| Plan Review Stops For Permit 06050632 |
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-05-18 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-05-18 |
Time |
10:33 |
Rev Time |
0.00 |
| Received By |
tgordon |
Date |
2006-05-17 |
Time |
14:26 |
Sent To |
|
|
| Notes |
| 2006-05-17 00:00:00 | TO "M" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2006-05-18 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-05-18 |
Time |
10:13 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2006-05-18 |
Time |
10:13 |
Sent To |
|
|
| Notes |
| 2006-05-18 00:00:00 | *** PORVISO *** | | | 1) AS PER 2004 FBC(M) 602.2.1, MATERIALS | | | EXPOSED WITHIN PLENUMS SHALL BE NON - | | | COMBUSTIBLE OR SHALL HAVE A FLAME SPREAD | | | INDEX OF NOT MORE THAN 25 AND SMOKE - | | | DEVELOPED INDEX OF NOT MORE THAN 50 WHEN | | | TESTED IN ACCORDANCE WITH ASTM E 84. | | | 2) OVERFLOW PROTECTION REQUIRED AS PER | | | 2001 FBC(M) 307.2.3. | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
|