-14 Time 14:18 Sent To B
Notes
2006-06-14 00:00:00NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-01-04 Cont ID  
Sent By jleech Date 2007-01-04 Time 15:12 Rev Time 0.00
Received By jleech Date 2007-01-04 Time 15:12 Sent To B
Notes
2007-01-04 15:17:29HEALTH DEPARTMENT INSPECTED521 21 ST ST (INSP.REPORT
 WITH PLANS) SEPTIC TANK HAS BEEN ABANDONED YEARS AGO
 NEVER TAKEN OFF SURVEY.

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-10-26 Cont ID  
Sent By jleech Date 2006-10-26 Time 11:08 Rev Time 0.00
Received By jleech Date 2006-10-26 Time 11:08 Sent To  
Notes
2006-10-26 11:26:05DENIED;
 THE SURVEY ATACHED TO PLANS DATED 4/19/06 SHOWS A
 SEPTIC TANK IN THE BACKYARD. THIS TANK MUST BE
 ABANDONED.
 TANK MUST BE PUMPED, HOLES BROKEN IN THE BOTTOM OF THE
 TANK AND FILLED WITH DIRT. A PERMIT IS REQUIRED BY THE
 HEALTH DEPARTMENT
 AND HEALTH DEPT. WILL DO THE FINAL INSPECTION. A GEEN
 FORM FROM THE HEALTH DEPARTMENT, OR COPY MUST BE
 SUBMITED
 WHEN SUBMITTING PLANS FOR NEXT REVIEW.THE HEALTH
 DEPARTMENT PHONE # IS 355-3022.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-06-14 Cont ID  
Sent By jleech Date 2006-06-14 Time 09:14 Rev Time 0.00
Received By jleech Date 2006-06-14 Time 09:14 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2006-10-23 Cont ID  
Sent By mmclean Date 2006-10-23 Time 18:25 Rev Time 0.00
Received By mmclean Date 2006-10-23 Time 18:25 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2006-06-07 Cont ID  
Sent By mmclean Date 2006-06-07 Time 07:46 Rev Time 0.00
Received By mmclean Date 2006-06-07 Time 07:46 Sent To I
Notes
2006-06-07 00:00:00DENIED,
 1. MUST SHOW THE PROPOSED ADDITION ON
 THE TWO COPY OF CURRENT SURVEY WITH
 SETBACKS FROM PROPERTY LINE (SIDE &
 REAR)
 2. THE ENCLOSED SURVEY DOES NOT SHOW THE
 PROPOSED WORK.
 3. THE PROPOSED ADDITION MUST BE 6FT
 FROM THE EXISTING WOOD SHED IN REAR OF
 PROPERTY.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720