| 2007-01-11 10:44:12 | DENIED 2ND TIME |
| | REFERENCE: FBC-2004 FUEL GAS, FBC-2004 CHAPTER 1, AND |
| | FLORIDA ADMINISTRATIVE CODE |
| | |
| | THE FOLLOWING CORRECTIONS ARE STILL REQUIRED FOR GAS |
| | PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. PERMIT CAN NOT BE ISSUED WITH OUT A PERMIT |
| | APPLICATION. THERE WAS NOT A PERMIT APPLICATION WITH |
| | THIS RESUBMITTAL. |
| | |
| | 2. NOTE: PER FLORIDA ADMINISTRATIVE CODE 61G15-23.002, |
| | A CERTIFICATE OF AUTHORIZATION NUMBER OF THE |
| | ENGINEERING BUSINESS REQUIRED IN THE TITLE BLOCK. |
| | |
| | 3. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | NOTE: THE RESUBMITTED DRAWING IS NOT AN ISOMETRIC AND |
| | DOES NOT CLEARLY SHOW ALL CUT SECTIONS OF PIPE WITH |
| | CORRESPONDING LENGTHS. PLEASE CORRECT AND RESUBMIT. |
| | |
| | 4. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | NOTE: THE RESUBMITTED DRAWING DOES NOT INDICATE ALL |
| | PIPING MATERIAL BEING INSTALLED OR ALL PIPE SIZES. |
| | PLEASE CORRECT AND RESUBMIT. |
| | |
| | 5. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | NOTE: NOT ALL APPLIANCE BTU LOADS OR WHAT THE APPLIANCE |
| | IS ARE CLEARLY INDICATED ON THE RESUBMITTED DRAWING. |
| | PLEASE CORRECT AND RESUBMIT. |
| | |
| | 6. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | |
| | 7. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | NOTE: THE RESUBMITTED DRAWINGS INDICATE A DELIVERY |
| | PRESSURE OF 0.5 TO 2.0 PSI. THIS IS WRONG. ON THE |
| | RESUBMITTAL ONLY ONE DELIVERY PRESSURE NEEDS TO BE |
| | INDICATED. DELIVERY PRESSURE IS EITHER GOING TO BE 0.5 |
| | PSI OR IT IS GOING TO BE 2.0 PSI. PLEASE CORRECT AND |
| | RESUBMIT. |
| | |
| | 8. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | NOTE: MANUFACTURER CUT SHEETS OF GENERATOR AND IF GAS |
| | DELIVERY PRESSURE IS 2 PSI MANUFACTURER CUT SHEETS OF |
| | MP REGULATORS ARE NEEDED ON THE RESUBMITTAL. |
| | |
| | 9. SHUT OFF VALVE AND REGULATOR IS MISSNG ON THE |
| | FIREPLACE. |
| | |
| | 10. PER FBC-2004 CHAPTER 1, SECTION 106: ON THE |
| | RESUBMITTAL PLEASE SUBMIT DRAWINGS VOID OF HAND WRITTEN |
| | RED LINES UNLESS INITIALED AND DATED BY ENGINEER OF |
| | RECORD. |
| | |
| | *********IMPORTANT INFORMATION |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK HIGH LIGHTED YELLOW FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |