Plan Review Details - Permit 06050622
Plan Review Stops For Permit 06050622
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-05-25 Cont ID  
Sent By shill Date 2006-05-25 Time 17:25 Rev Time 0.00
Received By shill Date 2006-05-25 Time 17:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-16 Cont ID  
Sent By shill Date 2006-05-16 Time 15:33 Rev Time 0.00
Received By shill Date 2006-05-16 Time 15:33 Sent To  
Notes
2006-05-16 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)THE PRODUCT SUBMITTED HAS A DESIGN
 PRESSURE LIMITATION OF -36.SEE FBC
 TABLE 1609.6B, 140MPH.THIS PRODUCT
 DOES NOT MEET THE DESIGN PRESSURE
 REQUIREMENTS FOR ZONES 2 AND 3.I WAS
 UNABLE TO FIND IN THE PRODUCT APPROVAL
 ENHANCED FASTENING FOR THE PERIMETER AND
 CORNER ZONES.