Plan Review Details - Permit 06050794
Plan Review Stops For Permit 06050794
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-06-01 Cont ID  
Sent By jwitmer Date 2006-06-01 Time 08:35 Rev Time 2.22
Received By jwitmer Date 2006-06-01 Time 08:35 Sent To  
Notes
2006-07-02 00:00:00PROVISO:
 PLEASE SEE COMMENTS FROM OTHER PLAN
 REVIEWERS.
2006-06-01 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06050794
 ADD: 930 SOUTHERN BLVD.
 CONT: SEIRRAES CONST
 TEL: (561)848-6607
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) COVER SHEET CODE REVIEW CODE DATA:
 PLANS INDICATE TYPE OF CONSTRUCTION
 AS TYPEIV WHICH IS HEAVY CONSTRUCTION,
 UNPROTECTED ,SPRINKLERED PLEASE SEE
 TABLE 503 HEADINGS A OR B FOR THE AMOUNT
 OF FIRE RESISTANCE RATING.
  
 4) PROVIDE INFORMATION AS TO DESCRIPTION
 OF WORK, SEE 2004 EXISTING BUILDING CODE
 LEVEL 1, LEVEL 2 OR LEVEL 3. PROVIDE IN
 CODE REVIEW SUMMARY, SEE 2004 EXISTING
 BUILDING SECTION 303, 304 & 305.CHANGE
 OF OCCUPANCY.
  
 5) ADDITIONAL INFORMATION REQUIRED,
 CODE REVIEW COMMENT INDICATES DAY CARE
 SQ FT WAS 3260 AND INCREASED TO 6014 SQ
 FT. SHEET A.1 INDICATES NEW ROOMS TO BE
 MEETING ROOMS, ARE THESE ROOMS TO BE
 OCCUPIED BY THE DAY CARE OCCUPANCY?
  
 6)1033.6 SPECIAL MEANS OF EGRESS
 FEATURES.
 EVERY ROOM OR SPACE NORMALLY SUBJECT TO
 CLIENT OCCUPANCY, OTHER THAN BATHROOMS,
 SHALL HAVE AT LEAST ONE OUTSIDE WINDOW
 FOR EMERGENCY RESCUE AND VENTILATION.
 SUCH WINDOW SHALL BE OPENABLE FROM THE
 INSIDE WITHOUT THE USE OF TOOLS AND
 SHALL PROVIDE A CLEAR OPENING OF NOT
 LESS THAN 20 INCHES (508 MM) WIDTH, 24
 INCHES (610 MM) IN HEIGHT, AND 5.7
 SQUARE FEET (0.53 M 2 ) IN AREA. THE
 BOTTOM OF THE OPENING SHALL BE NOT MORE
 THAN 44 INCHES (1118 MM) ABOVE THE
 FLOOR. THE CLEAR OPENING SHALL PERMIT A
 RECTANGULAR SOLID, WITH A MINIMUM WIDTH
 AND HEIGHT THAT PROVIDES THE REQUIRED
 5.7 SQUARE FOOT (0.53 M 2 ) OPENING AND
 A MINIMUM DEPTH OF 20 INCHES (8 MM), TO
 PASS FULLY THROUGH THE OPENING.
 EXCEPTIONS:
 1.IN BUILDINGS PROTECTED THROUGHOUT
 BY AN APPROVED, AUTOMATIC SPRINKLER
 SYSTEM.
 2.WHERE THE ROOM OR SPACE HAS A
 DOOR LEADING DIRECTLY TO THE OUTSIDE OF
 THE BUILDING.
  
 7)PROVIDE OCCUPANT LOAD IN EACH OF THE
 MEETING ROOMS. IT APPEARS THAT WHEN THE
 ACCORDIAN DOORS AND OR THE POCKET DOORS
 ARE CLOSED PLANS DO NOT MEET COMPLIANCE
 WITH:
 1033.2.1
 EVERY ROOM OR SPACE WITH AN OCCUPANT
 LOAD OF MORE THAN 50 PERSONS OR AN AREA
 OF MORE THAN 1,000 SQUARE FEET (93 M 2 )
 SHALL HAVE AT LEAST TWO EXIT ACCESS
 DOORWAYS AS REMOTELY LOCATED FROM EACH
 OTHER AS PRACTICABLE. SUCH DOORWAYS
 SHALL PROVIDE ACCESS TO SEPARATE EXITS,
 BUT WHERE EGRESS IS THROUGH CORRIDORS,
 THEY SHALL BE PERMITTED TO OPEN ONTO A
 COMMON CORRIDOR LEADING TO SEPARATE
 EXITS LOCATED IN OPPOSITE DIRECTIONS.
  
 8)SHEET A.1 DOESN'T INDICATE ANY WALL
 RATING ALONG THE EXIT ACCESS CORRIDOR AT
 THE DAY CARE AREA.SEE TABLE 1016.1 DAY
 CARE, OCUPANT LOAD > 30 AND WITH OUT
 FIRE SPRINKLER.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-10 Cont ID  
Sent By dpalmer Date 2006-06-10 Time 16:33 Rev Time 0.00
Received By dpalmer Date 2006-06-10 Time 15:54 Sent To  
Notes
2006-06-10 00:00:00** UNSAT **
  
 1) NOTE: PLEASE SEE NOTES FROM BUILDING
 REVIEW WHICH MAY REQUIRE SOME DESIGN
 CHNAGES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 2) NOTE: PLEASE SEE THAT THE PLANS SHALL
 INDICATE THE WIND LOAD CALCULAITONS FOR
 THE NEW LT POLE BEING RELOCATED.
 PLEASE SEE THIS MUST MEET THE 140 MPH
 UNDER THE 2004 FBC. THE STRUCTURAL CALCS
 WILL BE REVIEWED BY THE BUILDING
 REVIEWER.
  
 3) NOTE: PLEASE SEE PLANS SEEM STO
 INDICATE THE CIRCUITING FOR EXSITING LTS
 TO A PANEL "A" WHICH IS NOT SHOWN,
 HOWEVER THE SOME RECEPTS ARE ALSO SHOWN
 CIRCUITED TO THE SAME "A" PANEL. THE
 QUESTION ARRISES AS THE FIXTURE SCHEDULE
 SHOWS THE NEW EXT LTS AS 277V?
 PLEASE CLARIFY AS THE LTS AND RECEPTS
 ARE CIRCUITED TO THE SAME PANEL.?
 ** PLEASE ALSO INCLUDE THE NEW FIXTURE
 TYPE/BRAND ETC FOR THE NEW EM LTS SHOWN
 ON PLANS.
  
 4) NOTE: PLEASE GIVE A BREAK DOWN AND
 LABEL EACH ROOM ARE DESIGNATION.
 PLEASE SEE PANEL SCHEDULE SHALL INDICATE
 THE ROOM IN WHICH THE CIRCUITS ARE
 SHOWN.
 408.4.
 PLEASE KNOW THE PANEL SCHEDULE ON SITE
 SHOULD BE LABELED FOR EACH ROOM AND OR
 AREA WHICH IS FED.
  
 5) NOTE: PLEASE SEE A BATTERY BACK UP
 FIXTURE OF SOME TYPE WILL BE REQUIRED
 FOR THE NEW EGREE RAMP. LS 101 7.8 ,7.9
 LIGHTING SHALL BE PROVIDED TO THE PUBLIC
 RIGHT OF WAY.
 THIS IS REQUIRED FOR NEW AND EXISTING
 DAY CARE OCCUPANCIES.
  
 PLEASE BE SURE TO COMPLETELY REMOVE ANY
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO SETS FOR REVIEW AND
 STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-06-16 Cont ID  
Sent By mcarsill Date 2006-06-16 Time 13:54 Rev Time 0.00
Received By mcarsill Date 2006-06-16 Time 13:27 Sent To  
Notes
2006-06-16 00:00:001. ALL CONSTRUCTION. DEMOLTION, AND
 RENOVATION TO COMPLY WITH NFPA 241.
  
 2. DEMOLTION WORK SHALL NOT INTERFERE
 WITH ANY REQUIRED EXITS SINCE IT IS THE
 INTENT TO HAVE PORTIONS REMAIN OCCUPIED.
  
 3. DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY.
  
 4. A REQUIRED FIRE WATCH IS REQUIRED
 WHEN ANY REQUIRED FIRE SYSTEM IS DOWN
 FOR MORE THAN FOUR HOURS. ALL FIRE
 WATCHES MUST BE APPROVED BY THE CHIEF
 FIRE PREVENTION OFFICER OR THE ASSISTANT
 FIRE MARSHAL.
  
 5. SEPERATE PLANS AND PERMITS REQUIRED
 FOR THE RELOCATION OF FIRE SPRINKLER
 HEADS.
  
 6. PLEASE INDICATE PRESCRIPTIVE STRENGTH
 REQUIREMENTS FOR HANDRAILS AND
 GUARDRAILS.
  
 7. NEW FIRE DAMPERS AFTER INSTALLATION
 SHALL BE TESTED TO ENSURE PROPER
 OPERATION.
  
 8. PLEASE PROVIDE OCCUPANT LOADS FOR
 EACH ROOM IN THE SELECTIVE AREA OF
 DEMOLITION OR RENOVATION.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-20 Cont ID  
Sent By pkrauss Date 2006-07-20 Time 06:52 Rev Time 0.00
Received By pkrauss Date 2006-05-22 Time 14:52 Sent To  
Notes
2006-06-06 00:00:00TO "COMM" BD#50
2006-05-22 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-07-19 Cont ID  
Sent By pkrauss Date 2006-07-19 Time 14:30 Rev Time 0.00
Received By pkrauss Date 2006-07-19 Time 09:26 Sent To  
Notes
2006-07-19 00:00:00DENIED:2004 FBC
 1.PLAN SHEET M-1, PLEASE VERIFY
 PENETRATION AT RATED PARTITION BETWEEN
 ACTIVITY ROOM 113 AND THE EXISTING
 EXECUTIVE DIRECTOR OFFICE 115.
  
 2.PLEASE PROVIDE A COMPLETED FORM
 400C-04 CLIMATE ZONE 7, 8, & 9.
  
 3.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS IN ACCORDANCE WITH 2004 FMC
 TABLE 403.3
  
 4.PLEASE PROVIDE EXISTING EQUIPMENT
 INFORMAIION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-07-02 Cont ID  
Sent By pschmitz Date 2006-07-02 Time 06:55 Rev Time 0.00
Received By pschmitz Date 2006-07-02 Time 06:52 Sent To  
Notes
2006-07-02 00:00:00PROVISO:
 SHT D-1ROOM #113 DEMO PLBG TO BE RE
 CONNECTED TO EXISTING PIPING.
 COOKING FACILITIES, EXISTING KITCHEN.
 PLEASE SEE COMMENTS FROM OTHER PLAN
 REVIEWERS.