Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-05-31 Cont ID  
Sent By mperson Date 2006-05-31 Time 10:38 Rev Time 0.45
Received By mperson Date 2006-05-31 Time 10:38 Sent To PC
Notes
2006-05-31 00:00:00******DENIED******
 FEFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLAN REVIEW FOR A GAS PERMIT:
  
 1. ORIGANAL PLANS #04121374 ARE SIGNED
 AND SEALED BY AN ENGINEER. ANY REVISIONS
 TO THE ORIGINAL CONSTRUCTION DOCUMENTS
 BY L&R GAS CONTRACTORS, INC. NEED TO BE
 SIGNED AND SEALED BY THE ENGINEER OF
 RECORD.
 2. THE MAXITROL REGULATORS INDICATED FOR
 THE WATER HEATER AND THE GENERATOR ARE
 TO SMALL FOR THE INDIVIDUAL LOADS OF THE
 APPLIANCES, SEE ATTACHED MAXITROL SHEETS
 FOR REFERENCE FOR RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON