Plan Review Details - Permit 06050671
Plan Review Stops For Permit 06050671
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-02-20 Cont ID  
Sent By rnuquist Date 2007-02-20 Time 19:00 Rev Time 0.00
Received By rnuquist Date 2007-02-20 Time 19:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-06-12 Cont ID  
Sent By mmclean Date 2006-06-12 Time 07:12 Rev Time 0.00
Received By rnuquist Date 2006-06-12 Time 19:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-06-29 Cont ID  
Sent By btrobaug Date 2006-06-29 Time 09:24 Rev Time 1.00
Received By btrobaug Date 2006-06-29 Time 08:49 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-13 Cont ID  
Sent By btrobaug Date 2006-06-13 Time 15:32 Rev Time 0.50
Received By btrobaug Date 2006-06-13 Time 15:14 Sent To P
Notes
2006-06-13 00:00:00 
 PLEASE PROVIDE PLANS PER ATTACHED
 RESIDENTIAL GENERATOR REQUIREMENTS.
  
 PLEASE SEE 225.31 THROUGH 225.39,
 230.72, ARTICLE 445 AND 702.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 CONSTRUCTION SERVICES DEPARTMENT
 561) 805-6718
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-06-14 Cont ID  
Sent By mperson Date 2006-06-14 Time 15:56 Rev Time 0.15
Received By mperson Date 2006-06-14 Time 15:56 Sent To M
Notes
2006-06-14 00:00:00NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL GEN/RES INSPECTION.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-06-26 Cont ID  
Sent By adarroug Date 2006-06-26 Time 15:21 Rev Time 0.00
Received By adarroug Date 2006-06-26 Time 15:21 Sent To E
Notes
2006-06-26 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-02 Cont ID  
Sent By adarroug Date 2006-06-02 Time 12:08 Rev Time 0.00
Received By adarroug Date 2006-06-02 Time 12:08 Sent To E
Notes
2006-06-02 00:00:00TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-19 Cont ID  
Sent By tgordon Date 2006-06-19 Time 11:29 Rev Time 0.00
Received By tgordon Date 2006-05-19 Time 11:41 Sent To  
Notes
2006-05-19 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-06-19 Cont ID  
Sent By tgordon Date 2006-06-19 Time 11:04 Rev Time 0.15
Received By tgordon Date 2006-06-19 Time 11:04 Sent To  
Notes
2006-06-19 00:00:00*** PROVISO ***
 PER 2004 FBC, FUEL GAS - POWERED
 EQUIPMENT - PERMANENTLY INSTALLED
 EQUIPMENT POWERED BY INTERNAL COMBUSTION
 ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AND NFPA 37.
  
 NFPA 37 INSTALLATION & USE OF STATIONARY
 COMBUSTION ENGINES & GAS TURBINES:
 4.1.4ENGINES (GENERATORS) LOCATED
 OUTDOORS SHALL BE MINIMUM OF 5 FT FROM
 OPENINGS IN WALLS & AT LEAST 5 FT FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS.A
 MINIMUM CLEARANCE IS NOT REQUIRED WHEN
 (1) THE ADJACENT WALL HAS A MINIMUM FIRE
 RESISTANCE RATING OF 1 HOUR OR (2) THE
 WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF
 NON-COMBUSTIBLE MATERIALS, AND IT HAS
 BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE.
 A.8.2.3.1EXHAUST SYSTEMS SHOULD NOT
 TERMINATE UNDER STRUCTURES OR WHERE THE
 EXHAUST MIGHT BE DRAWN INTO THE
 VENTILATION INTAKES.
  
 2004 FMC 804.3.5 #3, WHERE THE
 TERMINATION IS LOCATED BELOW AN ADJACENT
 ROOF STRUCTURE, THE TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE
 ROOF STRUCTURE.
  
 PLEASE NOTE, WHILE ZONING ALLOWS
 MECHANICAL EQUIPMENT TO ENCROACH 4 FT
 INTO THE SETBACK, GENERATORS SHALL
 MAINTAIN THE REQUIRED ABOVE MENTIONED
 CLEARANCES TO THE ADJACENT PROPERTY
 STRUCTURES, I.E. FENCE, BUILDING,
 WINDOWS, DOORS, OR OPENINGS.
  
 PROVIDE MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AT THE JOBSITE FOR THE
 FIELD INSPECTOR.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-06-14 Cont ID  
Sent By mperson Date 2006-06-14 Time 15:55 Rev Time 0.00
Received By mperson Date 2006-06-14 Time 15:55 Sent To G
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2006-06-12 Cont ID  
Sent By mmclean Date 2006-06-06 Time 07:06 Rev Time 0.00
Received By mmclean Date 2006-06-06 Time 07:05 Sent To B
Notes
2006-06-12 00:00:00GENERATOR CAN ONLY PROJECT 4FT INTO A
 SETBACK. GENERATOR WILL BE 1FT FROM SIDE
 PROPERTY LINE.
  
 6/12/06 PLAN LOCATED WITHIN RYAN N,
 PLANNING INSPECTOR.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2006-06-01 Cont ID  
Sent By mmclean Date 2006-06-01 Time 10:02 Rev Time 0.00
Received By mmclean Date 2006-06-01 Time 10:02 Sent To I
Notes
2006-06-01 00:00:00DENIED,
 1. MUST SHOW THE PROPOSED GENERATOR ON
 THE TWO COPY OF GENERATOR WITH SETBACKS
 FROM THE PROPERTY LINE
 2. GENERATOR CANNOT BE LOCATED IN THE
 4.2 UTILITY EASEMENT IN THE REAR OF
 PROPERTY.
  
 NOTE: GENERATOR CAN ONLY ENCROACH 4FT
 INTO REQUIRED SETBACK.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720