Plan Review Details - Permit 06050698
Plan Review Stops For Permit 06050698
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-06-12 Cont ID  
Sent By rnuquist Date 2006-06-12 Time 19:06 Rev Time 0.00
Received By rnuquist Date 2006-06-12 Time 19:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By btrobaug Date 2007-03-19 Time 13:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-06-13 Cont ID  
Sent By btrobaug Date 2006-06-13 Time 15:52 Rev Time 0.33
Received By btrobaug Date 2006-06-13 Time 15:48 Sent To P
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2007-03-19 Cont ID  
Sent By mperson Date 2007-03-19 Time 09:40 Rev Time 0.55
Received By mperson Date 2007-03-19 Time 09:40 Sent To E
Notes
2007-03-19 09:49:38NOTE: HOMEOWNER SUBMITTED NOTARIZED LETTER VOIDING GAS
 PERMIT #06090649, BUT IN ORDER TO VOID PERMIT 4/TIMES
 THE FEE NEEDS TO BE PAID BECAUSE OF WORK BEING DONE
 WITHOUT A PERMIT. NEW GAS CONTRACTOR "BEACON APPLIANCE
 SERVICE" PERMIT #07030562 IS AWARE OF THIS. I HAVE
 TRIED TO CONTACT THE HOMEOWNER BY PHONE, LEFT MESSAGE
 ON ANSWER MACHINE.

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2007-01-11 Cont ID  
Sent By mperson Date 2007-01-11 Time 09:37 Rev Time 1.25
Received By mperson Date 2007-01-11 Time 09:37 Sent To PC
Notes
2007-01-11 10:44:12DENIED 2ND TIME
 REFERENCE: FBC-2004 FUEL GAS, FBC-2004 CHAPTER 1, AND
 FLORIDA ADMINISTRATIVE CODE
  
 THE FOLLOWING CORRECTIONS ARE STILL REQUIRED FOR GAS
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PERMIT CAN NOT BE ISSUED WITH OUT A PERMIT
 APPLICATION. THERE WAS NOT A PERMIT APPLICATION WITH
 THIS RESUBMITTAL.
  
 2. NOTE: PER FLORIDA ADMINISTRATIVE CODE 61G15-23.002,
 A CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS REQUIRED IN THE TITLE BLOCK.
  
 3. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: THE RESUBMITTED DRAWING IS NOT AN ISOMETRIC AND
 DOES NOT CLEARLY SHOW ALL CUT SECTIONS OF PIPE WITH
 CORRESPONDING LENGTHS. PLEASE CORRECT AND RESUBMIT.
  
 4. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 NOTE: THE RESUBMITTED DRAWING DOES NOT INDICATE ALL
 PIPING MATERIAL BEING INSTALLED OR ALL PIPE SIZES.
 PLEASE CORRECT AND RESUBMIT.
  
 5. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 NOTE: NOT ALL APPLIANCE BTU LOADS OR WHAT THE APPLIANCE
 IS ARE CLEARLY INDICATED ON THE RESUBMITTED DRAWING.
 PLEASE CORRECT AND RESUBMIT.
  
 6. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 NOTE: THE RESUBMITTED DRAWINGS INDICATE A DELIVERY
 PRESSURE OF 0.5 TO 2.0 PSI. THIS IS WRONG. ON THE
 RESUBMITTAL ONLY ONE DELIVERY PRESSURE NEEDS TO BE
 INDICATED. DELIVERY PRESSURE IS EITHER GOING TO BE 0.5
 PSI OR IT IS GOING TO BE 2.0 PSI. PLEASE CORRECT AND
 RESUBMIT.
  
 8. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 NOTE: MANUFACTURER CUT SHEETS OF GENERATOR AND IF GAS
 DELIVERY PRESSURE IS 2 PSI MANUFACTURER CUT SHEETS OF
 MP REGULATORS ARE NEEDED ON THE RESUBMITTAL.
  
 9. SHUT OFF VALVE AND REGULATOR IS MISSNG ON THE
 FIREPLACE.
  
 10. PER FBC-2004 CHAPTER 1, SECTION 106: ON THE
 RESUBMITTAL PLEASE SUBMIT DRAWINGS VOID OF HAND WRITTEN
 RED LINES UNLESS INITIALED AND DATED BY ENGINEER OF
 RECORD.
  
 *********IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK HIGH LIGHTED YELLOW FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2006-10-20 Cont ID  
Sent By mperson Date 2006-10-20 Time 09:44 Rev Time 0.45
Received By mperson Date 2006-10-20 Time 09:44 Sent To PC
Notes
2006-10-20 10:30:08UNSAT
 GAS PERMIT #06090649
 REFERENCE: FBC-2004 FUEL GAS AND FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS REQUIRED FOR GAS PLAN
 REVIEW:
  
 1. THERE WAS NOT A MASTER PERMIT APPLICATION SUBMITTED
 WITH THIS RESUBMITTAL
  
 2. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 3. CLEARLY INDICATE ON THE DRAWING ALL EXISTING PIPING
 AND NEW PIPING.
  
 4. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT
 (2LB REGULATORS) TO VERIFY COMPLIANCE WITH STANDARDS
 NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
  
 6. PLEASE NOTE THAT THE REGULATORS INDICATED ON THE
 DRAWING ARE 21LB REG, THIS IS INDICATED WRONG THE
 REGULATORS SHOULD BE INDICATED AS 2LB REG. PLEASE
 CORRECT FOR RESUBMITTAL.
  
 7. PLEASE CLARIFY WHAT THE PIPING BY THE FIREPLACE
 SLEEVE IS FOR AND THE BTU LOAD.
  
 8. PLEASE NOTE THAT THE REGULATOR INDICATED FOR THE
 DRYER AND WATER HEATER IS INDICATED IN THE WRONG
 LOCATION, PLEASE REFERENCE THE CORRECTED LOCATION IN
 RED INK FOR RESUBMITTAL.
  
 9. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-06-14 Cont ID  
Sent By mperson Date 2006-06-14 Time 16:06 Rev Time 0.15
Received By mperson Date 2006-06-14 Time 16:06 Sent To M
Notes
2006-06-14 00:00:00NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL GEN/RES INSPECTION.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-10-02 Cont ID  
Sent By adarroug Date 2006-10-02 Time 12:02 Rev Time 0.00
Received By adarroug Date 2006-10-02 Time 12:02 Sent To E
Notes
2006-10-02 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-09-29 Cont ID  
Sent By adarroug Date 2006-09-29 Time 09:20 Rev Time 0.00
Received By adarroug Date 2006-09-29 Time 09:20 Sent To Z
Notes
2006-09-29 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-02 Cont ID  
Sent By adarroug Date 2006-06-02 Time 08:25 Rev Time 0.00
Received By adarroug Date 2006-06-02 Time 08:25 Sent To E
Notes
2006-06-02 00:00:00TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By mmclean Date 2006-06-01 Time 10:36 Rev Time 0.00
Received By adarroug Date 2006-05-19 Time 11:40 Sent To  
Notes
2006-05-19 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-06-19 Cont ID  
Sent By tgordon Date 2006-06-19 Time 11:39 Rev Time 0.10
Received By tgordon Date 2006-06-19 Time 11:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-06-14 Cont ID  
Sent By mperson Date 2006-06-14 Time 16:06 Rev Time 0.00
Received By mperson Date 2006-06-14 Time 16:06 Sent To G
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2006-09-29 Cont ID  
Sent By mmclean Date 2006-09-29 Time 18:20 Rev Time 0.00
Received By mmclean Date 2006-09-29 Time 18:20 Sent To I
Notes
2006-09-29 00:00:00NOTE:THE PROPOSED GENERATOR SHALL NOT BE
 CLOSER THAN 8FT FROM SIDE PROPERTY LINE.
 9/29/06 NO PERMIT APPLICATION WAS RE-SUB
 WITH PACKAGE. CONTRACTOR WAS MADE AWARE
 BY DEWEY PALMER (PERMIT APPLICATION WAS
 MISPLACED BY THE CONTRACTOR)
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2006-06-01 Cont ID  
Sent By mmclean Date 2006-06-01 Time 10:28 Rev Time 0.00
Received By mmclean Date 2006-06-01 Time 10:28 Sent To I
Notes
2006-06-01 00:00:00DENIED,
 1. NEED TO KNOW IF THE GENERATOR IS 5'6"
 FROM REAR & SIDE SETBACK?EXPLAIN.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720