Plan Review Details - Permit 06050642
Plan Review Stops For Permit 06050642
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-05-30 Cont ID  
Sent By lursu Date 2006-05-30 Time 09:29 Rev Time 0.00
Received By lursu Date 2006-05-30 Time 09:28 Sent To  
Notes
2006-05-30 00:00:00THRU THE MONTHLY UPDATES OWNER INFO WILL
 BE CAHNGED IN THE LAND FILE.ON THE
 EPRMIT OWNER MATCHES PAPA INFO.
2006-05-25 00:00:00PLEASE CHG OWNER INFO SO THAT APPL
 MATCHES PROPERTY FILES (PAPERWORK IN
 PERMIT PKG)

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-08-11 Cont ID  
Sent By alange Date 2006-08-11 Time 13:34 Rev Time 0.00
Received By alange Date 2006-08-11 Time 13:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-08-10 Cont ID  
Sent By alange Date 2006-08-10 Time 10:18 Rev Time 0.00
Received By alange Date 2006-08-10 Time 10:18 Sent To  
Notes
2006-08-10 00:00:00BUILDING REVIEW OK, NEED HISTORIC
 APPROVAL AND FINAL STAMPING

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-07-12 Cont ID  
Sent By alange Date 2006-07-12 Time 10:19 Rev Time 2.00
Received By alange Date 2006-07-12 Time 09:55 Sent To  
Notes
2006-07-12 00:00:00DENIED
  
  
 1.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 2.BASED ON ICC BUILDING VALUATION DATA
 THE PERMIT VALUE HAS BEEN REVISED TO
 $136,648.ADDITIONAL PERMIT FEES ARE
 DUE " PRIOR TO RESUBMITTING ".
  
 3. SIGN OWNER/AGENT ON ENERGY CALCS.
  
 4. GAF SHINGLES HAS WRONG STATE PRODUCT
 APPROVAL ATTACHED.
 CASTCRETE MISSING NOA
 JELD-WEN DOOR MISSING SATATE PRODUCT
 APPROVAL
 KINCO MISSING STATE PRODUCT APPROVAL.
  
 5.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 6.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 7.SUBMIT TWO SETS OF TRUSS DRAWINGS
 FOR REVIEW PER 2004 FBC R-802.10.1
  
 8.BEDROOM EMERGENCY ESCAPE RESCUE
 OPENING SIZES SHALL COMPLY WITH
 R310.1.1, R310.1.2 AND R310.1.3.SH24
 DOES NOT MEET THE REQUIREMENTS OF THIS
 SECTION.
  
 11.R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A
 STORM SEWER CONVEYANCE OR OTHER APPROVED
 POINT OF COLLECTION SO AS TO NOT CREATE
 A HAZARD. LOTS SHALL BE GRADED SO AS TO
 DRAIN SURFACE WATER AWAY FROM FOUNDATION
 WALLS. THE GRADE AWAY FROM FOUNDATION
 WALLS SHALL FALL A MINIMUM OF 6 INCHES
 WITHIN THE FIRST 10 FEET.SHOW DETAIL
 ON PLANS.
  
 NEW COMMENT:
 A.SHOW FOOTING DEPTH COMPLYING WITH
 R403.1.4
  
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-06-06 Cont ID  
Sent By alange Date 2006-06-06 Time 09:22 Rev Time 2.50
Received By alange Date 2006-06-06 Time 09:22 Sent To  
Notes
2006-06-06 00:00:00DENIED
  
  
 1.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 2.BASED ON ICC BUILDING VALUATION DATA
 THE PERMIT VALUE HAS BEEN REVISED TO
 $136,648.ADDITIONAL PERMIT FEES ARE
 DUE.
  
 3. SIGN OWNER/AGENT ON ENERGY CALCS.
  
 4.PRODUCT APPROVALS REQUIRED FOR
 STRAPS AND TIEDOWNS, ROOFING AND
 LINTELS.
  
 5.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 6.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 7.SUBMIT TWO SETS OF TRUSS DRAWINGS
 FOR REVIEW PER 2004 FBC R-802.10.1
  
 8.BEDROOM EMERGENCY ESCAPE RESCUE
 OPENING SIZES SHALL COMPLY WITH
 R310.1.1, R310.1.2 AND R310.1.3.SH24
 DOES NOT MEET THE REQUIREMENTS OF THIS
 SECTION.
  
 9.ROOF SHEATHING SHALL COMPLY WITH FBC
 2304.9.1 #31
  
 10.SHOW SIZE AND LOCATION OF ATTIC
 ACCESS COMPLYING WITH FBC R807.1
  
 11.R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A
 STORM SEWER CONVEYANCE OR OTHER APPROVED
 POINT OF COLLECTION SO AS TO NOT CREATE
 A HAZARD. LOTS SHALL BE GRADED SO AS TO
 DRAIN SURFACE WATER AWAY FROM FOUNDATION
 WALLS. THE GRADE AWAY FROM FOUNDATION
 WALLS SHALL FALL A MINIMUM OF 6 INCHES
 WITHIN THE FIRST 10 FEET.SHOW DETAIL
 ON PLANS.
  
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-08-07 Cont ID  
Sent By btrobaug Date 2006-08-08 Time 15:16 Rev Time 0.50
Received By btrobaug Date 2006-08-07 Time 15:34 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-06-30 Cont ID  
Sent By btrobaug Date 2006-06-30 Time 07:39 Rev Time 0.50
Received By btrobaug Date 2006-06-30 Time 06:52 Sent To P
Notes
2006-06-30 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE RANGE OCP IS INCORRECT. CIRCUIT
 9,11. 310.16
  
 2) THE AHU IS INCORRECT PER 310.16
  
 3) THE PERSON TAKING RESPONSIBILITY FOR
 THE DESIGN MUST PRINT AND SIGN THEIR
 NAME TO SAME PER 106.3.4.2.
  
 4) THE SERVICE AND FEEDER CONDUCTORS ARE
 INCORRECT PER 310.15(B)(6). MINIMUM OF
 2/0 CU FOR A 200 AMP SERVICE.
  
 5) THE RISER DIAGRAM INDICATES A METER
 WITH A SEPARATE DISCONNECT. THE PLAN
 SHOWS A METER/MAIN COMBINATION. PLEASE
 CORRELATE.
  
 PLEASE CORRECT THE COVER SHEET REGARDING
 THE INDEX SHEET. THE ELECTRICAL PLAN IS
 ON 7.1.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-01 Cont ID  
Sent By btrobaug Date 2006-06-01 Time 11:31 Rev Time 0.50
Received By btrobaug Date 2006-06-01 Time 07:28 Sent To P
Notes
2006-06-01 00:00:00 
 NONCOMPLIANT
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 2} LOCATE THE SERVICE DISCONNECT ON THE
 PLAN.
  
 3} INDICATE COMPLIANCE WITH ARTICLE
 250.50 FOR THE GROUNDING ELECTRODE
 SYSTEM. ALL AVAILABLE MUST BE USED ON
 THE RISER. SIZE GEC PER 250.66.
  
 4} NOTE #1 INCORRECTLY REFERENCES THE
 2005 NEC. WE ARE CURRENTLY USING THE
 2002 NEC AS ADOPTED 553.73 FS.
  
 5} THE 80 AMP OCP WITH #6 CONDUCTOR,
 CIRCUITS #1,3-2,4 IS IN VIOLATION OF
 310.16.
  
 6} THE BATH FANS AND RECEPTACLES ON ONE
 CIRCUIT , TWO BATHS, ARE IN VIOLATION OF
 210.11(C)(3). SHOW ON SCHEDULE.
  
 7} THE RANGE OCP IS INCORRECT. CIRCUIT
 9,11.
  
 8} THE MICROWAVE SHOWN ON THE PLAN IS
 NOT ON THE SCHEDULE AND THEREFORE NOT IN
 THE CALCULATION. ADD SAME.
  
 8} 210.52(E) OUTDOOR OUTLETS. FOR A
 ONE-FAMILY DWELLING AND EACH UNIT OF A
 TWO-FAMILY DWELLING THAT IS AT GRADE
 LEVEL, AT LEAST ONE RECEPTACLE OUTLET
 ACCESSIBLE AT GRADE LEVEL AND NOT MORE
 THAN 2.0 M (61/2 FT) ABOVE GRADE SHALL
 BE INSTALLED AT THE FRONT AND BACK OF
 THE DWELLING. SEE 210.8(A)(3).
  
 9} THE PERSON TAKING RESPONSIBILITY FOR
 THE DESIGN MUST PRINT AND SIGN THEIR
 NAME TO SAME PER 106.3.4.2.
  
 PLEASE CORRECT THE COVER SHEET REGARDING
 THE INDEX SHEET. THE ELECTRICAL PLAN IS
 ON 7.1.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-08-03 Cont ID  
Sent By adarroug Date 2006-08-03 Time 09:45 Rev Time 0.00
Received By adarroug Date 2006-08-03 Time 09:45 Sent To E
Notes
2006-08-03 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-07-27 Cont ID  
Sent By adarroug Date 2006-07-27 Time 09:51 Rev Time 0.00
Received By adarroug Date 2006-07-27 Time 09:51 Sent To Z
Notes
2006-07-27 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-06-29 Cont ID  
Sent By adarroug Date 2006-06-29 Time 11:52 Rev Time 0.00
Received By adarroug Date 2006-06-29 Time 11:52 Sent To E
Notes
2006-06-29 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-21 Cont ID  
Sent By adarroug Date 2006-06-21 Time 16:29 Rev Time 0.00
Received By adarroug Date 2006-06-21 Time 16:29 Sent To Z
Notes
2006-06-21 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-06 Cont ID  
Sent By adarroug Date 2006-06-06 Time 16:29 Rev Time 0.00
Received By rbrown Date 2006-05-27 Time 15:11 Sent To  
Notes
2006-05-27 00:00:00TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 4 Status N Date 2006-08-11 Cont ID  
Sent By tgordon Date 2006-08-11 Time 10:56 Rev Time 0.10
Received By tgordon Date 2006-08-11 Time 10:56 Sent To  
Notes
2006-08-11 00:00:00NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.
  
 MECHANICAL PERMIT # 06050649 HAD BEEN
 VOIDED BY CONTRACTOR.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2006-08-08 Cont ID  
Sent By tgordon Date 2006-08-08 Time 09:45 Rev Time 0.30
Received By tgordon Date 2006-08-08 Time 09:45 Sent To B
Notes
2006-08-08 00:00:00*** DENIED ***
 1) PLEASE SUBMIT MANUAL D CALCULATIONS
 FOR RESIDENTIAL DUCT DESIGN, PER 2004
 FBC/R M1601.1 AND FBC 13-610.1.ABC.1 .
  
 2) MAKE NEEDED CORRECTIONS TO DUCT SIZES
 ON MECHANICAL PLANS, AS MANUAL D
 CALCULATIONS MAY REQUIRE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-07-10 Cont ID  
Sent By tgordon Date 2006-07-10 Time 14:51 Rev Time 0.45
Received By tgordon Date 2006-07-10 Time 14:51 Sent To B
Notes
2006-07-10 00:00:00*** DENIED ***
 1) AS REQUESTED IN LAST REVIEW 6-1-06
 NOTE #7, PLEASE SHOW CFM'S AT EACH
 SUPPLY AIR GRILL.
  
 2) SEE SUBMITTED MANUAL J CALCULATIONS
 "CFM'S PER ROOM", MOST SUPPLY AIR DUCTS
 TO ROOMS ARE OVER SIZED, PLEASE CORRECT.
  
 3) ONLY ONE ENERGY CALCULATION WAS
 SIGNED, PLEASE SIGN OTHER COPY.
  
 4) PLEASE SHOW SIZE OF RETURN AIR DUCT
 TO 24X14 RETURN AIR GRILL IN HALLWAY.
  
 5) PLEASE SEE ATTACHED MANUAL 'D' COVER
 AND RECOMMENED VELOCITY.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-06-01 Cont ID  
Sent By tgordon Date 2006-06-01 Time 17:54 Rev Time 0.56
Received By tgordon Date 2006-06-01 Time 17:06 Sent To P
Notes
2006-06-01 00:00:00*** DENIED ***
 1) NEED A/C EQUIPMENT LISTING ON
 MECHANICAL PLANS.
  
 2) PLANS SHOW NO RETURN AIR DUCTS OR
 GRILL SIZES TO BEDROOMS, PLEASE CORRECT.
  
 3) PLEASE SHOW DUCT LAY-OUT AS A RIDGED
 RECTANGULAR TRUNK LINE WITH FLEX DROPS,
 OR AS A ALL FLEX WITH MIXING BOXES
 (SPIDER LAY-OUT) AND SHOW CORRECT DUCT
 SIZES.
  
 4) SHOW CLOTHES DRYER VENT LOCATION ON
 MECH. PLANS.
  
 5) SHOW CONDENSATE DRAIN LINE LOCATION
 ON MECH. PLANS.
  
 6) HAVE ENERGY CALCULATIONS SIGNED BY
 OWNER/AGENT.
  
 7) SHOW CFM'S AT EACH SUPPLY AIR GRILL.
  
 8) SUBMIT MANUAL 'D' CALCULATIONS FOR
 RESIDENTIAL DUCT DESIGN, PER2004 BBC/R
 M1601.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-07-08 Cont ID  
Sent By jleech Date 2006-07-08 Time 09:32 Rev Time 0.00
Received By jleech Date 2006-07-08 Time 09:32 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-06-02 Cont ID  
Sent By jleech Date 2006-06-02 Time 09:54 Rev Time 0.00
Received By jleech Date 2006-06-02 Time 09:54 Sent To B
Notes
2006-06-02 00:00:00DENIED;
 1. AUTOMATIC CLOTHES WASHWER DISCHARGE
 PIPE REQUIRED TO BE 3" FBC-2004 PLUMBING
 SEC.406.3 AND MUST DISCHARGE DOWN STREAM
 OF A BATHROOM GROUP SEC. 909.1.
 2.RISER DIAGRAM VENT SYSTEM NOT CORRECT,
 1/2 THE VENTS ARE NOT REQUIRED. ( SEE
 ONE SET OF PLANS MARKED IN RED)
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 3 Status P Date 2006-08-02 Cont ID  
Sent By mmclean Date 2006-08-02 Time 07:43 Rev Time 0.00
Received By mmclean Date 2006-08-02 Time 07:43 Sent To I
Notes
2006-08-02 00:00:00PROVISO: THE PROPOSED WALKWAY GOING TO
 THE NORTH SHALL BE REDUCE TO 30" WIDE
  
 NOTE:MUST MAINTAIN 1000SQ FT OR 75% OF
 LANDSCAPE, WHICHEVER IS LESS WITHIN THE
 FIRST 25FT FRONT SETBACK.
  
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2006-06-28 Cont ID  
Sent By mmclean Date 2006-06-28 Time 14:43 Rev Time 0.00
Received By mmclean Date 2006-06-28 Time 14:43 Sent To I
Notes
2006-06-28 00:00:00DENIED,
 1. THE PROPOSED DRIVEWAY 14FT WIDE WILL
 EXCEED THE REQUIREMENTS FOR LANDSCAPE
 WITHIN THE FIRST 25FT FRONT SETBACK.
 2. NEED TO REDUCE THE PROPOSED DRIVEWAY
 TO 10FT WIDE TO MEET THE REQUIREMENT
 WITH THE PROPOSED WALKWAY.PLEASE SHOW
 CHANGES ON THE TWO COPY OF SURVEY (SIDE
 PLAN DOES NOT GIVE THE DIMENSION OF THE
 LOT.
  
  
 NOTE: MUST MAINTIAN 1000SQ FT OR 75%
 WHICHEVER IS LESS OF LANDSCAPE WITHIN
 THE FIRST 25FT FRONT SETBACK.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2006-05-31 Cont ID  
Sent By mmclean Date 2006-05-31 Time 11:01 Rev Time 0.00
Received By mmclean Date 2006-05-31 Time 11:01 Sent To E
Notes
2006-05-31 00:00:00DENIED,
 1. MUST PROVIDE THE DIMENSION OF THE
 PROPOSED DRIVEWAY & WALKWAY (LENGTH &
 WIDTH).
  
  
 NOTE:
 1. MUST MAINTAIN 1000SQ FT OR 75% OF
 LANDSCAPE, WHICHEVER IS LESS WITHIN THE
 FIRST 25FT FRONT SETBACK.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720