Plan Review Details - Permit 06050665
Plan Review Stops For Permit 06050665
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-31 Cont ID  
Sent By alange Date 2006-05-31 Time 09:38 Rev Time 2.00
Received By alange Date 2006-05-31 Time 09:31 Sent To  
Notes
2006-05-31 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.SUBMIT TWO COPIES OF ENERGY CALCS
 PER 2004 FBC AND SIGN OWNER/AGENT.
  
 3.PRODUCT APPROVALS REQUIRED FOR
 EXTERIOR DOORS WINDOWS, IMPACT
 PROTECTION AND STRAPS AND TIE-DOWNS.
  
 4.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 5.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 6.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 7.ALL PLANS SUBMITTED AFTER OCTOBER,
 1, 2005 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE.
  
 8.SHOW GAURD RAIL DETAILS ON BALCONY
 COMPLYING WITH FBC R312.1 AND R312.2
  
 9.SHOW SIZE AND LOCATION OF ATTIC
 ACCESS.R807.1
  
 10.PERMIT APPLICATIONS SCOPE OF WORK
 SHOULD REFLECT THE WORK ON PLANS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-05-22 Cont ID  
Sent By btrobaug Date 2006-05-22 Time 08:31 Rev Time 1.00
Received By btrobaug Date 2006-05-22 Time 07:05 Sent To P
Notes
2006-05-22 00:00:00NONCOMPLIANT
 ~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE ENGINEER OF RECORD SHALL INDICATE
 THE CERTIFICATE OF AUTHORIZATIONNUMBER
 ALONG WITH OTHER INFORMATION REQUIRED BY
 61G15-23.002FLORIDA ADMINISTRATIVE
 CODE.
  
 2} 210.52(C)(1) WALL COUNTER SPACES. A
 RECEPTACLE OUTLET SHALL BE INSTALLED AT
 EACH WALL COUNTER SPACE THAT IS 300 MM
 (12 IN.) OR WIDER. RECEPTACLE OUTLETS
 SHALL BE INSTALLED SO THAT NO POINT
 ALONG THE WALL LINE IS MORE THAN 600 MM
 (24 IN.) MEASURED HORIZONTALLY FROM A
 RECEPTACLE OUTLET IN THAT SPACE. SEE
 KITCHEN , ELECTRICAL PLAN, REVIEWED SET.
  
 3) 210.52 DWELLING UNIT RECEPTACLE
 OUTLETS.
 (A)(1) SPACING. RECEPTACLES SHALL BE
 INSTALLED SO THAT NO POINT MEASURED
 HORIZONTALLY ALONG THE FLOOR LINE IN ANY
 WALL SPACE IS MORE THAN 1.8 M (6 FT)
 FROM A RECEPTACLE OUTLET.
 (A)(2)(1)ANY SPACE 600 MM (2 FT) OR MORE
 IN WIDTH (INCLUDING SPACE MEASURED
 AROUND CORNERS) AND UNBROKEN ALONG THE
 FLOOR LINE BY DOORWAYS, FIREPLACES, AND
 SIMILAR OPENINGS. SEE LIVING ROOM, AND
 BOTH BEDROOMS UPSTAIRS.
  
 4} A SMOKE DETECTOR IS REQUIRED IN THE
 HALL AT THE STAIRS ON THE SECOND FLOOR,
 PER R313.1, 2&3.
  
 5} PLEASE INDICATE THE INTENT OF THE TWO
 RECEPTACLES LOCATED OFF THE WALL IN THE
 MASTER BEDROOM. ARE THESE IN THE CEILING
 POSSIBLY, OR LOCATEED AS FLOOR BOXES OFF
 THE WALL?
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-31 Cont ID  
Sent By alange Date 2006-05-31 Time 09:39 Rev Time 0.00
Received By alange Date 2006-05-19 Time 11:23 Sent To  
Notes
2006-05-19 00:00:00TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-05-24 Cont ID  
Sent By tgordon Date 2006-05-24 Time 13:59 Rev Time 0.45
Received By tgordon Date 2006-05-24 Time 13:59 Sent To B
Notes
2006-05-24 00:00:00*** DENIED ***
 1) PLEASE SHOW LISTING OF EXISTING A/C
 EQUIPMENT ON MECHHANICAL PLAN.
  
 2) SHOW SIZE OF MAIN SUPPLY AIR DUCT
 RUNNING ALONG FAMILY ROOM WALL.
  
 3) SHOW IF AHU #1 IS IN A CLOSET OR
 ATTIC.
  
 4) SHOW CLOTHES DRYER VENT TERMINATION,
 PER 2004 FBC/M 501.2 .
  
 5) SUBMIT MANUAL "D" CALCULATIONS FOR
 RESIDENTIAL DUCT DESIGN, PER 2004 FBC/R
 M1601 .
  
 6) PLEASE PROVIDE RETURN AIR FOR
 BEDROOMS, PER 2004 FBC/R M1602.4, OR
 PROVIDE FBC THAT EXEMPTS THIS HOME.
  
 7) PLEASE EXPLAIN WHAT "VS" MEANS AT
 SUPPLY AIR GRILLS IN FAMILY ROOM AND
 LIVING ROOM.
  
 8) PLEASE NOTE THAT THE ARCHITECT'S SEAL
 IS MISSING FROM MECHANICAL PLANS, PLEASE
 COMPLY WITH FS 61G1-16.003 .
  
 9)ENERGY CALCULATIONS NEED TO BE ON FORM
 600A-04 (2004) PER FBC 13-600.3.A .
  
 10) PLEASE HAVE ENERGY CAL'S. SIGNED BY
 OWNER/AGENT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-05-23 Cont ID  
Sent By mperson Date 2006-05-23 Time 10:05 Rev Time 2.00
Received By mperson Date 2006-05-23 Time 10:05 Sent To M
Notes
2006-05-23 00:00:00******DENIED******
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLUMBING PLAN REVIEW FOR A PERMIT:
  
 1. PER FBC-2004 CHAPTER 1, THE FOLLWING
 IS REQUIRED ON THE ISOMETRIC PLUMBING
 RISER DIAGRAM.
 (A) 106.3.5.4 RESIDENTIAL (ONE AND TWO
 FAMILY) SUBMIT A PLUMBING SANITARY
 ISOMETRIC RISER DIAGRAM INDICATING ALL
 WASTE, VENTS, TRAPS WITH SIZES, AND
 CLEANOUT LOCATIONS. NOTE: THE DOUBLE
 BOWL KITCHEN SINK WITH DISHWASHER IN
 ROOM #105 NEEDS TO BE INDICATED AND ONLY
 ONE LAV IS INDICATED FOR ROOM #203 THERE
 ARE TWO THAT NEED TO BE INDICATED.
 PLEASE SEE CORRECTED DRAWING ON SHEET
 P-1 FOR RESUBMITTAL REFERENCE FOR THE
 ABOVE OTHER REQUIREMENTS.
 2. PER FBC-2004 PLUMBING, THE FOLLOWING
 IS REQUIRED ON THE ISOMETRIC PLUMBING
 RISER DIAGRAM PRETAINING TO THE WASHING
 MACHINES IN ROOM #106
 (A) 802.4 STANDPIPES.STANDPIPES SHALL BE
 INDIVIDUALLY TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING. PLEASE INDICATE STANDPIPES
 ON DRAWING FOR RESUBMITTAL.
 (B) THE WASHING MACHINE IS NOT VENTED
 PER, 908.3 CONNECTIONS AT DIFFERENT
 LEVELS. WHERE THE FIXTURE DRAINS CONNECT
 AT DIFFERENT LEVELS, THE VENT SHALL
 CONNECT AS A VERTICAL EXTENTION OF THE
 VERTICAL DRAIN. THE UPPER FIXTURE SHALL
 NOT BE A WATER CLOSET. PLEASE SEE
 CORRECTED DRAWING ON SHEET P-1 FOR
 RESUBMITTAL REFERENCE.
 3. PER FBC-2004 PLUMBING, THE FOLLOWING
 CORRECTIONS ARE REQUIRED FOR ROOM #107.
 (A) THE SHOWER IS NOT VENTED PER 902.2.1
 (B) THE HORIZONTAL DRY VENT INDICATED
 FOR THE WATER CLOSET IS NOT ALLOWED PER
 905.3
 4. PER FBC-2004 PLUMBING, THE FOLLOWING
 CORRECTIONS ARE REQUIRED FOR ROOM #205.
 (A) SHOWER INDICATES A "S" TRAP, "S"
 TRAPS PROHIBITED PER 1002.3
 (B) THE HORIZONTAL DRY VENT INDICATED ON
 THE TUB NOT ALLOWED PER 905.3
 5. PER FBC-2004 PLUMBING, SECTION 916.2
 VENTS OTHER THAN STACK VENTS OR VENT
 STACKS. VENTS EXCEEDING 40 FEET(12192MM)
 IN DEVELOPED LENGTH SHALL BE INCREASED
 BY ONE NOMINAL PIPE SIZE FOR THE ENTIRE
 DEVELOPED LENGTH OF THE VENT PIPE. NOTE:
 PLEASE REFERENCE CORRECTED PLBG. ISO.
 RISER DIAGRAM ON SHEET P-1 FOR
 RESUBMITTAL.
 6. PLEASE NOTE THE CLEANOUT LOCATIONS ON
 THE CORRECTED PLBG. ISO. RISER DIAGRAM
 FOR REFERENCE FOR RESUBMITTAL.
 (A) 708.3.4 BASE OF STACK. A CLEANOUT
 SHALL BE PROVIDED AT THE BASE OF EACH
 WASTE OR SOIL STACK
 (B) 708.3.5 BUILDING DRAIN AND BUILDING
 SEWER JUNCTION. THERE SHALL BE A
 CLEANOUT NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER.
 (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM)
 (D) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 7. ON SHEET A-2 IN THE BOXES 03 AND 04
 THE SCALE INDICATED 1"=1'-0" IS WRONG,
 IT SHOULD BE 1/4"=1'-0" PLEASE CORRECT
 FOR RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  