Plan Review Details - Permit 06050807
Plan Review Stops For Permit 06050807
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-06-19 Cont ID  
Sent By mperson Date 2006-06-19 Time 15:33 Rev Time 0.33
Received By mperson Date 2006-06-19 Time 15:33 Sent To PC
Notes
2006-06-19 00:00:00NOTE: PLEASE NOTIFY FLORIDA PUBLIC
 UTTILITIES OF GAS METER UPGRADE TO 2 PSI
 FROM 0.5 PSI.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-06-06 Cont ID  
Sent By mperson Date 2006-06-06 Time 16:00 Rev Time 0.45
Received By mperson Date 2006-06-06 Time 16:00 Sent To PC
Notes
2006-06-06 00:00:00******DENIED******
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING INFORMATION IS REQUESTED
 FOR GAS PLAN REVIEW:
  
 1. A GAS PERMIT CAN NOT BE ISSUED UNTIL
 A GEN/RES PERMIT APPLICATION HAS BEEN
 APPLIED FOR AND APPROVED BY ZONING FOR
 THE GENERATOR LOCATION.(NOTE: ZONING
 FAILED 6/1/06 SEE ATTACHED SHEET FOR
 REFERENCE)
 2. NOTE: MORE INFORMATION REQUIRED,
 HOUSE HAS EXISTING GAS, PLEASE INDICATE
 THE FOLLOWING INFORMATION ON THE
 RESUBMITTED DRAWING. SEE ATTACHED SHEET
 FOR REFERENCE INDICATING EXISTING GAS
 PIPING.
 3. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.(NOTE: INDICATE EXISTING
 PIPE AND NEW PIPE TO GENERATOR ON
 RESUBMITTED DRAWINGS)
 4. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 (NOTE: INDICATE THE ABOVE INFORMATION TO
 EXISTING PIPING AND TO PROPOSED PIPING
 TO GENREATOR ON RESUBMITTED DRAWINGS)
 5. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).(NOTE: EXISTING GAS PIPE IS
 PART OF SYSTEM PLEASE INCLUDE TOTAL BTU
 LOAD OF SYSTEM ON RESUBMITTED DRAWINGS)
 6. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).(NOTE:
 EXISTING GAS PIPE IS PART OF SYSTEM,
 LONGEST LENGTH METHOD OF SYSTEM TO BE
 USED FOR SIZING PLEASE INDICATE THE
 ABOVE INFORMATION ON THE RESUBMITTED
 DRAWINGS)
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-12 Cont ID  
Sent By adarroug Date 2006-06-12 Time 14:13 Rev Time 0.00
Received By adarroug Date 2006-06-12 Time 14:13 Sent To G
Notes
2006-06-12 00:00:00TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-06 Cont ID  
Sent By mperson Date 2006-06-06 Time 16:32 Rev Time 0.00
Received By mperson Date 2006-05-23 Time 09:54 Sent To  
Notes
2006-05-23 00:00:00TO "G" BOX