Plan Review Details - Permit 06050609
Plan Review Stops For Permit 06050609
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2007-05-07 Cont ID  
Sent By lmartine Date 2007-05-07 Time 16:22 Rev Time 0.00
Received By lmartine Date 2007-05-07 Time 16:22 Sent To  
Notes
2007-05-07 16:38:00PLEASE REVISE WINDOW SCHEDULE TO CALL OUT SINGLE HUNG
 OR PROVIDE APPROVED DOUBLE HUNG PRODUCT APPROVAL.
  
  
  
  
  
  
 L.MARTINEZ
 561-805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-03-30 Cont ID  
Sent By lmartine Date 2007-03-30 Time 18:29 Rev Time 0.00
Received By lmartine Date 2007-03-30 Time 18:29 Sent To  
Notes
2007-03-30 18:30:16SECOND FLOOR BATHROOM REVISIONOK

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-03-30 Cont ID  
Sent By lmartine Date 2006-11-17 Time 18:29 Rev Time 0.00
Received By lmartine Date 2006-11-17 Time 13:33 Sent To  
Notes
2006-11-17 13:33:51STRUCTURAL REV. OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-08-23 Cont ID  
Sent By alange Date 2006-08-23 Time 08:52 Rev Time 0.00
Received By alange Date 2006-08-23 Time 08:52 Sent To  
Notes
2006-08-23 00:00:00REVIEW, STAMP, ISSUE

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-08-16 Cont ID  
Sent By alange Date 2006-08-16 Time 14:19 Rev Time 1.00
Received By alange Date 2006-08-16 Time 14:15 Sent To  
Notes
2006-08-16 00:00:00DENIED
  
  
 4.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE MIAMI-DADE'S SHALL
 HAVE THE FOLLOWING STATE APPROVAL
 ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-07-18 Cont ID  
Sent By alange Date 2006-07-18 Time 11:16 Rev Time 2.00
Received By alange Date 2006-07-18 Time 11:16 Sent To  
Notes
2006-07-18 00:00:00DENIED
  
  
 2.SIGN OWNER/AGENT ON ENERGY CALCS.
  
 3.PRODUCT APPROVALS REQUIRED FOR
 HARDI-PLANK SIDING AND LINTELS.
  
 4.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 5.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 6.SUBMIT TWO SETS OF TRUSS DRAWINGS
 FOR REVIEW PER 2004 FBC R-802.10.1
  
 7.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 9.SHOW ON PLANS HOW THE PRESSURE
 GROUTING PROGRAM WILL BE IMPLEMENTED AS
 RECOMMENDED BY THE GEOTECHNICAL REPORT.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE . A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-06-20 Cont ID  
Sent By alange Date 2006-06-20 Time 09:46 Rev Time 3.50
Received By alange Date 2006-06-20 Time 09:41 Sent To  
Notes
2006-06-20 00:00:00DENIED
  
  
 1.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 2.SIGN OWNER/AGENT ON ENERGY CALCS.
  
 3.PRODUCT APPROVALS REQUIRED FOR
 HARDI-PLANK SIDING AND LINTELS.
  
 4.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 5.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 6.SUBMIT TWO SETS OF TRUSS DRAWINGS
 FOR REVIEW PER 2004 FBC R-802.10.1
  
 7.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 8.SUBMIT BBQ SPECS WITH REQUIRED HOOD
 SPECS.
  
 9.SHOW ON PLANS HOW THE PRESSURE
 GROUTING PROGRAM WILL BE IMPLEMENTED AS
 RECOMMENDED BY THE GEOTECHNICAL REPORT.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE . A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-04-05 Cont ID  
Sent By btrobaug Date 2007-04-05 Time 13:08 Rev Time 0.75
Received By btrobaug Date 2007-04-05 Time 12:07 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-03-13 Cont ID  
Sent By btrobaug Date 2007-03-13 Time 10:52 Rev Time 0.50
Received By btrobaug Date 2007-03-13 Time 07:40 Sent To M
Notes
2007-03-13 10:52:12 
  
 REVISION DENIED
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE LOAD CALCULATION, AFTER DEMAND FACTORS ARE TAKEN
 , IS LARGER THAN THE PROPOSED SERVICE. SEE 220 PART II.
 INDICATE IF USING THE STANDARD CALCULATION IN 220 PART
 I, OR THE OPTIONAL CALCULATION (PREFERRED), 220.31(B).
 PLEASE SEE 230.31(B) MUST BE USED BECAUSE OF THE
 ADDITIONAL A/C LOADS.
  
 2} THE BATH CIRCUITS SHOWN AS HOME RUNS ON SHEET E-1,
 THIS REVISION, ARE NOT LISTED ON THE PANEL SCHEDULE. AS
 REQUIRED PER210.11(C)(3).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-06-08 Cont ID  
Sent By btrobaug Date 2006-06-08 Time 17:59 Rev Time 0.75
Received By btrobaug Date 2006-06-08 Time 16:45 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2007-04-18 Cont ID  
Sent By adarroug Date 2007-04-18 Time 14:02 Rev Time 0.00
Received By adarroug Date 2007-04-18 Time 14:02 Sent To B
Notes
2007-04-18 14:03:16TO "LMARTINEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-04-10 Cont ID  
Sent By rregueir Date 2007-04-10 Time 15:41 Rev Time 0.00
Received By rregueir Date 2007-04-10 Time 15:40 Sent To M
Notes
2007-04-10 15:41:05MECH REV SENT TO HAROLD MOSER.

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-04-03 Cont ID  
Sent By spalmer Date 2007-04-03 Time 18:06 Rev Time 0.00
Received By spalmer Date 2007-04-03 Time 18:06 Sent To E
Notes
2007-04-03 18:06:20TO SAMANTHA HILL

Review Stop I INCOMING/PROCESSING
Rev No 8 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By adarroug Date 2007-02-26 Time 16:59 Sent To  
Notes
2007-02-26 16:59:50TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-11-06 Cont ID  
Sent By adarroug Date 2006-11-06 Time 09:35 Rev Time 0.00
Received By adarroug Date 2006-11-06 Time 09:35 Sent To B
Notes
2006-11-06 09:35:37TO "ALANGE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-08-17 Cont ID  
Sent By adarroug Date 2006-08-17 Time 16:19 Rev Time 0.00
Received By adarroug Date 2006-08-17 Time 16:19 Sent To B
Notes
2006-08-17 00:00:00TO "ALANGE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-08-12 Cont ID  
Sent By adarroug Date 2006-08-12 Time 12:48 Rev Time 0.00
Received By adarroug Date 2006-08-12 Time 12:48 Sent To B
Notes
2006-08-12 00:00:00TO "ALANGE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-07-11 Cont ID  
Sent By adarroug Date 2006-07-11 Time 16:25 Rev Time 0.00
Received By adarroug Date 2006-07-11 Time 16:25 Sent To M
Notes
2006-07-11 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-06-30 Cont ID  
Sent By adarroug Date 2006-06-30 Time 09:25 Rev Time 0.00
Received By adarroug Date 2006-06-30 Time 09:25 Sent To Z
Notes
2006-06-30 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-07 Cont ID  
Sent By adarroug Date 2006-06-07 Time 18:48 Rev Time 0.00
Received By adarroug Date 2006-06-07 Time 18:48 Sent To E
Notes
2006-06-07 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-20 Cont ID  
Sent By alange Date 2006-06-20 Time 09:46 Rev Time 0.00
Received By alange Date 2006-05-18 Time 08:30 Sent To  
Notes
2006-05-18 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2007-04-10 Cont ID  
Sent By hmoser Date 2007-04-10 Time 16:22 Rev Time 0.00
Received By hmoser Date 2007-04-10 Time 16:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-04-06 Cont ID  
Sent By tgordon Date 2007-04-06 Time 09:16 Rev Time 0.30
Received By tgordon Date 2007-04-06 Time 09:16 Sent To  
Notes
2007-04-06 09:17:13REVISION TO MECH. PLANS PAGE M-1 AND M-2.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-03-13 Cont ID  
Sent By tgordon Date 2007-03-13 Time 15:35 Rev Time 0.35
Received By tgordon Date 2007-03-13 Time 15:35 Sent To B
Notes
2007-03-13 15:45:19** MECHANICAL REVISION **
 *** DENIED ***
 1) PLEASE PROVIDE RETURN AIR TO PLAYROOM, PER 2004
 FBC/R M1602.4.
  
 2) PLEASE SHOW THE SIZE OF THE TWO SUPPLY AIR DUCTS
 FROM AHU #2 TO THE TWO MIXING BOXES (SEE YELLOW
 HIGHLIGHT ON PLANS PAGE M-1).
  
 3) REVISED MECHANICAL PLANS ARE SHOWING A 6" PIPE TO
 THE EXISTING STOVE IN THE EXISTING KITCHEN, IF PIPE IS
 NEW SHOW WHAT IT IS FOR, TYPE OF MATERIAL, AND WERE
 PIPE TERMINATES.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-07-12 Cont ID  
Sent By tgordon Date 2006-07-12 Time 11:48 Rev Time 0.30
Received By tgordon Date 2006-07-12 Time 11:48 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-06-14 Cont ID  
Sent By tgordon Date 2006-06-14 Time 10:18 Rev Time 1.00
Received By tgordon Date 2006-06-14 Time 10:18 Sent To B
Notes
2006-06-14 00:00:00*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED
 BY OWNER/AGENT, PER 2004
 FBC/13-600.3.ABC.2 .
  
 2) "TITLE BLOCK" ARCHITECT PRINTED NAME,
 AND THE FIRM'S LICENSE NUMBER MUST
 APPEAR IN THE TITLE BLOCK, PER FAC
 61G1-16.003 .
  
 3) SHOW SUPPLY AIR CFM'S. AT ALL SUPPLY
 AIR GRILLS.
  
 4) AHU #3 PLEASE SHOW CORRECT SIZES FOR
 MAIN SUPPLY AIR TRUNK LINE.
  
 5) SHOW LOCATION AND TERMINATION OF
 CLOTHES DRYER VENT.
  
 6) PLEASE PROVIDE COMBUSTION AIR, OR
 COMBUSTION AIR CALCULATIONS FOR GAS
 WATER, PER 2004 FBC/M 701.
  
 7) PLEASE PROVIDE A APPROVED EXHAUST
 HOOD FOR THE GRILL IN THE COVERED LOGGIA
 WITH DETAILED MANUFACTURE'S
 SPECIFICATION'S AND INSTALLATION
 INSTRUCTIONS, OR PROVIDE GRILL
 MANUFACTURE'S SPECIFICATION'S SHOWING
 ONE IS NOT REQUIRED, PER 2004 FBC/M
 505.3 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-06-13 Cont ID  
Sent By jleech Date 2006-06-13 Time 14:29 Rev Time 0.00
Received By jleech Date 2006-06-13 Time 14:29 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2006-07-11 Cont ID  
Sent By mmclean Date 2006-07-11 Time 14:43 Rev Time 0.00
Received By mmclean Date 2006-07-11 Time 14:43 Sent To I
Notes
2006-07-11 00:00:00NOTE: THE PROPOSED MOTOR COURT, MUST BE
 A SMOOTH NON-DUSTING SURFACE (PAVERS,
 ASPHALT, CONCRETE).
  
 NOTE: MUST MAINTAIN 1000SQ FT OR 75% OF
 LANDSCAPE, WHICHEVER IS LESS WITHIN THE
 FIRST 25FT FRONT SETBACK.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-06-07 Cont ID  
Sent By mmclean Date 2006-06-07 Time 06:58 Rev Time 0.00
Received By mmclean Date 2006-06-06 Time 07:00 Sent To I
Notes
2006-06-07 00:00:00DENIED,
 1.MUST PROVIDE THE DIMENSION ON THE
 PROPOSED NEW MOTORCOURT (WIDTH & LENGTH)
  
 NOTE: MUST MAINTAIN 1000SQ FT OR 75% OF
 LANDSCAPE WITHIN THE FIRST 25FT FRONT
 SETBACK.
  
 2. THE NEW A/C UNIT (2) MUST BE 1FT AWAY
 FROM PROPERTY, MUST SHOW THAT ON THE TWO
 COPY OF SITEPLAN (PLEASE SHOW SETBACK).
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720