| 2006-05-23 00:00:00 | ******DENIED****** |
| | REFERENCE: FBC-2004 PLUMBING |
| | |
| | THE FOLLOWING INFORMATION IS REQUIRED |
| | FOR PLUMBING PLAN REVIEW FOR A PERMIT: |
| | |
| | 1. ON SHEET 2 OF 2 THE WATER RISER |
| | DIAGRAM INDICATES A FUTURE SINK, PLEASE |
| | INDICATE THIS FUTURE SINK ON THE |
| | SANITARY PLBG. RISER DIAGRAM AND ON THE |
| | FLOOR PLAN AND ADHERE TO THE FOLLOWING |
| | CODE REQUIREMENTS FOR FUTURE FIXTURES |
| | (A) 704.4 FUTURE FIXTURES. DRAINAGE |
| | PIPING FOR FUTURE FIXTURES SHALL |
| | TERMINATE WITH AN APPROVED CAP OR PLUG. |
| | (B) 905.6 VENT FOR FUTURE FIXTURES. |
| | WHERE THE DRAINAGE PIPING HAS BEEN |
| | ROUGHED-IN FOR FUTURE FIXTURES, A |
| | ROUGH-IN CONNECTION FOR A VENT SHALL BE |
| | INSTALLED. THE VENT SIZE SHALL BE NOT |
| | LESS THAN ONE-HALF THE DIAMETER OF THE |
| | ROUGH-IN DRAIN TO BE SERVED. THE VENT |
| | ROUGH-IN SHALL CONNECT TO THE VENT |
| | SYSTEM, OR SHALL BE VENTED BY OTHER |
| | MEANS AS PROVIDED FOR IN THIS CHAPTER. |
| | THE CONNECTION SHALL BE IDENTIFIED TO |
| | INDICATE THAT IT IS A VENT. |
| | (C) 710.2 FUTURE FIXTURES. WHERE |
| | PROVISION IS MADE FOR FUTURE |
| | INSTALLATION OF FIXTURES, THOSE PROVIDED |
| | FOR SHALL BE CONSIDERED IN DETERMINING |
| | THE REQUIRED SIZES OF DRAIN PIPES. |
| | 2. ON SHEET 1 OF 2 FLOOR PLAN DRAWING |
| | PLEASE INDICATE THE WASHING MACHINE |
| | LOCATION AND SEE CORRECTED SANITARY |
| | PLBG. RISER DIAGRAM FOR REFERENCE FOR |
| | THE FOLLOWING CORRECTIONS FOR |
| | RESUBMITTAL. |
| | (A) 406.3 WASTE CONNECTIONS.THE TRAP AND |
| | FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES |
| | WASHER SHALL BE A MINIMUM OF 2 INCHES |
| | (51MM) IN DIAMETER. THE AUTOMATIC |
| | CLOTHES WASHER FIXTURE DRAIN SHALL |
| | CONNECT TO A BRANCH DRAIN OR DRAINAGE |
| | STACK A MINIMUM OF 3 INCHES (76MM) IN |
| | DIAMETER. |
| | (B) 802.4 STANDPIPES.STANDPIPES SHALL BE |
| | INDIVIDUALLY TRAPPED. STANDPIPES SHALL |
| | EXTEND A MINIMUM OF 18 INCHES (457MM) |
| | AND A MAXIMUM OF 42 INCHES (1066MM) |
| | ABOVE THE TRAP WEIR. ACCESS SHALL BE |
| | PROVIDED TO ALL STANDPIPES AND DRAINS |
| | FOR RODDING. NOTE: PLEASE INDICATE |
| | STANDPIPE ON RESUBMITTED DRAWING. |
| | |
| | (C) 708.9 ACCESS. ACCESS SHALL BE |
| | PROVIDED TO ALL CLEANOUTS. NOTE: SEE |
| | CORRECTED SHEET 1 OF 2 FOR REFERENCE OF |
| | WASHING MACHINE CLEANOUT LOCATION FOR |
| | RESUBMITTAL |
| | 3. PER 905.3 VENT CONNECTIONS TO |
| | DRAINAGE SYSTEMS. EVERY DRY VENT |
| | CONNECTING TO A HORIZONTAL DRAIN SHALL |
| | CONNECT ABOVE THE CENTERLINE OF THE |
| | HORIZONTAL DRAIN PIPE. NOTE: THE TUB AND |
| | SHOWER IN THE MASTER BATH ARE DRY |
| | VENTED, PLEASE SEE CORRECTED DRAWING ON |
| | SHEET 1 OF 2 FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | 4. PLEASE SEE CORRECTED WATER RISER |
| | DIAGRAM ON SHEET 2 OF 2 FOR REFERENCE |
| | FOR THR WATER- HAMMER ARRESTORS. |
| | (A) 604.9 WATER HAMMER. A WATER-HAMMER |
| | ARRESTOR SHALL BE INSTALLED WHERE |
| | QUICK-CLOSING VALVES ARE UTILIZED. |
| | 5. PLEASE ADD THE DISHWASHER TO THE |
| | SANITARY ISOMETRIC RISER DIAGRAM, SEE |
| | SHEET 1 OF 2 FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |