| 2006-05-23 00:00:00 | ******DENIED****** |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | |
| | THE FOLLOWING INFORMATION IS REQUIRED |
| | FOR PLUMBING PLAN REVIEW FOR A PERMIT: |
| | |
| | 1. PER FBC-2004 CHAPTER 1, THE FOLLWING |
| | IS REQUIRED ON THE ISOMETRIC PLUMBING |
| | RISER DIAGRAM. |
| | (A) 106.3.5.4 RESIDENTIAL (ONE AND TWO |
| | FAMILY) SUBMIT A PLUMBING SANITARY |
| | ISOMETRIC RISER DIAGRAM INDICATING ALL |
| | WASTE, VENTS, TRAPS WITH SIZES, AND |
| | CLEANOUT LOCATIONS. NOTE: THE DOUBLE |
| | BOWL KITCHEN SINK WITH DISHWASHER IN |
| | ROOM #105 NEEDS TO BE INDICATED AND ONLY |
| | ONE LAV IS INDICATED FOR ROOM #203 THERE |
| | ARE TWO THAT NEED TO BE INDICATED. |
| | PLEASE SEE CORRECTED DRAWING ON SHEET |
| | P-1 FOR RESUBMITTAL REFERENCE FOR THE |
| | ABOVE OTHER REQUIREMENTS. |
| | 2. PER FBC-2004 PLUMBING, THE FOLLOWING |
| | IS REQUIRED ON THE ISOMETRIC PLUMBING |
| | RISER DIAGRAM PRETAINING TO THE WASHING |
| | MACHINES IN ROOM #106 |
| | (A) 802.4 STANDPIPES.STANDPIPES SHALL BE |
| | INDIVIDUALLY TRAPPED. STANDPIPES SHALL |
| | EXTEND A MINIMUM OF 18 INCHES (457MM) |
| | AND A MAXIMUM OF 42 INCHES (1066MM) |
| | ABOVE THE TRAP WEIR. ACCESS SHALL BE |
| | PROVIDED TO ALL STANDPIPES AND DRAINS |
| | FOR RODDING. PLEASE INDICATE STANDPIPES |
| | ON DRAWING FOR RESUBMITTAL. |
| | (B) THE WASHING MACHINE IS NOT VENTED |
| | PER, 908.3 CONNECTIONS AT DIFFERENT |
| | LEVELS. WHERE THE FIXTURE DRAINS CONNECT |
| | AT DIFFERENT LEVELS, THE VENT SHALL |
| | CONNECT AS A VERTICAL EXTENTION OF THE |
| | VERTICAL DRAIN. THE UPPER FIXTURE SHALL |
| | NOT BE A WATER CLOSET. PLEASE SEE |
| | CORRECTED DRAWING ON SHEET P-1 FOR |
| | RESUBMITTAL REFERENCE. |
| | 3. PER FBC-2004 PLUMBING, THE FOLLOWING |
| | CORRECTIONS ARE REQUIRED FOR ROOM #107. |
| | (A) THE SHOWER IS NOT VENTED PER 902.2.1 |
| | (B) THE HORIZONTAL DRY VENT INDICATED |
| | FOR THE WATER CLOSET IS NOT ALLOWED PER |
| | 905.3 |
| | 4. PER FBC-2004 PLUMBING, THE FOLLOWING |
| | CORRECTIONS ARE REQUIRED FOR ROOM #205. |
| | (A) SHOWER INDICATES A "S" TRAP, "S" |
| | TRAPS PROHIBITED PER 1002.3 |
| | (B) THE HORIZONTAL DRY VENT INDICATED ON |
| | THE TUB NOT ALLOWED PER 905.3 |
| | 5. PER FBC-2004 PLUMBING, SECTION 916.2 |
| | VENTS OTHER THAN STACK VENTS OR VENT |
| | STACKS. VENTS EXCEEDING 40 FEET(12192MM) |
| | IN DEVELOPED LENGTH SHALL BE INCREASED |
| | BY ONE NOMINAL PIPE SIZE FOR THE ENTIRE |
| | DEVELOPED LENGTH OF THE VENT PIPE. NOTE: |
| | PLEASE REFERENCE CORRECTED PLBG. ISO. |
| | RISER DIAGRAM ON SHEET P-1 FOR |
| | RESUBMITTAL. |
| | 6. PLEASE NOTE THE CLEANOUT LOCATIONS ON |
| | THE CORRECTED PLBG. ISO. RISER DIAGRAM |
| | FOR REFERENCE FOR RESUBMITTAL. |
| | (A) 708.3.4 BASE OF STACK. A CLEANOUT |
| | SHALL BE PROVIDED AT THE BASE OF EACH |
| | WASTE OR SOIL STACK |
| | (B) 708.3.5 BUILDING DRAIN AND BUILDING |
| | SEWER JUNCTION. THERE SHALL BE A |
| | CLEANOUT NEAR THE JUNCTION OF THE |
| | BUILDING DRAIN AND THE BUILDING SEWER. |
| | (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL |
| | BE THE SAME NOMINAL SIZE AS THE PIPE |
| | THEY SERVE UP TO 4 INCHES (102MM) |
| | (D) 708.9 ACCESS. ACCESS SHALL BE |
| | PROVIDED TO ALL CLEANOUTS. |
| | 7. ON SHEET A-2 IN THE BOXES 03 AND 04 |
| | THE SCALE INDICATED 1"=1'-0" IS WRONG, |
| | IT SHOULD BE 1/4"=1'-0" PLEASE CORRECT |
| | FOR RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |