| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-05-16 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-05-16 |
Time |
15:31 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-05-16 |
Time |
15:31 |
Sent To |
|
|
| Notes |
| 2006-05-16 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 | | | EXISTING BUILDING CODE | | | FBC*CITY OF WEST PALM BEACH | | | AMENDMENTS TO THE FBC2004 | | | | | | 1.)THE PRODUCT SUBMITTED HAS A DESIGN | | | PRESSURE LIMITATION OF -36.SEE FBC | | | TABLE 1609.6B, 140MPH.THIS PRODUCT | | | DOES NOT MEET THE DESIGN PRESSURE | | | REQUIREMENTS FOR ZONES 2 AND 3.I WAS | | | UNABLE TO FIND IN THE PRODUCT APPROVAL | | | ENHANCED FASTENING FOR THE PERIMETER AND | | | CORNER ZONES. |
|
|
|