| 2006-05-19 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | ROOFING PERMIT; ONLY CHECKED ITEMS APPLY |
| | |
| | |
| | ____1.)A NOTICE OF COMMENCEMENT |
| | MUST BE FILED WITH THE CLERK OF COURTS |
| | BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | _XX_2.)CONTRACTOR IS TO PROVIDE THE |
| | MEAN ROOF HEIGHT ON THE APPLICATION. |
| | |
| | ____3.)CONTRACTOR IS TO PROVIDE THE |
| | ROOF PITCH ON THE APPLICATION. |
| | |
| | _XX_4.)CONTRACTOR IS TO PROVIDE THE |
| | ROOF DECK TYPE ON THE APPLICATION. |
| | |
| | _XX_5.)FLORIDA STATE OR LOCAL |
| | PRODUCT APPROVAL REQUIRED AS WELL AS AN |
| | EVALUATION REPORT SUBMITTED, FAC9B72. |
| | WWW.FLORIDABUILDING.ORG.NO PRODUCT |
| | APPROVAL FOR THE TILE WAS SUBMITTED. |
| | |
| | ____6.)FOR THE FLAT DECK, SELECT THE |
| | APPROVED ASSEMBLY YOU ARE USING. |
| | |
| | ____7.)THE SYSTEM PROVIDED HAS A LOW |
| | PRESSURE FOR ZONE ____. |
| | |
| | ____8.)THE SYSTEM PROVIDED STATES |
| | LIMITATION #9, ENHANCED FASTENING NOT |
| | ALLOWED. |
| | |
| | ____9.)PROVIDE AN ENGINEER?S LETTER |
| | TO CONFIRM THAT THE ROOF WHICH CURRENTLY |
| | HAS SHINGLES INSTALLED CAN ACCOMMODATE |
| | THE ADDITIONAL WEIGHT OF THE PROPOSED |
| | TILE. |
| | |
| | _XX_ 10.)ON THE TILE PRODUCT APPROVAL, |
| | INDICATE WHICH METHOD OF ATTACHMENT YOU |
| | ARE USING. |
| | |
| | _XX_ 11.)DECLARE AN EXPOSURE CATEGORY |
| | FBC1609.4.IT IS NOT CLEAR WHY YOU ARE |
| | SPECIFYING ENHANCED FASTENING, WHICH IS |
| | NOT ALLOWED TO INCREASE DESIGN PRESSURE |
| | LIMITATION, FOR THE FIELD. |