Plan Review Details - Permit 06050625
Plan Review Stops For Permit 06050625
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-07-11 Cont ID  
Sent By alange Date 2006-07-11 Time 14:07 Rev Time 0.00
Received By alange Date 2006-07-11 Time 14:07 Sent To  
Notes
2006-07-11 00:00:00RESTAMP NEW PAGES

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-05-24 Cont ID  
Sent By alange Date 2006-05-24 Time 11:56 Rev Time 0.00
Received By alange Date 2006-05-24 Time 11:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-09-07 Cont ID  
Sent By btrobaug Date 2006-09-07 Time 17:59 Rev Time 0.75
Received By btrobaug Date 2006-09-07 Time 17:24 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-08-03 Cont ID  
Sent By btrobaug Date 2006-08-03 Time 16:16 Rev Time 0.75
Received By btrobaug Date 2006-08-03 Time 14:03 Sent To  
Notes
2006-08-03 00:00:00 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE 1" FEEDER TO PANEL "L2" IS TOO
 SMALL FOR THE FEED CONDUCTORS.
  
 2} PLEASE INDICATE THE LOCATION OF THE
 OVERCURRENT PROTECTION FOR PANEL "L2",
 AND SECONDARY PROTECTION FOR THE 30K
 TRANSFORMER.
  
 3} THE CIRCUIT NUMBERS FOR THE LIGHTS
 AND ON THE PLAN AND THE PANEL SCHEDULE
 DO NOT CORRELATE.
  
 4} INDICATE THE LOCATIONS OF THE EXIT
 AND EMERGENCY LIGHTING, AND LABEL SAME
 WITH CIRCUIT NUMBERS.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-07-07 Cont ID  
Sent By btrobaug Date 2006-07-07 Time 17:29 Rev Time 1.00
Received By btrobaug Date 2006-07-07 Time 16:11 Sent To  
Notes
2006-07-07 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE SCOPE OF THIS WORK REQUIRES
 ENGINEERING PER 471 FS.
 PLEASE HAVE AN ENGINEER DESIGN THE PLAN
 AND RESUBMIT. THE TERM "ENGINEER"
 APPLIES TO A PERSON LICENSED UNDER
 CHAPTER 471 FS. THE ARCHITECTDID NOT
 SEAL PAGE E-2, WHICH IS INCEDENTAL TO
 HIS DESIGN. HE, OR THE ENGINEER TAKING
 RESPONSIBILITY FOR THE SERVICE DRAWING,
 MUST SIGN AN DSEAL THIS SHEEET PR EITHER
 471 OR 481.FS
  
 2} INCLUDE ALL EQUIPMENT (PANELS "L" AND
 "H"), ON THE RISER.
  
 3} PANEL SCHEDULE "H" DOES NOT SHOW A
 FEED FOR THE 30 KVA TRANSFORMER. SHOW
 PANEL "H" ON THE RISER.
  
 4} PANEL "L2" IS LISTED AS "MLO",
 THEREFORE THE TRANSFORMER FEEDING IT HAS
 NO SECONDARY PROTECTION.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-05-17 Cont ID  
Sent By btrobaug Date 2006-05-17 Time 18:37 Rev Time 0.33
Received By btrobaug Date 2006-05-17 Time 18:10 Sent To  
Notes
2006-05-17 00:00:00 
  
 THE SCOPE OF THIS WORK REQUIRES
 ENGINEERING PER 471 FS.
 PLEASE HAVE AN ENGINEER DESIGN THE PLAN
 AND RESUBMIT.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-07-11 Cont ID  
Sent By mcarsill Date 2006-07-11 Time 14:59 Rev Time 0.00
Received By mcarsill Date 2006-07-11 Time 14:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-05-30 Cont ID  
Sent By mwennerg Date 2006-05-30 Time 15:10 Rev Time 0.00
Received By mwennerg Date 2006-05-30 Time 15:10 Sent To  
Notes
2006-05-30 00:00:00IN ADDITION TO FIRE SPRINKLER SYSTEM,
 SEPARATE SHOP DRAWINGS AND PERMIT
 REQUIRED FOR FIRE ALARM IF APPLICABLE
 GREATER THAN (5) DEVICES.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-08-22 Cont ID  
Sent By adarroug Date 2006-08-22 Time 17:45 Rev Time 0.00
Received By adarroug Date 2006-08-22 Time 17:45 Sent To E
Notes
2006-08-22 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-07-22 Cont ID  
Sent By adarroug Date 2006-07-22 Time 13:16 Rev Time 0.00
Received By adarroug Date 2006-07-22 Time 13:16 Sent To  
Notes
2006-08-01 00:00:00TO "BOB"#8
2006-07-22 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-06 Cont ID  
Sent By adarroug Date 2006-07-06 Time 15:28 Rev Time 0.00
Received By adarroug Date 2006-07-06 Time 15:28 Sent To  
Notes
2006-07-07 00:00:00TO "BOB"#6
2006-07-06 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-06 Cont ID  
Sent By adarroug Date 2006-06-06 Time 15:23 Rev Time 0.00
Received By adarroug Date 2006-05-17 Time 14:47 Sent To  
Notes
2006-05-17 00:00:00TO "BOB"#8

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-05-18 Cont ID  
Sent By tgordon Date 2006-05-18 Time 14:48 Rev Time 0.25
Received By tgordon Date 2006-05-18 Time 14:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-08-07 Cont ID  
Sent By jleech Date 2006-08-07 Time 08:20 Rev Time 0.00
Received By jleech Date 2006-08-07 Time 08:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-07-15 Cont ID  
Sent By jleech Date 2006-07-15 Time 12:26 Rev Time 0.00
Received By jleech Date 2006-07-15 Time 12:26 Sent To  
Notes
2006-07-15 00:00:00DENIED;
 1.HOSE BIBS WILL HAVE BACKFLOW
 PROTECTION TO COMPLY WITH FBC-2004
 PLUMBING SECTION 608.15.4.2.
 2.THE EQUIPMENT DRAIN IS NOT SHOWN. IF
 INDIRECT A FLOOR DRAIN IS REQUIRED WITH
 AN AIR GAP, IF DIRECT SHOW ON PLANS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-06-06 Cont ID  
Sent By jleech Date 2006-06-06 Time 10:03 Rev Time 0.00
Received By jleech Date 2006-06-06 Time 10:03 Sent To  
Notes
2006-06-06 00:00:00DENIED;
 SUBMIT MANUFATURE'S SPECIFCATIONS FOR
 PROC. NOT ENOUGH INFORMATION TO DO A
 PLUMBING PLAN REVIEW.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695