Plan Review Details - Permit 06050604
| Plan Review Stops For Permit 06050604 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2007-12-13 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-12-13 |
Time |
09:47 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2007-12-13 |
Time |
09:46 |
Sent To |
|
|
| Notes |
| 2007-12-12 13:10:16 | BLDG REVISIONS 9-29-07 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2007-11-08 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-11-08 |
Time |
09:34 |
Rev Time |
|
| Received By |
jwitmer |
Date |
2007-11-08 |
Time |
09:34 |
Sent To |
|
|
| Notes |
| 2007-11-08 14:14:51 | BUILDING PLAN REVIEW | | | PERMIT: 06050604 | | | ADD: 1810 S DIXIE HWY | | | CONT: BATTEN CONSTRUCTION | | | TEL: (561)662-0309 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ NOV. 21 2005 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVISION REVIEW | | | ACTION: DENIED | | | | | | 1A) SITE PLAN, INDICATES THE DELETION OF THE | | | HANDICAPPED RAMP TO SPACE # 1 AND THE NEW DOOR TO THE | | | REAR OF SPACE # 1 IS ALSO NOT ON AN ACCESSIBLE ROUTE | | | PLEASE SEE , 11-4.1.6(A) NO ALTERATION SHALL BE | | | UNDERTAKEN WHICH DECREASES OR HAS THE EFFECT OF | | | DECRESING ACCESSIBILITY OR USABILITY OF A BUILDING. | | | | | | 1B) SITE PLAN, THE TENANT SEPERATION LINE ON THIS SHEET | | | DOES NOT MATCH WITH SHEET# 3. IT APPEARS ON SHEET # 3 | | | TENANT SPACE # 2 HAS THE FRONT ENTRY DELETED AND THE | | | INTERIOR FOYER. THE NEW ENTRY WILDEMERE AVENUE BUT THE | | | SITE PLAN HAS NOT BEEN UPDATED | | | TO REFLECT A NEW ENTRY OR WALKWAY FROM THE PUBLIC WAY. | | | 11-4.1.6(A) NO ALTERATION SHALL BE UNDERTAKEN WHICH | | | DECREASES OR HAS THE EFFECT OF DECRESING ACCESSIBILITY | | | OR USABILITY OF A BUILDING. | | | | | | 1C) SITE PLAN, PLEASE UPDATE THE SITE PLAN SHOWING AN | | | ACCESSIBLE ROUTE TO BOTH SPACE NUMBER 1 & 2. THE ISSUE | | | NOW CREATED WITH THE REMOVAL OF THE HANDICAPPED RAMP | | | AND NOT INDICATING THE ACCESSIBLE ROUTE TO SPACE NUMBER | | | ONE WHERE THE NEW DOOR IS | | | LOCATED IN THE REAR OF THE BUILDING IT WILL CAUSE THE | | | DISABLED INDIVIDUAL TO TRAVEL BEHIND PARKED VEHICLE, | | | PLEASE SEE 11-4.6.2 ACCESSIBLE PARKING SPACES SERVING A | | | PARTICULAR BUILDING SHALL BE LOCATED ON THE SHOREST | | | SAFELY ACCESSIBLE ROUTE TRAVELED FROM ADJACENT PARKING | | | TO AN ACCESSIBLE ENTRANCE. WITH THE DELETION OF THE | | | FRONT ENTRY LOBBY IT COULD BE ARGUED THAT EQUIVALENT | | | FACILITATION 11-2.2 IS NOT BEING MET, | | | | | | 2) SHEET NUMBER THREE PLEASE SHOW THE REVISION TO THE | | | PLAN HIGHLIGHT WITH EITHER A CLOUD OR DELTA WHATTHE | | | SCOPE OF WORK TO BE COMPLETED UNDER THIS REVISION, | | | PLANS ARE UNCLEAR, EXAMPLE IF THERE IS TO BE NO TENANT | | | BUILDOUT IN SPACE # 1 THEN DO NOT SHOW A | | | FINISHED INTERIOR, OR IF THE FRONT ENTRY AND LOBBY ARE | | | DELETED THEN REMOVE FROM THE PROJECT. 106.1.1 | | | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY | | | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK | | | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE | | | PROVISIONS OF THIS CODE.\ | | | | | | 3)SHEET # 5 INDICATES THE REMOVAL OF ROOF DRAINS, AND | | | SHEET # 10 INDICATES THE REMOVAL OF THE PARAPET, PLEASE | | | SHOW HOW AND OR WHERE THE WATER WILL BE REOMVED FROM | | | THE ROOF. EITHER SHOW THE SLOPE WHERE ATER WILL OVER | | | FLOW THE EDGE OF THE ROOF, WHERE A GUTTER AND ROOF | | | LEADERS1503.4 ROOF DRAINAGE, 1503.4.1 GUTTERS. 1503.3.6 | | | PROTECTION AGAINST DECAY & TERMITES. CONDENSATE LINES & | | | ROOF DOWN SPOUTS SHALL DISCHARGE AT LEAST 1 FT. AWAY | | | FROM THE STRUCTURE SIDEWALL, WHETHER BY UNDERGROUND | | | PIPING, TAIL EXTENSIONS, OR SPLASH BLOCKS. 102.1* | | | WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS OF THIS | | | CODE SPECIFY DIFFERENT MATERIALS, METHODS OF | | | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST | | | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT | | | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC | | | REQUIREMENT, THE SPECIFIC | | | REQUIREMENT SHALL BE APPLICABLE. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAILCOMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2007-09-18 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-09-18 |
Time |
07:49 |
Rev Time |
1.37 |
| Received By |
jwitmer |
Date |
2007-09-18 |
Time |
07:49 |
Sent To |
|
|
| Notes |
| 2007-09-18 07:54:41 | BUILDING PLAN REVIEW | | | PERMIT: 06050604 | | | ADD: 1810 S DIXIE HWY | | | CONT: BATTEN CONSTRUCTION | | | TEL: (561)820-0027 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVISIONREVIEW: 7-26-07 | | | ACTION: DENIED | | | | | | | | | 1) THE FLOOR PLAN AND NEW ELEVATIONS ON SHEETS 20 AND | | | 21 DO NOT MATCH UPPER OPENING. PLEASE REVIEW AND ON THE | | | BUILDING CALCULATE THE PERCENT OF OPENINGS | | | TABLE 704.8 MAXIMUM AREA OF WALL OPENINGS. | | | | | | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS | | | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF | | | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST | | | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT | | | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC | | | REQUIREMENT, THE SPECIFIC | | | REQUIREMENT SHALL BE APPLICABLE. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | | | | | | | | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2007-01-16 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-01-03 |
Time |
14:24 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2007-01-02 |
Time |
14:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2006-10-25 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-10-25 |
Time |
16:33 |
Rev Time |
3.33 |
| Received By |
jwitmer |
Date |
2006-10-25 |
Time |
16:33 |
Sent To |
|
|
| Notes |
| 2006-10-25 16:57:29 | PERMIT: 06050604 | | | ADD: 1810 S DIXIE HWY | | | CONT: BATTEN CONSTRUCTION | | | TEL: (561)820-0027 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2NDREVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2) FL S S 713.13 | | | NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT BEFORE A | | | PERMIT WILL BE ISSUED. NOTE: 713.13(2) | | | IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS | | | NOT ACTUALLY COMMENCED | | | WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. | | | | | | 3) SHEET# 1 CODE DATA INDICATES A | | | TYPE III BUILDING BUT NO DESIGNATION TO | | | "A" OR "B". | | | | | | 4) COMPLIED. | | | | | | 5)2ND REQUEST, SHEET 1B INDICATES AS DEPICTED A 2" DROP | | | FROM THE INTERIOR FINISH SLAB TO THE EXTERIOR OF THE | | | BUILDING. | | | SHEET# 1B INDICATES ELEVATIONS ON | | | THE INTERIOR FINISH FLOOR OF 16.76'AND | | | THE EXTERIOR ELEVATION OF 16.64'. | | | 11-4.3.8 CHANGES IN LEVEL. | | | CHANGES IN LEVELS ALONG AN ACCESSIBLE | | | ROUTE SHALL COMPLY WITH SECTION 11-4.5.2 | | | . IF AN ACCESSIBLE ROUTE HAS CHANGES IN | | | LEVEL GREATER THAN ? INCH (13 MM), THEN | | | A CURB RAMP, RAMP, ELEVATOR, OR PLATFORM | | | LIFT (AS PERMITTED IN SECTION 11-4.1.3 | | | AND 11-4.1.6 ) SHALL BE PROVIDED THAT | | | COMPLIES WITH SECTION 11-4.7 , 11-4.8 , | | | 11-4.10 , OR 11-4.11 , RESPECTIVELY. AN | | | ACCESSIBLE ROUTE DOES NOT INCLUDE | | | STAIRS, STEPS, OR ESCALATORS. SEE | | | DEFINITION OF ?EGRESS, MEANS OF? IN | | | SECTION 11-3.5 [SEE FIGURE 11-7 (C) AND | | | FIGURE 11-7 (D)]. | | | | | | 6) COMPLIED. | | | | | | 7) COMPLIED. | | | | | | 8) COMPLIED. | | | | | | 9) COMPLIED. | | | | | | 10) SHEET 3, 4 AND SHEET 11 ALL DETECT A MEZANINE | | | LEVEL. AS ASKED IN REVIEW COMMENT | | | NUMBER 1 PLEASE REMOVE ALL OLD SHEETS FROM THE PERMIT | | | PACKAGE. SHEET 11 ALSO NEEDS TO BE REMOVED. | | | | | | 11)COMPLIED, ONCE ALL REFRENCE TO MEZZANINE IS | | | REMOVED FROM PLANS. | | | | | | 12) COMPLIED, ONCE ALL REFRENCE TO MEZZANINE | | | | | | 13) 2ND REQUEST, SHEET#3 DOESN'T PROVIDE ANY CUT | | | SECTION THROUGH THE TENANT | | | SEPERATION WALL PROVIDING A 1 HR TENANT SEPERATION. | | | EITHER PROVIDE THE UL LISTING AND | | | DESCRIPTION OF WALL OR TAKE THE PERSCRIPTIVE MEETHOD IN | | | TABLE 720.1(2). | | | | | | 14) COMPLIED. | | | | | | 15) COMPLIED. | | | | | | 16) COMPLIED, ONCE ALL REFRENCES TO THE MEZZANINE LEVEL | | | ARE REMOVED. | | | | | | 17)) 1209.3 MECHANICAL APPLIANCES. | | | ACCESS TO MECHANICAL APPLIANCES INSTALLED IN | | | UNDER-FLOOR AREAS, IN ATTICS SPACES AND ON ROOFS OR | | | ELEVATED STRUCTURES SHALL BE IN ACCORDANCE WITH THE | | | FLORIDA BUILDING MECHANICAL CODE. | | | | | | 18) COMPLIED ONCE ALL REFRENCES TO THE MEZZANINE ARE | | | REMOVED. | | | | | | 19) COMPLIED. | | | | | | 20) COMPLIED. | | | | | | 21) COMPLIED. | | | | | | 22) COMPLIED, ONCE ALL REFRENCES TO THE MEZZANINE ARE | | | REMOVED. | | | | | | 23)COMPLIED. | | | | | | 24) COMPLIED. | | | | | | 25) 2ND REQUEST,) WPB ADMIN CODE 106.3* PRODUCT | | | APPROVALS. THOSE PRODUCT WHICH ARE | | | REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL | | | FOR JURISDICTIONAL APPROVAL. | | | | | | 26)2ND REQUEST, UNTIL REVIEWD BY THE DESIGNED | | | PROFESSIONAL | | | AND SIGNED OFF ACCEPTED THIS COMMENT WILL REMAIN. FL | | | BLD CODE 1606.1.5: COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | | TESTING REPORTS,MISSING REPORTS ARE AS | | | FOLLOWS: | | | A) FIXED WINDOWS | | | B) MULLIONS | | | C) GLAZED DOORS | | | D) HOLLOW METAL DOORS SINGLE & PAIR | | | E) ROOF ASSEMBLIES | | | 1) FLAT ROOF INSULATION | | | 2) MODIFIED SINGLE PLY | | | 3) SLOPED ROOFING APPLICATION | | | 4) ROOF TILE REPORT | | | | | | 27) THIS ROOF IS MISSING OR NOT IN | | | COMPLIANCE WITH THE FOLLOW ITEMS: | | | ___ CONTRACTOR FAILED TO SUBMIT PRODUCT APPROVALS. | | | | | | _X_ CONTRACTOR FAILED TO INDICATE WHICH | | | SYSTEM TO BE USED. | | | | | | _X_ THE SYSTEM PROVIDED HAS A LOW | | | PRESSURE FOR ZONE ___ . | | | | | | _X_ NO SYSTEMS WERE SUBMITTED IN REPORT. MISSING | | | SUBREPORTS LISTED PAGE9-18. | | | NO SUBREPORT WAS HIGHLIGHTED.WITH THE REPORT | | | SUBMITTED, THIS MAY BE A | | | SITUATION: | | | THE SYSTEM PROVIDED STATES | | | LIMITATION# 7, SHOULD THE FASTENER | | | RESISTANCE BE LESS THAN THAT | | | REQUIRED, AS DETERMINED BY THE | | | BUILDING OFFICIAL, A REVISED | | | FASTENER SPACING, PREPARED , SIGNED | | | | | | AND SEALED BY A FLORIDA REGISTERED | | | PROFESSIONAL ENGINEER, REGISTERED | | | ARCHITECT OR REGISTERED ROOF | | | CONSULTANT MAY BE SUBMITTED. | | | | | | _X_NO SUBSYSTEMS SUBMITTED, MAYBE A | | | SITUATION. | | | THE SYSTEM PROVIDED INDICATES | | | LIMITATION# 9, NO ENHANCED | | | FASTENING ALLOWED. | | | | | | _X_ HIP OR RIDGE TILE INDICATE WHAT TYPE | | | OF HIP BOARD TO BE USED, ALSO | | | INDICATE TYPE OF FASTENING. | | | CLAY AND CONCRETE ROOF TILES SHALL BE | | | FASTENED IN ACCORDANCE WITH SECTION 1609 | | | OR IN ACCORDANCE WITH FRSA/RTI | | | 07320/08/05 INSTALLATION MANUAL. | | | | | | 1507.3.8 APPLICATION. | | | TILE SHALL BE APPLIED ACCORDING TO THE MANUFACTURER?S | | | INSTALLATION INSTRUCTIONS | | | OR RECOMMENDATIONS OF THE FRSA/RTI | | | 07320/08/05. | | | | | | 28) COMPLIED. | | | | | | 29) PROVISO: TO BE CHECKED BY INSPECTOR BEFORE C.O.: | | | 804.5.1 MINIMUM CRITICAL RADIANT FLUX . | | | INTERIOR FLOOR FINISH IN VERTICAL EXITS, | | | EXIT PASSAGEWAYS AND EXIT ACCESS | | | CORRIDORS SHALL NOT BE LESS THAN CLASS I | | | IN GROUPS I-2 AND I-3 AND NOT LESS THAN | | | CLASS II IN GROUPS A, B, E, H, I- 4, M, | | | R-1, R-2 AND S. IN ALL OTHER AREAS, THE | | | INTERIOR FLOOR FINISH SHALL COMPLY WITH | | | THE DOC FF-1 ?PILL TEST? (CPSC 16 CFR, | | | PART 1630). | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-06-01 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-06-01 |
Time |
13:24 |
Rev Time |
4.44 |
| Received By |
jwitmer |
Date |
2006-06-01 |
Time |
13:24 |
Sent To |
|
|
| Notes |
| 2006-06-01 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 06050604 | | | ADD: 1810 S DIXIE HWY | | | CONT: BATTEN CONSTRUCTION | | | TEL: (561)820-0027 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2) FL S S 713.13 | | | NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT BEFORE A | | | PERMIT WILL BE ISSUED. NOTE: 713.13(2) | | | IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS | | | NOT ACTUALLY COMMENCED | | | WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. | | | | | | 3) SHEET# 1 CODE DATA INDICATES A | | | TYPE III BUILDING BUT NO DESIGNATION TO | | | "A" OR "B". | | | | | | 4) MISSING FROM CODE DATA SHEET# 1 IS | | | FROM THE 2004 EXISTING BUILDING CODE, | | | TO WHAT LEVEL OF REMODELING, LEVEL 1, | | | LEVEL 2 OR LEVEL 3? SEE EXISTING | | | BUILDING CODE SECTIONS 303, 304 & 305. | | | | | | 5) SHEET # 1B INDICATES ELEVATIONS ON | | | THE INTERIOR FINISH FLOOR OF 16.76'AND | | | THE EXTERIOR ELEVATION OF 16.64'. | | | 11-4.3.8 CHANGES IN LEVEL. | | | CHANGES IN LEVELS ALONG AN ACCESSIBLE | | | ROUTE SHALL COMPLY WITH SECTION 11-4.5.2 | | | . IF AN ACCESSIBLE ROUTE HAS CHANGES IN | | | LEVEL GREATER THAN ? INCH (13 MM), THEN | | | A CURB RAMP, RAMP, ELEVATOR, OR PLATFORM | | | LIFT (AS PERMITTED IN SECTION 11-4.1.3 | | | AND 11-4.1.6 ) SHALL BE PROVIDED THAT | | | COMPLIES WITH SECTION 11-4.7 , 11-4.8 , | | | 11-4.10 , OR 11-4.11 , RESPECTIVELY. AN | | | ACCESSIBLE ROUTE DOES NOT INCLUDE | | | STAIRS, STEPS, OR ESCALATORS. SEE | | | DEFINITION OF ?EGRESS, MEANS OF? IN | | | SECTION 11-3.5 [SEE FIGURE 11-7 (C) AND | | | FIGURE 11-7 (D)]. | | | | | | 6) SHEET# 3, PLANS INDICATE AREAS OF | | | WALLS WHERE NEW OPENINGS ARE BEING | | | CREATED. ON THE NORTH WALL THERE IS A | | | SECTION 3/10 WITH A NOTE NEW #6 NEXT TO | | | OPENINGS, DOES MEAN IF A #6 REBAR IS | | | DEPICTED NEXT TO AN OPENING THIS IS A | | | NEW OPENING? | | | | | | 7) OFFICE WITH DOOR# 7 PRIVATE RESTROOM | | | TO BE ADAPTABLE, REQUIRING BACKING & | | | TURNING RADIUS. | | | 11-4.1.3(11) TOILET FACILITIES. IF | | | TOILET ROOMS ARE PROVIDED, THEN EACH | | | PUBLIC AND COMMON USE TOILET ROOM SHALL | | | COMPLY WITH SECTION 11-4.22 . OTHER | | | TOILET ROOMS PROVIDED FOR THE USE OF | | | OCCUPANTS OF SPECIFIC SPACES (I.E., A | | | PRIVATE TOILET ROOM FOR THE OCCUPANT OF | | | A PRIVATE OFFICE) SHALL BE ADAPTABLE . | | | IF BATHING ROOMS ARE PROVIDED, THEN EACH | | | PUBLIC AND COMMON USE BATHROOM SHALL | | | COMPLY WITH SECTION 11-4.23 . ACCESSIBLE | | | TOILET ROOMS AND BATHING FACILITIES | | | SHALL BE ON AN ACCESSIBLE ROUTE. | | | | | | 8) SHEET# 3 CONFERENCE ROOM DOOR# 22 | | | MISSING THE REQUIRED 18" ON PULL SIDE. | | | 11-4.13.6 MANEUVERING CLEARENCES | | | AT DOORS. MINIMUM MANEUVERING CLEARENCES | | | AT DOORS THAT ARE NOT AUTOMATIC OR | | | POWER-ASSISTED SHALL BE AS SHOWN IN | | | FIG. 25. THE FLOOR OR GROUND AREA WITH | | | IN THE REQUIRED CLEARENCES SHALL BE | | | CLEAR & LEVEL. | | | | | | 9) RESTROOM DOORS 12& 13 SWING OVER THE | | | 1/2 THE REQUIRED EGRESS WIDTH. | | | 1008.1.8.8 | | | DURING ITS SWING, ANY DOOR IN A MEANS OF | | | EGRESS SHALL LEAVE UNOBSTRUCTED AT LEAST | | | ONE HALF OF THE REQUIRED WIDTH OF AN | | | AISLE, CORRIDOR, PASSAGEWAY, OR LANDING, | | | NOR PROJECT MORE THAN 7 INCHES (178 MM) | | | INTO THE REQUIRED WIDTH OF AN AISLE, | | | CORRIDOR, PASSAGEWAY OR LANDING, WHEN | | | FULLY OPEN | | | | | | 10) SHEET# 3 & 4 BOTH INDICATE A | | | MEZZANINE BUT PLANS DO NOT INDICATE WHAT | | | TYPE OF OCCUPANCY WILL TAKE PLACE | | | MEZZANINE LEVEL? | | | | | | 11)MEZZANINE IF STORAGE: | | | 106.4.2 STORAGE & FACTORY- INDUSTRIAL OCCUPANCIES. IT | | | SHALL BE THE | | | RESPONSIBILITY OF THE OWNER, AGENT, | | | PROPIETOR OR OCCUPANT OF GROUP S AND | | | GROUP F OCCUPANCIES, OR ANY OCCUPANCY | | | WHERE EXCESSIVE FLOOR LOADING IS LIKELY | | | TO OCCUR, TO EMPLOY A COMPETENT ARCHI- | | | TECT OR ENGINEER IN COMPUTING THE SAFE | | | FLOOR LOAD CAPACITY. ALL SUCH COMPUTA- | | | TIONS SHALL BE ACCOMPANIED BY AN AFFA- | | | DAVIT FROM THE ARCHITECT OR ENGINEER | | | STATING THE SAFE ALLOWABLE FLOOR LOADS | | | ON EACH FLOOR IN POUNDS PER SQ FT.THE | | | COMPUTATIONS & AFFADAVIT SHALL BE FILED | | | AS A PERMANENT RECORD OF THE BLDG DEPT. | | | | | | 12) MEZZANINE: IF STORAGE: | | | 106.4.3.SIGNS REQUIRED. IN EVERY | | | BUILDING OR PART OF A BUILDING USED FOR | | | STORAGE, INDUSTRIAL OR HAZARDOUS PUR- | | | POSES, THE SAFE FLOOR LOADS, AS REVIEWED | | | BY THE BUILDING OFFICIAL ON THE PLAN, | | | SHALL BE MARKED ON PLATES OF APPROVED DE | | | SIGN WHICH SHALL BE SUPPLIED & SECURELY | | | AFFIXED BY THE OWNER OF THE BUILDING IN | | | A CONSPICUOUS PLACE IN EACH STORY TO | | | WHICH THEY RELATE. SUCH PLATES SHALL NOT | | | BE REMOVEDOR DEFACED, & IF LOST, | | | REMOVED THE OWNER OF THE BUILDING SHALL | | | REPLACE THEM. | | | | | | 13) SHEET#3 DOESN'T PROVIDE ANY CUT | | | SECTIONS THROUGH TENANT SEPARATION WALL | | | PROVIDING 1HR TENANT SEPERTION. | | | 708.1(5) | | | | | | 14) DOOR SCHEDULE DOESN'T INDICATE THE | | | RATING FOR DOORS 2 & 3. | | | | | | 15) OVERFLOW SCUPPERS, SHEET 4,6 AND 6A | | | DO NOT PROVIDE ENOUGH INFORMATION AS TO | | | THE LOCATION THE OVERFLOW SCUPPERS ARE | | | TO BE PLACED IN RELATION TO THE ROOF | | | DECK. | | | 1503.4.3 | | | WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW | | | WATER IS NOT PROVIDED, OVERFLOW SCUPPERS | | | SHALL BE PLACED IN WALLS OR PARAPETS NOT | | | LESS THAN 2 INCHES (51 MM) NOR MORE THAN | | | 4 INCHES (102 MM) ABOVE THE FINISHED | | | ROOF COVERING AND SHALL BE LOCATED AS | | | CLOSE AS PRACTICAL TO REQUIRED VERTICAL | | | LEADERS OR DOWNSPOUTS OR WALL AND | | | PARAPET SCUPPERS. AN OVERFLOW SCUPPER | | | SHALL BE SIZED IN ACCORDANCE WITH THE | | | FLORIDA BUILDING CODE, PLUMBING. | | | | | | 16) PLANS DO NOT PROVIDE THE FINISHED | | | HEIGTH FLOOR TO CEILING BENEATH THE | | | MEZZANINE. 1208.2 MINIMUM CEILING | | | HEIGHTS. | | | OCCUPIABLE SPACES, HABITABLE SPACES AND | | | CORRIDORS SHALL HAVE A CEILING HEIGHT OF | | | NOT LESS THAN 7 FEET 6 INCHES (2286 MM). BATHROOMS, | | | TOILET ROOMS, KITCHENS, | | | STORAGE ROOMS AND LAUNDRY ROOMS SHALL BE | | | PERMITTED TO HAVE A CEILING HEIGHT OF | | | NOT LESS THAN 7 FEET (2134 MM). | | | | | | 17) 1209.3 MECHANICAL APPLIANCES. | | | ACCESS TO MECHANICAL APPLIANCES | | | INSTALLED IN UNDER-FLOOR AREAS, IN ATTIC | | | SPACES AND ON ROOFS OR ELEVATED | | | STRUCTURES SHALL BE IN ACCORDANCE WITH | | | THE FLORIDA BUILDING CODE, MECHANICAL. | | | | | | 18) SHEET# 9 DETAIL# 2, IS MISSING THE | | | HANDRAIL COTINUING TO THE BOTTOM OF | | | STAIR LEFT SIDE OF DETAIL. | | | 1009.11 HANDRAILS. STAIRWAYS SHALL HAVE | | | HANDRAILS ON EACH SIDE. | | | | | | 19) SHEET# 10 INDICATES A 12"X12" | | | EXTERIOR MOLDING, PROVIDE DETAILS, AND | | | TYPE OF MATERIAL? | | | | | | 20) SHEET# 12 WIND INFORMATION | | | REFREENCES THE FBC 2001 CODE. | | | | | | 21) SHEET# 12 NO MENTION OF THE LIVE | | | FLOOR LOADS REQUIRED FOR THE MECANICAL | | | CLOSETS 60 PSF TABLE 1607.1. | | | | | | 22) SHEET# 12 NO MENTION TO THE LIVE | | | LOADS TO BE RESISTED FOR THE STAIRS. | | | TABLE 1607.1. | | | | | | 23) SHEET 18 INDICATES A/C DUCT | | | PENETRATING TENANT SEPERATION WALL AND | | | TRANSFER GRILLE NO FIRE DAMPERS.716.1.1 | | | DUCTS AND AIR TRANSFER OPENINGS WITHOUT | | | DAMPERS. DUCTS AND AIR TRANSFER OPENINGS | | | THAT PENETRATE FIRE-RESISTANCE-RATED | | | ASSEMBLIES AND ARE NOT REQUIRED BY THIS | | | SECTION TO HAVE DAMPERS SHALL COMPLY | | | WITH THE REQUIREMENTS OF SECTION 712 | | | | | | 24) SHEET 18 ALSO INDICATES A/C | | | CONDENSATE PENETRATING 1 HR TENANT | | | SEPERATION WALL. | | | 712.3.1.2 THROUGH-PENETRATION FIRESTOP | | | SYSTEM. THROUGH PENETRATIONS SHALL BE | | | PROTECTED BY AN APPROVED PENETRATION | | | FIRESTOP SYSTEM INSTALLED AS TESTED IN | | | ACCORDANCE WITH ASTM E 814 OR UL 1479, | | | WITH A MINIMUM POSITIVE PRESSURE | | | DIFFERENTIAL OF 0.01 INCH (2.49 PA) OF | | | WATER AND SHALL HAVE AN F RATING OF NOT | | | LESS THAN THE REQUIRED FIRE-RESISTANCE | | | RATING OF THE WALL PENETRATED. | | | | | | 25) WPB ADMIN CODE 106.3* PRODUCT | | | APPROVALS. THOSE PRODUCT WHICH ARE | | | REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL | | | FOR JURISDICTIONAL APPROVAL. | | | | | | 26) FL BLD CODE 1606.1.5: COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | | TESTING REPORTS,MISSING REPORTS ARE AS | | | FOLLOWS: | | | A) FIXED WINDOWS | | | B) MULLIONS | | | C) GLAZED DOORS | | | D) HOLLOW METAL DOORS SINGLE & PAIR | | | E) ROOF ASSEMBLIES | | | 1) FLAT ROOF INSULATION | | | 2) MODIFIED SINGLE PLY | | | 3) SLOPED ROOFING APPLICATION | | | 4) ROOF TILE REPORT | | | | | | 27) THIS ROOF IS MISSING OR NOT IN | | | COMPLIANCE WITH THE FOLLOW ITEMS: | | | _X_ CONTRACTOR FAILED TO SUBMIT PRODUCT APPROVALS. | | | | | | _X_ CONTRACTOR FAILED TO INDICATE WHICH | | | SYSTEM TO BE USED. | | | | | | _X_ THE SYSTEM PROVIDED HAS A LOW | | | PRESSURE FOR ZONE ___ . | | | | | | _X_ NO REPORT SUBMITTED,MAY BE A | | | SITUATION: | | | THE SYSTEM PROVIDED STATES | | | LIMITATION# 7, SHOULD THE FASTENER | | | RESISTANCE BE LESS THAN THAT | | | REQUIRED, AS DETERMINED BY THE | | | BUILDING OFFICIAL, A REVISED | | | FASTENER SPACING, PREPARED , SIGNED | | | | | | AND SEALED BY A FLORIDA REGISTERED | | | PROFESSIONAL ENGINEER, REGISTERED | | | ARCHITECT OR REGISTERED ROOF | | | CONSULTANT MAY BE SUBMITTED. | | | | | | _X_NO REPORT SUBMITTED, MAYBE A | | | SITUATION. | | | THE SYSTEM PROVIDED INDICATES | | | LIMITATION# 9, NO ENHANCED | | | FASTENING ALLOWED. | | | | | | _X_ HIP OR RIDGE TILE INDICATE WHAT TYPE | | | | | | OF HIP BOARD TO BE USED, ALSO | | | INDICATE TYPE OF FASTENING. | | | CLAY AND CONCRETE ROOF TILES SHALL BE | | | FASTENED IN ACCORDANCE WITH SECTION 1609 | | | OR IN ACCORDANCE WITH FRSA/RTI | | | 07320/08/05 INSTALLATION MANUAL. | | | | | | 1507.3.8 APPLICATION. | | | TILE SHALL BE APPLIED ACCORDING TO THE MANUFACTURER?S | | | INSTALLATION INSTRUCTIONS | | | OR RECOMMENDATIONS OF THE FRSA/RTI | | | 07320/08/05. | | | | | | 28)SHEET 11 DETAILS D/E GLASS IN GUARD | | | RAILS: | | | 1607.7.1.1 CONCENTRATED LOAD. | | | HANDRAIL ASSEMBLIES AND GUARDS SHALL BE | | | ABLE TO RESIST A SINGLE CONCENTRATED | | | LOAD OF 200 POUNDS (0.89 KN), APPLIED IN | | | ANY DIRECTION AT ANY POINT ALONG THE | | | TOP, AND HAVE ATTACHMENT DEVICES AND | | | SUPPORTING STRUCTURE TO TRANSFER THIS | | | LOADING TO APPROPRIATE STRUCTURAL | | | ELEMENTS OF THE BUILDING. THIS LOAD NEED | | | NOT BE ASSUMED TO ACT CONCURRENTLY WITH | | | THE LOADS SPECIFIED IN THE PRECEDING | | | PARAGRAPH. | | | 2407.1.1 LOADS. | | | THE PANELS AND THEIR SUPPORT SYSTEM | | | SHALL BE DESIGNED TO WITHSTAND THE LOADS | | | SPECIFIED IN SECTION 1607.7 . A SAFETY | | | FACTOR OF FOUR SHALL BE USED. | | | 2407.1.2 SUPPORT. | | | EACH HANDRAIL OR GUARD SECTION SHALL BE | | | SUPPORTED BY A MINIMUM OF THREE GLASS | | | BALUSTERS OR SHALL BE OTHERWISE | | | SUPPORTED TO REMAIN IN PLACE SHOULD ONE | | | BALUSTER PANEL FAIL. GLASS BALUSTERS | | | SHALL NOT BE INSTALLED WITHOUT AN | | | ATTACHED HANDRAIL OR GUARD. | | | | | | 29) NOTE TO BE CHECKED WITH INSPECTOR: | | | FLUX | | | 804.5.1 MINIMUM CRITICAL RADIANT FLUX . | | | INTERIOR FLOOR FINISH IN VERTICAL EXITS, | | | EXIT PASSAGEWAYS AND EXIT ACCESS | | | CORRIDORS SHALL NOT BE LESS THAN CLASS I | | | IN GROUPS I-2 AND I-3 AND NOT LESS THAN | | | CLASS II IN GROUPS A, B, E, H, I- 4, M, | | | R-1, R-2 AND S. IN ALL OTHER AREAS, THE | | | INTERIOR FLOOR FINISH SHALL COMPLY WITH | | | THE DOC FF-1 ?PILL TEST? (CPSC 16 CFR, | | | PART 1630). | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2007-10-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-10-26 |
Time |
08:07 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-10-25 |
Time |
16:56 |
Sent To |
|
|
| Notes |
| 2007-10-26 08:14:16 | PREVIOUSLY REVIEWED AND STAMPED ON 9/8/07. | | | SAME SHEETS, NO NEW SHEETS. | | | RETAINED ELECTRICAL FROM ONE SET FOR FILING. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2007-09-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-09-08 |
Time |
19:13 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-09-08 |
Time |
19:13 |
Sent To |
|
|
| Notes |
| 2007-09-08 19:15:29 | 2007-09-08 19:15:29 | | | | | | SCOPE OF WORK DECREASED. | | | HIGH-LIGHTED AND REDLINED PLANS FOR SCOPE OF ELECTRICAL | | | NO LONGER INCLUDED. | | | ELECTRICAL PLANS STAMPED. NEED TO RETAIN ONE COPY OF | | | ELECTRICLA ONCE FIRE REVIEW IS COMPLETED. | | | | | | ** PLEASE KNOW REVISED ENERGY CALCULATIONS FOR ACTUALL | | | SCOPE OF WORK WILL BE REQUIRED BEFORE FINAL. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2007-02-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-02-14 |
Time |
11:57 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-02-14 |
Time |
11:47 |
Sent To |
|
|
| Notes |
| 2007-02-14 11:58:49 | HAND WRITTEN OC SENSOR ADDED TO PLANS OK AND REDLINED. | | | | | | MIN 2GRND RODS REQUIRED FOR GROUNDING ELECTRODE SYSTEM. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2006-12-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-12-17 |
Time |
15:18 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-12-17 |
Time |
14:32 |
Sent To |
|
|
| Notes |
| 2006-12-17 15:19:38 | *** UNSAT 3RD REVIEW *** | | | | | | ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEWS HAVE NOT | | | YET BEEN FULLY ADDRESSED. | | | PLEASE SEE NEW COMMENTS WHICH SHOULD BE NOTED AS THIS | | | REVIEWER GOING THROUGH PLANS SUBMITTED. | | | | | | 1) NOTE: PLEASE SEE AREA FOR INGRESS/EGRESS AT THE REAR | | | OF BUILD OUT WHICH DOES NOT SEEM TO INDICATE ANY DEVICE | | | TO TURN ON OR OFF LIGHTING AUTOMATICALLY. ( AREA | | | REDLINED) | | | PLEASE SEE RESPONSE AND CONVERSATION ON PHONE WITH MR. | | | JIMMY EDWARDS WAS THAT METHOD "B" WAS GOING TO BE USED | | | AND SUBMITTED. | | | PLEASE THE ORIGINAL ENERGY CALCULATIONS DATED 5-1-06 | | | ARE STILL BEING ATTACHED INDICATING A METHOD "A". | | | PLEASE SEE THIS DOES NOT COMPLY OR PROVIDE THE | | | INFORMATION AS NEEDED AND NOTED IN PREVIOUS REVIEWS. | | | PLEASE SEE THIS METHOD AS ATTACHED STILL INDICATES ALL | | | LIGHTING BEING MANUALLY CONTROLLED WHICH BY PLANS AND | | | DESIGN IS NOT THE CASE. | | | PLEASE SEE 13-415.1.ABC.1.1, AND 13-415.2.ABC.1 FOR | | | MINIMUM CALCULATIONS FOR LIGHTING POWER DENSITIES. | | | | | | ** NEW NOTES NOTED BY THIS REVIEWER WHICH DO NOT APPLY | | | TO CHANE ENGINEERING** | | | | | | 1) NOTE: PLEASE SEE MISSING TITLE BLOCKS FROM LANDSCAPE | | | SHEETS WHICH ARE SIGNED, AND SEALED BY A LANDSCAPE | | | ARCHITECT. PLEASE SEE FLORIDA ADMINISTRATIVE CODE | | | 61G1-16.004 AND FS 481.219 | | | | | | 2) NOTE: PLEASE SEE MISSING INFORMATION REQUIRED ON | | | TITLE BLOCKS FOR THE CIVIL ENGINEERING/SITE SHEETS. | | | PLEASE SEE MISSING PRINTED NAME AND LICENSE NUMBER. | | | | | | ** THESE TWO COMMENTS ARE REQUIRED TO BE DONE WHETHER | | | OR NOT COMMENT IS MADE BY ANY OTHER TRADE. | | | PLEASE KNOW SAID INFORMATION MAY BE STAMPED, LABELED, | | | OR HANDWRITTEN ON SHEETS AS LONG AS THERE ARE NOT | | | COMMENTS WHICH WILL REQUIRE SHEETS TO BE CHANGED. | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2006-10-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-10-15 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-10-15 |
Time |
12:35 |
Sent To |
|
|
| Notes |
| 2006-10-15 14:16:59 | ********* UNSAT2ND REVIEW *********** | | | | | | | | | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW WHICH ARE | | | STILL IN NEED OF ADDRESSING ALONG WITH NEW NOTES DUE TO | | | INFORMATION NOW SHOWN OR CHANGES MADE. | | | | | | | | | 1) NOTE: NO, SAME NOTE . | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE THE FOLLOWING | | | MININUM CODES SHALL BE SPECIFIED ON THE | | | PLANS FOR DESIGN AND BUILDING. | | | NFPA-70 2002, NFPA-101 2003, NFPA-72 | | | 2002. | | | | | | 2) NOTE:NO, COULD NOT LOCATE ANY INFORMATION ON | | | SUMMARY OR BREAK DOWN OFLOADS AND HOW THEY HAVE BEEN | | | FIGURED OR DERIVED? PLEASE ALSO SEE COMMENT FOR SIGN | | | CIRCUIT. PLEASE SEE BOTH ARE BEING SHOWN ON THE SAME | | | CIRCUIT NOW ON PANEL "L" WHICH PANEL "M" STILL SHOWS | | | THE CIRCUITING WHICH WAS DONE ON PREVIOUS PLANS( M-15) | | | ?? PLEASE SEE ALL NOTES PERTAINIGN TO THESE ADJUST AND | | | CORRELATE. | | | | | | **PREVIOUS REVIEW NOTE ** | | | PLEASE SEE THE SHOW WINDOW | | | REQUIRED DEDICATED CIRCUITS MAY NOT BE | | | SHARED AS/OR WITH THE REQUIRED SIGN | | | CIRCUITS. PLEASE SHOW LOADS PER 220.12A | | | ON CALCS FOR "WATTS" PER LINEAR FT. | | | | | | 3) NOTE:NO, PLEASE SEE NOTE ABOVE, ALSO PLEASE SEE | | | 600.5, AS PERVIOUSLY NOTED FOR LOCATION(S) OF REQUIRED | | | CIRCUIT. PLEASE SEE THE SAME 600.5 WHICH REFERENCES | | | 220.3B6 FOR MIN VA REQUIRED FOR THIS. PLEASE SEE PANEL | | | SCHEDULE EITHER "M" OR "L" EACH SHOWS A 4A LOAD?? HOW | | | IS THIS POSSIBLE WHEN THE MIN VA IS REQUIRED TO BE | | | FIGURED AT 1200VA.PLEASE ADJUST. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE THE REQUIRED | | | DEDICATED SIGN CIRCUITS SHALL BE SIZED | | | AND CIRCUITED PER 600.5 WHETHER OR NOT | | | AN ELECTRICAL TYPE SIGN WILL BE | | | INSTALLED. | | | | | | 4) NOTE: ? SEE NEW NOTES AS THIS NOTE WAS ADDED ON | | | PANEL SCHEDULE FOR "PLUGMOLD"?? | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE 220.12B, TRACK LTS | | | SHALL BE SHOWN IN CALCULATIONS . | | | | | | 5) NOTE:NO, SAME NOTE, ALONG WIHT NOTES ABOVE ABOUT | | | SIGNS, SHOW WINDOWS ETC, PLEASE PROVIDE A LOAD SUMMARY | | | ON HOW LOADS WERE DERIVED. SHOWING A CONNECTED AMERAGE | | | LOAD DOES NOTPROVIDE INFORMATION. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE THAT LOAD | | | CALCULATIONS SHALL BE SHOWN. RECEPTS | | | WHEN KNOWN ARE TO BE SHOWN, LIGHTING | | | LOADS SHALL BE SHOWN AND IF CONTINUOUS | | | THESE SHALL BE IDENTIFIED WITH 125% FIG. | | | PLEASE SEE CALCUALTIONS WILL BE REQUIRED | | | EVEN IF NO DERATINGS ARE GOING TO BE | | | DONE. PLEASE SEE THE LOADS ON PANELS NOW | | | ARE NOT COMPLETE AT THIS TIME. | | | 220.3,220.10,220.11,220.13,, | | | 215.3,230.42 ETC. | | | 215.5 | | | | | | 6) NOTE:NO, PLEASE SEE THESE ARE STILL BEING SHOWN | | | WITH TWO SEPARATE LOADS, WHERE THE MECHANICAL PLANS | | | STILL INDICATE BOTH OF THESE BEING SAME?? | | | PLEASE ADJUST. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE CORRELATE LOADS AND OCP | | | FOR ALL AHU'S. PLEASE SEE UNIT 1 AND 2 | | | ARE THE SAME , YET THE AMPERAGE IS NOT | | | THE SAME AND THE OCP IS DIFFERENT? | | | PLEASE SEE MECHANICAL PLANS AND | | | CORRELATE. | | | PLEASE BE SURE TO SEE 424.3B FOR 125% | | | OCP MIN. | | | PLEASE ADJUST AWG PER 310.16 | | | | | | 7) NOTE:NO, THIS IS UNCLEAR AT THIS TIME AS THE | | | STAIRS AND MEZZ LEVELS ARE UNCLEAR IF THEY EVEN EXIST | | | ANYMORE AS SHEETS ARE STILL BEING SUBMITTED SHOWING A | | | MEZZ LEVEL, YET NO LIGHTING OR STAIRS ARE SHOWN?? | | | PLEASE ALSO SEE NEW NOTES. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SHOW THE NORMAL AND | | | EMERGENCY FT CANDLES FOR STAIRS. PLEASE | | | SEE NFPA-101 2003, 708.1.3,709.2.2 WHICH | | | NOW REQUIRES 10FT CANDLES (108LUX) UNDER | | | NORMAL AND 10.8 FT CANDLES (10.8) UNDER | | | EM CONDITIONS. | | | PLEASE SHOW THE PHOTO-METRICS FOR THE | | | EGRESS PATHS TO THE PUBLIC RIGHT OF WAY | | | AS REQUIRED. | | | | | | 8) NOTE: ? NO, ?PANEL HAS NOT MOVED AND ROOM | | | DESIGNATION HAS BEEN REMOVED FROM PLANS ALL TOGETHER?? | | | THE ROOM SHALL BE IDENTIFIED ON PLANS FOR USE AND | | | OCCUPANCY. IF INDEED THIS IS GOING TO BE USED AS A | | | STORAGE ROOM, PLEASE RELOCATE PANELS AS THIS IS A LIFE | | | SAFETY ISSUE AND AT THE VERY LEAST A FIRE HAZARD TO THE | | | OCCUPANTS AND PROPERTY DAMAGE POTENTIAL. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE LOCATION OF PANEL | | | "L" SHALL NOT BE LOCATED IN STORAGE | | | ROOM. | | | PLEASE RELOCATE.110.26,408.7, 240.24 | | | ETC. | | | PLEASE ALSO SHOW SECTION #2 OF PANEL "L" | | | ON PLANS. | | | | | | 9) NOTE: OK, HOWEVER DUE TO PLANS NOT BEING COMPLETE | | | FOR CLEAR REVIEW, PLEASE SEE PLANS WHICH STILL INDICATE | | | A MEZZ LEVEL IN SETS DO NOT CONTAIN SOME ITEMS | | | IDENTIFIED TO BE ON FIXTURE SCHEDULE. FIXTURE FOR | | | POSSIBLE STAIR AREA IS NTO SHOWN, PLEASE SEE OTHER | | | NOTES FOR COORDINATION. | | | | | | ** PREIVOUS REVIEW NOTE ** | | | PLEASE COMPLETE FIXTURE | | | IDENTIFICATION ON PLANS. PLEASE SEE SOME | | | ARE MISSING FIX DESIGNATIONS. | | | PLEASE ALSO SEE SOME FIXTURES ON FIX | | | SCHEDULE COULD NOT BE LOCATED ON PLANS? | | | | | | 10) NOTE: OK. | | | | | | 11) NOTE: OK, CIRCUITING WAS COMPLETED HOWEVER WILL BE | | | REVISED BASED ON OTHER COMMENTS. | | | | | | 12) NOTE: OK, HOWEVER SEE ONE NEW NOTE AS "FYI". | | | | | | 13) NOTE: OK, HOWEVER PROVIDE A GROUNDING ELECTRODE | | | ATTACHMENT DETAIL FOR A NEW BUILDING? PLEASE KNOW IT | | | SEEMS THIS BUILDING IS EXISTING AND TO SHOW AN | | | ATTACHMENT TO THE FOOTER STEELMAY NOT BE DESIRED. | | | PLEASE KNOW ON AN EXISTING OLDER BLDG WHERE THE FOOTER | | | STEEL IS NOT AVAILABLE, IT IS NOT REQUIRED TO CHIP | | | OUT/EXPOSE THE EXISTING FOOTER STEEL (IF THERE IS ONE) | | | AS THIS MAY AFFECT THE STRUCTURAL INTEGRITY OF THE | | | EXSITING FOOTER AND HAVING TO SEAL THIS AREA BACKSO | | | THAT MOISTURE AND SPALDING DOES NOT OCCUR. PLEASE ONLY | | | INCLUDETHE LOCATIONS WHICH WILL BE AVAILABLE ETC PER | | | 250.50 2002 NEC. CODES ARE NOTE REQUIRED TO BE ON | | | DETAIL HOWEVER MAY. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SHOW THE LOCATION OF | | | THE ATTACHMENT OF THE GROUNDING | | | ELECTRODE CONDUCTOR. | | | 250.24B,250.6,215.5 | | | | | | 14) NOTE: OK, HOWEVER SEE 240.12 FOR SELECTIVE | | | COORDINATION FOR DESIGNER TO VERIFY. THISNOTE WAS FOR | | | AIC RATINGS.110.9 AND IS OK. | | | | | | | | | 15) NOTE: OK. | | | | | | 16) NOTE:NO/OK, OCCUPANT DEVICES HAVE BEEN USED AND | | | ADDED TO ALMOST ALL LOCATIONS, HOWEVER AS THE MEZZ | | | LEVEL IS NOT CLEAR THIS CAN NOT BE REVIEWED. PLEASE | | | ALSO SEE NO LIGHTING POWER DENSITIES WERE LOCATED FOR | | | MAX WATTAGE ALLOWED . 13-415.2.ABC.1 PLEASE ALSO | | | SPECIFY THE MAX TIMES ON DEVICES CHOSEN. (TIMER TYPE | | | 4HRS MAX, OS TYPE 30 MINS MAX). | | | PLEASE SEE CIRCUITING OF EM/ EXT LTS WILL BE AFFECT AS | | | SHOWN. MUST BE WIRED INTO BRANCH CIRCUIT AHEAD OF ANY | | | CONTROL DEVICE. PLEASE INDICATE. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE THIS NOTE IS VERY | | | IMPORTANT AND WILL REQUIRE MANY CHANGES | | | IN THE ELECTRICAL LIGHTING SYSTEM AS | | | SHOWN. | | | PLEASE SEE FBC 2004 CHAPTER 13. PLEASE | | | SEE THIS IS NEW IN THE 2004 CODE AND | | | MANY CHANGES WERE MADE TO THE ELECTRICAL | | | SECTION FROM THE 2001 FBC. THESE CHANGES | | | BECAME FEDERALLY MANDATED IN JULY 04 FOR | | | EACH STATE TO ADOPT THESE MIN | | | REQUIREMENTS BY THE NEXT CODE CYCLE. | | | | | | **PLEASE SEE 13-101.1.3 THE ENERGY CODE | | | COMPLIANCE FORM SHALL BE "C". | | | PLEASE SEE 13-413.1.ABC.1, A WORST CASE | | | VOLTAGE DROP CALCULATION WILL BE | | | REQUIRED TO BE SHOWN ON PLANS FOR | | | FEEDERS AND BRANCH CIRCUITS. | | | PLEASE SEE 13-415.1.ABC.1.1, | | | 13-415.1.ABC.1.2, 13-415.1.ABC.1.3, ALL | | | OF WHICH REQUUIRES MANY ITEMS ON PLANS | | | TO BE CHANGED. PLEASE INDICATE THE TYPE | | | OF SYSTEM WHICH WILL BE USED, | | | SCHEDULING, THE LOCATIONS OF THE | | | REQUIRED OVER RIDE SWITCHES, THE | | | LOCATIONS OF THE OCCUPANCY SENSORS(IF | | | USED) AND PLEASE SEE THE REQUIREMENTS OF | | | THE MULTIPLE FLOORS. ETC | | | PLEASE BE SURE TO INCLUDE DEVICES FOR | | | SEPARATE SPACES. | | | | | | | | | 17) NOTE: OK. | | | | | | | | | 18) NOTE:NO, THIS WAS NOT DONE,. | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | **PREVIOUS REVIEW NOTE ** | | | PLEASE KNOW, BEFORE | | | RESUBMITTING PLANS, PLEASE BE SURE TO | | | COMPLETELY REMOVE ANY OLD/VOIDED SHEETS | | | FROM SETS AND ONLY INSERT THE "NEW" | | | SHEETS INTO SETS FOR REVIEW AND | | | STAMPING. THIS WILL HELP TO ALLEAVAITE | | | DELAYS IN REVIEW OF SAID PROJECT. ONE | | | COPY OF THE OLD/VOIDED REMOVED SHEETS | | | SHOULD ACCOMPANY THE NEW SETS FOR | | | REFERENCE. | | | | | | ** NEW NOTES ** | | | | | | 19) NOTE: PLEASE SEE ALL NOTES ABOVE WITH REPSETC TO | | | MEZZ LEVEL AND COMPLETE PLANS ACCORDINGLY. | | | | | | 20) NOTE: ** THIS IS ONLY A NOTE: PLEASE SEE A 1/0 | | | EQUIPMENT GROUNDING CONDUCTOR IS BEING SHOWN FROM MAIN | | | TO PANEL "L". PLEASE SEE 250.122 FOR MIN REQUIRED. SIZE | | | IS MUCH LARGER THAN NEEDED, HOWEVER MAY BE USED. PLEASE | | | KNOW, IF SHOWN ON PLANS LIKE THIS, THEN THE 1/0 WILL BE | | | REQUIRED OT BE INSTALLED. THIS IS FOR INFORMATIONAL | | | PURPOSE ONLY AND DOES NOT NEED TO BE REVISED. | | | | | | 21) NOTE: PLEASE SEE A NOTE WAS ADDED TO PANEL WITH A | | | DOUBLE "* *" NEXT TO CIRCUIT FOR PLUGMOLD WHICH NOTES | | | LOADS ALL FIGURED PER 220.12B AND 150WATTS PER 2'?? | | | PLEASE SEE 220.12B IS FOR TRACK LIGHTING AND MAY NOT BE | | | USED FOR PLUGMOLD. PLEASE SEE PREVIOUS NOTE FOR LOAD | | | CALCULATIONS AND REVISE. | | | | | | 22) NOTE: PLEASE SEE FOYER/ENTRANCE AREA SHALL CONTAIN | | | AN EM LT AS THERE DOORS FROM OTHER AREAS WHICH DO | | | SUPPLY THE NEEDED ILLUMINATION FOR REQUIRED EGRESS. | | | PLEASE SEE NFPA-101 7.8, 7.9 | | | | | | 23) NOTE: PLEASE SEE COPY OF FLORIDA STATUES ATTACHED | | | 553.80(2)(B) WITH RESPECTTO REPEAT COMMENTS FOR CODE | | | COMPLIANCE. | | | | | | 24) NOTE: PLEASE SEE 422.17 FOR WHAT APPEARS TO BE A | | | WATER HEATER IN A STORAGE CLOSET.PLEASE RELOCATE. | | | | | | | | | PLEASE SEE ANY COMMENTS FROM OTHER | | | TRADES WHICH MAY AFFECT ELECTRICAL | | | PLANS/ DESIGN. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-06-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-06-10 |
Time |
13:55 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-06-10 |
Time |
12:39 |
Sent To |
|
|
| Notes |
| 2006-06-10 00:00:00 | IN ELEC | | | ********* UNSAT *********** | | | | | | 1) NOTE: PLEASE SEE THE FOLLOWING | | | MININUM CODES SHALL BE SPECIFIED ON THE | | | PLANS FOR DESIGN AND BUILDING. | | | NFPA-70 2002, NFPA-101 2003, NFPA-72 | | | 2002. | | | | | | 2) NOTE: PLEASE SEE THE SHOW WINDOW | | | REQUIRED DEDICATED CIRCUITS MAY NOT BE | | | SHARED AS/OR WITH THE REQUIRED SIGN | | | CIRCUITS. PLEASE SHOW LOADS PER 220.12A | | | ON CALCS FOR "WATTS" PER LINEAR FT. | | | | | | 3) NOTE: PLEASE SEE THE REQUIRED | | | DEDICATED SIGN CIRCUITS SHALL BE SIZED | | | AND CIRCUITED PER 600.5 WHETHER OR NOT | | | AN ELECTRICAL TYPE SIGN WILL BE | | | INSTALLED. | | | | | | 4) NOTE: PLEASE SEE 220.12B, TRACK LTS | | | SHALL BE SHOWN IN CALCULATIONS . | | | | | | 5) NOTE: PLEASE SEE THAT LOAD | | | CALCULATIONS SHALL BE SHOWN. RECEPTS | | | WHEN KNOWN ARE TO BE SHOWN, LIGHTING | | | LOADS SHALL BE SHOWN AND IF CONTINUOUS | | | THESE SHALL BE IDENTIFIED WITH 125% FIG. | | | PLEASE SEE CALCUALTIONS WILL BE REQUIRED | | | EVEN IF NO DERATINGS ARE GOING TO BE | | | DONE. PLEASE SEE THE LOADS ON PANELS NOW | | | ARE NOT COMPLETE AT THIS TIME. | | | 220.3,220.10,220.11,220.13,, | | | 215.3,230.42 ETC. | | | 215.5 | | | | | | 6) NOTE: PLEASE CORRELATE LOADS AND OCP | | | FOR ALL AHU'S. PLEASE SEE UNIT 1 AND 2 | | | ARE THE SAME , YET THE AMPERAGE IS NOT | | | THE SAME AND THE OCP IS DIFFERENT? | | | PLEASE SEE MECHANICAL PLANS AND | | | CORRELATE. | | | PLEASE BE SURE TO SEE 424.3B FOR 125% | | | OCP MIN. | | | PLEASE ADJUST AWG PER 310.16 | | | | | | 7) NOTE: PLEASE SHOW THE NORMAL AND | | | EMERGENCY FT CANDLES FOR STAIRS. PLEASE | | | SEE NFPA-101 2003, 708.1.3,709.2.2 WHICH | | | NOW REQUIRES 10FT CANDLES (108LUX) UNDER | | | NORMAL AND 10.8 FT CANDLES (10.8) UNDER | | | EM CONDITIONS. | | | PLEASE SHOW THE PHOTO-METRICS FOR THE | | | EGRESS PATHS TO THE PUBLIC RIGHT OF WAY | | | AS REQUIRED. | | | | | | 8) NOTE: PLEASE SEE LOCATION OF PANEL | | | "L" SHALL NOT BE LOCATED IN STORAGE | | | ROOM. | | | PLEASE RELOCATE.110.26,408.7, 240.24 | | | ETC. | | | PLEASE ALSO SHOW SECTION #2 OF PANEL "L" | | | ON PLANS. | | | | | | 9) NOTE: PLEASE COMPLETE FIXTURE | | | IDENTIFICATION ON PLANS. PLEASE SEE SOME | | | ARE MISSING FIX DESIGNATIONS. | | | PLEASE ALSO SEE SOME FIXTURES ON FIX | | | SCHEDULE COULD NOT BE LOCATED ON PLANS? | | | | | | 10) NOTE: PLEASE IDENTIFY ALL FIXTURES | | | WHICH ARE EM TYPE, WITH THE REQUIRED | | | NOTED BATTERY BACK UP. | | | 215.5 | | | | | | 11) NOTE: PLEASE COMPLETE ALL CIRCUITING | | | ON PLANS. PLEASE BE SURE TO SEE 700.12E | | | FOR EM/EXT LTS WHICH ARE REQUIRED TO BE | | | CIRCUITED TO THE NORMAL BRANCH CIRCUIT | | | IN THE AREA IN WHICH THESE FIXTURES ARE | | | LOCATED. | | | | | | 12) NOTE: PLEASE COMPLETE RISER DIAGRAM. | | | PLEASE INCLUDE ALL SEC'S ON RISER FROM | | | METER TO GUTTER AND FROM GUTTER TO EACH | | | MAIN(S). | | | 310.16,215.5 | | | | | | 13) NOTE: PLEASE SHOW THE LOCATION OF | | | THE ATTACHMENT OF THE GROUNDING | | | ELECTRODE CONDUCTOR. | | | 250.24B,250.6,215.5 | | | | | | 14) NOTE: PLEASE INDICATE THE AIC | | | RATINGS FOR ALL SERVICE EQUIPMENT PER | | | 110.9, 215.5 | | | THIS IS SHOWN FOR PANELS, BUT NOT FOR | | | MAINS?? | | | | | | 15) NOTE: PLEASE COMPLETE PANEL SCHEDULE | | | FOR ALL CIRCUITS. PLEASE KNOW, THE AREA, | | | ROOM, IDENTIFICATION OF EACH CIRCUIT IS | | | REQUIRED. IE: CONFERENCE RM RECEPTS, | | | OFFICE #2 RECEPTS, BREAK RM RECEPTS,, | | | ETC ETC. | | | PLEASE KNOW, GENERAL "RECEPTS" OR | | | "LIGHTS" ARE NO LONGER ACCEPTABLE.408.4, | | | 215.5 | | | ** PLEASE KNOW, IT IS KNOWN AND COMMON | | | THAT THESE WILL CHANGE DURING THE | | | CONSTRUCTION AND WILL BE REQUIED TO BE | | | REVISED ALONG WITH ANY OTHER CHANGES AT | | | A LATER DATE. THIS IS HOWEVER REQ'D AT | | | THIS TIME. PLEASE BE SURE ALL AREA AND | | | ROOM DESIGNATIONS ARE ON PLANS. | | | | | | 16) NOTE: PLEASE SEE THIS NOTE IS VERY | | | IMPORTANT AND WILL REQUIRE MANY CHANGES | | | IN THE ELECTRICAL LIGHTING SYSTEM AS | | | SHOWN. | | | PLEASE SEE FBC 2004 CHAPTER 13. PLEASE | | | SEE THIS IS NEW IN THE 2004 CODE AND | | | MANY CHANGES WERE MADE TO THE ELECTRICAL | | | SECTION FROM THE 2001 FBC. THESE CHANGES | | | BECAME FEDERALLY MANDATED IN JULY 04 FOR | | | EACH STATE TO ADOPT THESE MIN | | | REQUIREMENTS BY THE NEXT CODE CYCLE. | | | | | | **PLEASE SEE 13-101.1.3 THE ENERGY CODE | | | COMPLIANCE FORM SHALL BE "C". | | | PLEASE SEE 13-413.1.ABC.1, A WORST CASE | | | VOLTAGE DROP CALCULATION WILL BE | | | REQUIRED TO BE SHOWN ON PLANS FOR | | | FEEDERS AND BRANCH CIRCUITS. | | | PLEASE SEE 13-415.1.ABC.1.1, | | | 13-415.1.ABC.1.2, 13-415.1.ABC.1.3, ALL | | | OF WHICH REQUUIRES MANY ITEMS ON PLANS | | | TO BE CHANGED. PLEASE INDICATE THE TYPE | | | OF SYSTEM WHICH WILL BE USED, | | | SCHEDULING, THE LOCATIONS OF THE | | | REQUIRED OVER RIDE SWITCHES, THE | | | LOCATIONS OF THE OCCUPANCY SENSORS(IF | | | USED) AND PLEASE SEE THE REQUIREMENTS OF | | | THE MULTIPLE FLOORS. ETC | | | PLEASE BE SURE TO INCLUDE DEVICES FOR | | | SEPARATE SPACES. | | | | | | | | | 17) NOTE: PLEASE SEE THIS COMMENT IS NOT | | | FOR ELECTRICAL ENGINEER. | | | PLEASE SEE ALL COPIES OF PLANS DONE BY | | | AN ENGINEER IS REQUIRED TO CONTAIN AND | | | ORIGINAL SIGNATURE AND SEAL AND DATE. | | | PLEASE SEE DRAINAGE CALCUALTIONS WHICH | | | ARE "PHOTO-COPIES" OF SIGNED AND SEALED | | | SHEETS. THIS IS REQUIRED PER FAC | | | 61G15-23.002, FS 471.025 WHETHER OR NOT | | | COMMENT IS MADE BY OTHER | | | ENGINEERING/CIVIL REVIEWER. | | | | | | | | | 18) NOTE: PLEASE KNOW, BEFORE | | | RESUBMITTING PLANS, PLEASE BE SURE TO | | | COMPLETELY REMOVE ANY OLD/VOIDED SHEETS | | | FROM SETS AND ONLY INSERT THE "NEW" | | | SHEETS INTO SETS FOR REVIEW AND | | | STAMPING. THIS WILL HELP TO ALLEAVAITE | | | DELAYS IN REVIEW OF SAID PROJECT. ONE | | | COPY OF THE OLD/VOIDED REMOVED SHEETS | | | SHOULD ACCOMPANY THE NEW SETS FOR | | | REFERENCE. | | | | | | | | | PLEASE SEE ANY COMMENTS FROM OTHER | | | TRADES WHICH MAY AFFECT ELECTRICAL | | | PLANS/ DESIGN. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE NAY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
4 |
Status |
P |
Date |
2007-02-16 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2007-02-16 |
Time |
10:40 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2007-02-16 |
Time |
10:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
P |
Date |
2007-01-12 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2007-01-12 |
Time |
09:28 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2007-01-12 |
Time |
09:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
F |
Date |
2006-10-23 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2006-10-23 |
Time |
13:17 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2006-10-23 |
Time |
13:03 |
Sent To |
|
|
| Notes |
| 2006-10-23 13:17:28 | FAILED FOR FOLLOWING REASONS: | | | | | | 1 PLEASE CALCULATE THE WORST CASE EITHER 1" OVER ENTIRE | | | SITE OR 2.5" CRITERIA. EXFILTRATION TRENCH LENGTH WOULD | | | BE LOT MORE THAN YOU CALCULATED. | | | 2.PLEASE ADD IN DRAWING SET CITY OF WPB STANDARDS FOR | | | DUMPSTER ENCLOSURE, | | | SIDEWALK,DRIVEWAY,APPROACH,PARKING,HANDICAP PARKING, | | | ADA, STANDARDS. | | | 3 NEED POLLUTION PREVENTION PLAN DETAILS | | | 4 NEED UTILITY REVIEW FROM 45TH STREET | | | 5 PLEASE SHOW STORM WATER CATCH BASINS & OUTLETS AROUND | | | YOUR SITE | | | | | | PLEASE RESPOND EACH ITEM TO EXPEDITE PERMITTING | | | PROCESS. | | | | | | RASIKCHOKSHI |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2006-07-18 |
|
|
Cont ID |
|
| Sent By |
|
Date |
2006-07-18 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
2006-07-18 |
Time |
|
Sent To |
|
|
| Notes |
| 2006-07-18 00:00:00 | REVISE DRAINAGE CAL TO RETAIN 1" OF | | | RUNOFF OVER THE ENTIRE SITE. | | | PLEASE INDICATE LOCATION OF | | | EXFILTRATION TRENCH, SHOW FLOW | | | DIRECTION,ON SHEET 1 OF STORM WATER | | | MANAGEMENT, | | | ALSO, SHOW APPLICABLE RAMP/ACCESSIBLE | | | DETAIL, CITY STANDARD SHEET ATTACHED FOR | | | YOUR USE | | | | | | | | | PLEASE CALL IF YOU HAVE ANY QUESTIONS, | | | RASIK CHOKSHI 805-6723 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2007-11-05 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-11-05 |
Time |
15:44 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-11-05 |
Time |
15:37 |
Sent To |
|
|
| Notes |
| 2007-11-05 15:43:53 | *****APPROVED***** | | | | | | REVISED PLAN SHEET 20 STAMPED, INITIALED, AND DATED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
F |
Date |
2007-09-24 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-09-24 |
Time |
15:22 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-09-24 |
Time |
14:57 |
Sent To |
|
|
| Notes |
| 2007-09-24 15:03:29 | *****UNSAT***** | | | | | | REVISED PLAN SHEET 15 STAMPED, INITIALED, AND DATED; | | | HOWEVER REVISED PLAN SHEET 20 (WHICH REPLACES SHEET 6) | | | DOES NOT DISPLAY/SHOW THE NUMERICAL ADDRESS.AS PER | | | WEST PALM BEACH CODE, BUILDING ADDRESS NUMBERS SHALL BE | | | NO LESS THAN 6" IN HEIGHT AND 1" IN WIDTH. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2007-01-08 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-01-08 |
Time |
17:54 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-01-08 |
Time |
17:54 |
Sent To |
|
|
| Notes |
| 2007-01-08 18:04:43 | *** AS PER WEST PALM BEACH CODE, BUILDING ADDRESS | | | NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND 1" IN | | | WIDTH |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2006-10-25 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2006-10-25 |
Time |
07:35 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2006-10-25 |
Time |
07:35 |
Sent To |
|
|
| Notes |
| 2006-10-25 07:39:04 | 1) EXIT SIGNAGE AND EMERGENCY LIGHTING NEEDED FOR | | | MEZZANINE AREA. | | | 2) PORTABLE FIRE EXTINGUISHERS THAT ARE CURRENTLY | | | SERVICE TAGGED AND MOUNTED SHALL BE PROVIDED | | | THROUGHOUT. | | | 3) SUBJECT TO FIELD INSPECTION AND APPROVAL. | | | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION OFFICER 804-4709 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2006-06-16 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2006-06-16 |
Time |
11:00 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2006-10-25 |
Time |
07:34 |
Sent To |
|
|
| Notes |
| 2006-06-16 00:00:00 | 1. DEMOLITION, RENOVATION, AND | | | CONSTRUCTION TO COMPLY WITH NFPA 241. | | | | | | 2. DEBRIS SHALL BE REMOVED FROM THE SITE | | | DAILY. | | | | | | 3. GASOLINE POWERED DEMOLITION EQUIPMENT | | | SHALL NOT BE USED WITHOUT PROPER | | | VENTILATION TO PREVENT CARBON MONOXIDE | | | BUILD-UP OF VAPORS. | | | | | | 4. ADDITIONAL EXIT SIGNS APPEAR TO BE | | | NEEDED TO DIRECT PERSONS TO EXITS THAT | | | ARE BEYOND CORNERS AND ROOMS. | | | | | | 5. NEW STAIRS UP SHALL MEET MINIMUM CODE | | | REQUIREMENTS. ANY HANDRAILS AND | | | GUARDRAILS SHALL COMPLY WITH THE | | | PRESCRIPTIVE STRENGTH REQUIREMENTS. | | | | | | 6. THE MEZZANINE IS TO BE USED FOR WHAT | | | PURPOSES. PLEASE INDICATE THE PURPOSE ON | | | THE PLANS. | | | | | | 7. PLEASE REVIEW DOORS SWINGS FOR | | | RESTROOMS THAT OPEN ONTO THE CORRIDOR | | | PROVIDING ACCESS TO THEM. | | | | | | 8. ENSURE THAT THE EXISTING ADDRESS | | | DISPLAYEED ON PAGE 6A MEETS MINIMUM CODE | | | REQUIREMENTS OF AT LEAST 6" HIGH WITH | | | THE PROPER WIDTH STROKE. | | | | | | 9. FLOOR PLANS DOES NOT ILLUSTRATE ANY | | | NEW OR EXISTING PORTABLE FIRE | | | EXTINGUISHERS. PLEASE DISPLAY. | | | | | | 10. PLEASE INDICATE INTERIOR FINISH FOR | | | WALLS AND CEILINGS. | | | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | | OFFICER | | | 804-4709 |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2006-05-16 00:00:00 | OK PER F MITNER NO FEE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2007-12-10 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-12-10 |
Time |
09:27 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-12-10 |
Time |
09:27 |
Sent To |
|
|
| Notes |
| 2007-12-10 09:28:08 | TO "COMM" BD#16 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2007-10-03 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-10-03 |
Time |
17:36 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-10-03 |
Time |
17:36 |
Sent To |
|
|
| Notes |
| 2007-10-25 15:05:16 | TO "COMM" BD#18 | | 2007-10-03 17:37:08 | WAITING FOR "COMM" BD-REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2007-08-08 |
|
|
Cont ID |
|
| Sent By |
mmiller |
Date |
2007-08-08 |
Time |
18:55 |
Rev Time |
0.00 |
| Received By |
mmiller |
Date |
2007-08-08 |
Time |
18:55 |
Sent To |
|
|
| Notes |
| 2007-09-07 16:02:10 | TO "COMM" BD#29 | | 2007-08-08 18:55:45 | WAITING FOR COMMERCIAL BOARD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2007-03-26 |
|
|
Cont ID |
|
| Sent By |
mmiller |
Date |
2007-03-26 |
Time |
18:43 |
Rev Time |
0.00 |
| Received By |
mmiller |
Date |
2007-03-26 |
Time |
18:41 |
Sent To |
|
|
| Notes |
| 2007-03-26 18:43:41 | SENT TO ZONING MMILLER |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-02-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-02-06 |
Time |
13:44 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-02-06 |
Time |
13:44 |
Sent To |
|
|
| Notes |
| 2007-02-13 14:40:43 | TO "COMM" BD#57 | | 2007-02-06 13:44:18 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
|
Date |
2006-11-29 |
|
|
Cont ID |
|
| Sent By |
mmiller |
Date |
2006-11-29 |
Time |
19:40 |
Rev Time |
0.00 |
| Received By |
mmiller |
Date |
2006-11-29 |
Time |
19:40 |
Sent To |
|
|
| Notes |
| 2006-12-13 14:47:53 | TO "COMM" BD#23 | | 2006-11-29 19:40:49 | WAITING FOR COMMERCIAL BOARD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-09-22 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-09-22 |
Time |
10:59 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-09-22 |
Time |
10:59 |
Sent To |
|
|
| Notes |
| 2006-10-11 14:52:38 | TO "COMM" BD#60 | | 2006-09-22 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-07-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-07-27 |
Time |
16:58 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-05-18 |
Time |
15:48 |
Sent To |
|
|
| Notes |
| 2006-06-01 00:00:00 | TO "COMM" BD#11 | | 2006-05-18 00:00:00 | **THIS IS NOT A "BOB" APPLICATION PER | | | "RBROWN" | | | WAITING FOR "COMM" BD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2007-11-01 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-11-01 |
Time |
08:10 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2007-11-01 |
Time |
08:10 |
Sent To |
|
|
| Notes |
| 2007-11-01 08:11:26 | REVISED MECH. PLANS PAGE 17 AND 18. REVIEWED AND | | | APPROVED 9-11-07. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2006-12-21 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-12-21 |
Time |
14:34 |
Rev Time |
0.25 |
| Received By |
tgordon |
Date |
2006-12-21 |
Time |
14:34 |
Sent To |
|
|
| Notes |
| 2006-12-17 14:53:43 | NEW SHEETS IN SETS |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2006-10-12 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-10-12 |
Time |
09:38 |
Rev Time |
0.45 |
| Received By |
tgordon |
Date |
2006-10-12 |
Time |
09:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2006-06-23 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-06-23 |
Time |
13:35 |
Rev Time |
0.45 |
| Received By |
tgordon |
Date |
2006-06-23 |
Time |
13:35 |
Sent To |
|
|
| Notes |
| 2006-06-23 00:00:00 | *** DENIED *** | | | 1) AHU #1 SHOW SIZE OF MAIN RETURN AIR | | | DUCT TO 42"X24" R.A. GRILL IN MEZZANINE. | | | | | | 2) AHU #2 SHOW SIZE OF MAIN RETURN AIR | | | DUCT FROM AHU TO 12"X8" DUCTS. | | | | | | 3) AHU #3 SUPPLY AIR TO OFFICE CAN NOT | | | RETURN TO AHU #1, 10'X10" TRANSFER GRILL | | | DOES NOT OPEN TO AHU #3 ZONE. | | | | | | 4) A/C SUPPLY AIR DUCT AND RETURN AIR | | | TRANSFER GRILL GOING TO LOBBY ARE | | | PENETRATING A FIRE RATED WALL, AND | | | REQUIRE FIRE DAMPERS, PER 2004 FBC/M 607 | | | | | | 5) SEE BUILDING REVIEW NOTES #23 & #24. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2007-09-22 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-09-22 |
Time |
05:58 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-09-21 |
Time |
18:52 |
Sent To |
|
|
| Notes |
| 2007-09-22 05:59:11 | REVISION OK--SHT 19 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2007-01-23 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-01-23 |
Time |
17:29 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-01-23 |
Time |
17:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2006-10-28 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-10-28 |
Time |
13:28 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-10-28 |
Time |
12:44 |
Sent To |
|
|
| Notes |
| 2006-10-28 14:02:03 | PAUL SCHMITZ | | | [email protected] | | | FBC 2004 PLUMBING CODE PLAN REVIEW | | | FBC2004 FUEL GAS CODEPLAN REVIEW | | | FBC 2004 CH 11, FL ACESSIBILITY CODE | | | AMENDMENTS TO THE FLORIDA BUILDING CODE | | | CHAPT.1, ADMINISTRATION, 2004 EDITION | | | | | | UNSAT | | | NEW COMMENT, SAYING WILL COMPLY, IS NOT ACCEPTABLE, | | | PROVIDE THE INFORMATIOIN ON THE PLANS. | | | | | | 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN | | | UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE | | | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE | | | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT | | | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS | | | DETERMINED BY THE BUILDING OFFICIAL (SEE ALSO SECTION | | | 106.3.5). | | | | | | | | | 1) INCLUDE NOTE BELOW ONSHT 2. DEMOLITION | | | SEC 704.5DEAD ENDS.IN THE INSTALLATION | | | OR REMOVAL OF ANY PART OF THE DRAINAGE | | | SYSTEM, DEAD ENDS SHALL BE PROHIBITED. | | | | | | 2) PROVIDE THE INFORMATION AS REQUIRED FOR EACH | | | SEPERATE OCCUPANCY, (SPACE #1,#2) | | | SHT 3. SEC 403.1MINIMUM NUMBER OF | | | PLUMBING FIXTURES SHALL BE PROVIDED FOR | | | THEOCCUPANT LOAD BASED ON TABLE 403.1 | | | | | | 3) DOOR SWINGS IN CLEAR FLOOR SPACE FOR D/F BY UNISEX | | | REST RM. | | | SHT 3.SEC 410.1 DRINKING FOUNTAIN | | | | | | 4) COMPLIED | | | SHT 3. SEC 11-4.1.3 PRIVATE TOILET ROOM(DELETED) | | | | | | 5) SHOWDIMENSIONS FOR FIXTURES OFF WALLS | | | SHT 3 SEC 11-4.22, UNISEX TOILET | | | ROOM, EACH PUBLIC AND COMMON USE TOILET | | | ROOM SHALL COMPLY WITH SEC 11-4.1.3 | | | | | | 6) SHT 5. ROOF PLAN: COMPLIED | | | | | | 7) SHT 19 SEC 606.1 (4) FULLY OPEN VALVES, COMPLIED | | | | | | END OF COMMENTS QUESTIONS 561-805-6692 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2006-07-01 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-07-01 |
Time |
10:38 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-07-01 |
Time |
10:26 |
Sent To |
|
|
| Notes |
| 2006-07-01 00:00:00 | PAUL SCHMITZ | | | [email protected] | | | FBC 2004 PLUMBING CODE PLAN REVIEW | | | FBC2004 FUEL GAS CODEPLAN REVIEW | | | FBC 2004 CH 11, FL ACESSIBILITY CODE | | | AMENDMENTS TO THE FLORIDA BUILDING CODE | | | CHAPT.1, ADMINISTRATION, 2004 EDITION | | | | | | UNSAT | | | | | | 1) SHT 2. DEMOLITION | | | SEC 704.5DEAD ENDS.IN THE INSTALLATION | | | OR REMOVAL OF ANY PART OF THE DRAINAGE | | | SYSTEM, DEAD ENDS SHALL BE PROHIBITED. | | | | | | 2) SHT 3. SEC 403.1MINIMUM NUMBER OF | | | PLUMBING FIXTURES SHALL BE PROVIDED FOR | | | THEOCCUPANT LOAD BASED ON TABLE 403.1 | | | | | | 3) SHT 3.SEC 410.1 DRINKING FOUNTAIN | | | REQUIRED. BOTTLED WATER DISPENSER SHALL | | | BE PERMITTED, FOR NOT MORE THAN 50% OF | | | REQUIRED DRINKING FOUNTAINS. | | | | | | 4) SHT 3. SEC 11-4.1.3 PRIVATE TOILET | | | ROOM FOR THE OCCUPANT OF A PRIVATE | | | OFFICE, SHALL BE ADAPTABLE. | | | | | | 5) SHT 3 SEC 11-4.22, UNISEX TOILET | | | ROOM, EACH PUBLIC AND COMMON USE TOILET | | | ROOM SHALL COMPLY WITH SEC 11-4.1.3 | | | | | | 6) SHT 5. ROOF PLAN: SEC 1106 PROVIDE | | | THE CALCULATIONS FOR THE PRIMARY AND | | | SECONDARY ROOF DRAINAGE. | | | TABLE 1106.2,1106.3 AND 1106.7 | | | PROVIDE AN ISOMETRIC DRAWING ALL PIPE | | | SIZES. INCLUDE POINT OF DISPOSAL. | | | | | | 7) SHT 19 SEC 606.1 (4) FULLY OPEN | | | VALVES SHALL BE INSTALLEDON THE TOP OF | | | EVERY WATER DOWN FEED PIPE. | | | | | | END OF COMMENTS QUESTIONS 561-805-6692 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
8 |
Status |
P |
Date |
2007-12-11 |
|
|
Cont ID |
|
| Sent By |
kdfreema |
Date |
2007-12-11 |
Time |
10:46 |
Rev Time |
0.00 |
| Received By |
kdfreema |
Date |
2007-12-11 |
Time |
10:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
7 |
Status |
F |
Date |
2007-11-06 |
|
|
Cont ID |
|
| Sent By |
kdfreema |
Date |
2007-11-06 |
Time |
14:49 |
Rev Time |
0.00 |
| Received By |
kdfreema |
Date |
2007-11-06 |
Time |
14:49 |
Sent To |
|
|
| Notes |
| 2007-11-06 14:50:25 | ***FAILED*** | | | | | | PLEASE RECONFIGURE PARKING CONFIGURATION AS DISCUSSED | | | 11/6/07. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
6 |
Status |
F |
Date |
2007-09-25 |
|
|
Cont ID |
|
| Sent By |
kdfreema |
Date |
2007-09-25 |
Time |
09:38 |
Rev Time |
0.00 |
| Received By |
kdfreema |
Date |
2007-09-19 |
Time |
13:12 |
Sent To |
|
|
| Notes |
| 2007-09-19 13:12:57 | ***FAILED*** | | | | | | 1. THE DUMPSTER ENCLOSURE SHALL REMAIN. SECTION 94-444 | | | OF THE ZONING AND LAND DEVELOPMENT REGULATIONS REQUIRES | | | GARBAGE AND TRASH RECEPTACLES TO BE SCREENED. | | | | | | 2. PLEASE UPDATE THE SITE DATA TABLE TO REFLECT THE | | | CHANGES IN SCOPE OF WORK. | | | | | | 3. PLEASE CLARIFY THE SITUATION WITH THE HANDICAP | | | PARKING. THE AREA WHERE THE HANDICAP PARKING SPACES ARE | | | CURRENTLY LOCATED IS SLATED TO BECOME LANDSCAPING. | | | WHERE ARE THESE SPACES BEING MOVED? | | | | | | 4. AS THE SPACES ON THE SOUTH SIDE OF THE BUILDING ARE | | | BEING REMOVED, THEY MUST BE ACCOUNTED FOR ELSEWHERE ON | | | THE PROPERTY. | | | | | | 5. PLEASE SUBMIT A REVISED LANDSCAPE PLAN REFLECTING | | | THE CHANGES IN THE SCOPE OF WORK. PLEASE NOTE AS THE | | | PERMIT VALUE REMAINS IN EXCESS OF 50% OF THE VALUE OF | | | THE STRUCTURE, THE LANDSCAPING MUST BE BROUGHT UP TO | | | CODE. | | | | | | PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1435 | | | OR [email protected] WITH QUESTIONS. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
5 |
Status |
P |
Date |
2007-03-27 |
|
|
Cont ID |
|
| Sent By |
kdfreema |
Date |
2007-03-27 |
Time |
08:56 |
Rev Time |
0.00 |
| Received By |
kdfreema |
Date |
2007-03-27 |
Time |
08:56 |
Sent To |
|
|
| Notes |
| 2007-03-27 09:00:16 | PROVISO: PARKING DETAIL SHOWN ON SITE PLAN SHALL | | | PREVAIL OVER PARKING DETAILS SHOWN ON THE CIVIL | | | ENGINEERING PLANS. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
F |
Date |
2007-02-23 |
|
|
Cont ID |
|
| Sent By |
kdfreema |
Date |
2007-02-23 |
Time |
10:24 |
Rev Time |
0.00 |
| Received By |
kdfreema |
Date |
2007-02-23 |
Time |
10:24 |
Sent To |
|
|
| Notes |
| 2007-02-23 10:25:11 | **FAILED** | | | | | | 1) THE PERMIT DOCUMENTATION FROM FDOT MAKES NO MENTION | | | OF ON-STREET PARKING SPACES, ADDITIONALLY; THE PLANS | | | STAMPED BY FDOT DO NOT SHOW THE PROPOSED PARKING | | | SPACES. WRITTEN PERMISSION MUST BE PROVIDED FROM FDOT | | | TO ALLOW THE ON-STREET PARKING SPACES. | | | | | | 2) THE PERIMETER LANDSCAPE REQUIREMENT IS NOT MET. ALL | | | PERIMETER TREES MUST BE PLANTED WITHIN 5 FEET OF THE | | | PROPERTY LINE TO SATISFY THIS REQUIREMENT. | | | | | | 3) A MAXIMUM OF 35% OF THE PERIMETER TREES REQUIRED MAY | | | BE SUBSTITUTED WITH PALM TREES. YOU?RE ALLOWED 7 PALMS | | | MAXIMUM AND THE PLANS SHOW 8 PALMS. | | | | | | PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1435 | | | WITH ANY QUESTIONS. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2007-01-17 |
|
|
Cont ID |
|
| Sent By |
kdfreema |
Date |
2007-01-17 |
Time |
08:46 |
Rev Time |
0.00 |
| Received By |
kdfreema |
Date |
2007-01-17 |
Time |
08:46 |
Sent To |
|
|
| Notes |
| 2007-01-17 08:51:04 | **FAILED** | | | | | | 1) REGARDING THE ON-STREET PARKING SPACES, NO APPROVAL | | | HAS BEEN PROVIDED BY EITHER THE CITY?S ENGINEERING | | | DEPARTMENT OR FDOT. THE APPLICANT MUST PROVIDE BOTH IN | | | WRITING AT THE TIME OF RESUBMISSION TO SATISFY THIS | | | REQUIREMENT. | | | | | | 2) ALL IMPROVEMENTS SHOWN ON THE SITE PLAN SHALL BE | | | SHOWN ON THE LANDSCAPE PLAN. | | | | | | 3) A HEDGE MUST BE PLANTED ALONG THE EASTERN PROPERTY | | | BOUNDARY. BOTH A WALL (WHICH CURRENTLY EXISTS) AND A | | | HEDGE ARE REQUIRED ALONG THAT BOUNDARY. | | | | | | 4) THE PERIMETER LANDSCAPE REQUIREMENT IS NOT MET. TO | | | COUNT TOWARD MEETING THE REQUIREMENT, THE TREES MUST BE | | | PLANTED WITHIN THE 5 FOOT LANDSCAPE BUFFER. | | | | | | 5) THE PERIMETER LANDSCAPE BUFFER MUST CONTAIN EITHER | | | SHADE TREES OR FLOWERING TREES. THE FOXTAIL PALMS SHOWN | | | ON THE PLAN DO NOT SATISFY THIS REQUIREMENT. | | | | | | 6) A MAXIMUM OF 35% OF THE PERIMETER TREES REQUIRED MAY | | | BE SUBSTITUTED WITH PALM TREES. PLEASE REFER TO SECTION | | | 94-442(C) FOR MORE DETAILS. | | | | | | 7) PLEASE PROVIDE A DATA TABLE ON THE LANDSCAPE PLAN | | | SHOWING PERVIOUS/IMPERVIOUS AREAS AS WELL AS OPEN SPACE | | | SQUARE FOOTAGE. PLEASE PROVIDE AN ADDITIONAL TABLE | | | SHOWING HOW THE PLANTS PROVIDED COMPARE TO WHAT IS | | | REQUIRED BY CODE. PLEASE SEE SECTION 94-448(D)(2) FOR | | | MORE INFORMATION RELATING TO THE ITEMS REQUIRED TO BE | | | SHOWN ON A LANDSCAPE PLAN. | | | | | | 8) SOME OF THE PLANTS PROPOSED TO NOT MEET MINIMUM | | | SIZE/HEIGHT STANDARDS. PLEASE REFER TO SECTION 94-445 | | | FOR INFORMATION ON PLANT MATERIAL STANDARDS AND | | | SPECIFICATIONS. | | | | | | 9) PLEASE SHOW POWER LINES ON LANDSCAPE PLAN. | | | | | | 10) REPLACE TWO THE WESTERN-MOST LIVE OAK TREES ALONG | | | NORTH PROPERTY LINE AND LIVE OAKS IN TERMINAL ISLANDS | | | WITH SMALLER TREES, THERE IS NOT ENOUGH ROOM FOR THEM. | | | | | | 11) PLEASE INDICATE WHICH PLANTS ARE DROUGHT TOLERANT. | | | | | | 12) FOR FOXTAILS PLEASE CLARIFY HEIGHT, PLANS SHOW 12' | | | HEIGHT AND 12' CLEAR TRUNK. | | | | | | 13) PLEASE ADJUST PLANTING DIAGRAMS TO REFLECT THOSE | | | FOUND ON THE CITY'S WEBSITE: | | | HTTP://WWW.WPB.ORG/PLAN/SUGGESTEDTREELIST.PDF | | | | | | 14) ADD THE FOLLOWING VERBIAGE TO THE LANDSCAPE PLAN: | | | LANDSCAPE INSTALLER SHALL CHECK ALL CONTAINERIZED | | | MATERIAL FOR CIRCLING ROOTS. REJECT MATERIAL OR CUT | | | ROOTS PER THE FLORIDA DEPARTMENT OF AGRICULTURE | | | APPROVED GRADES AND STANDARDS. | | | | | | PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1435 | | | WITH ANY QUESTIONS. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2006-10-31 |
|
|
Cont ID |
|
| Sent By |
kdfreema |
Date |
2006-10-31 |
Time |
15:28 |
Rev Time |
0.00 |
| Received By |
kdfreema |
Date |
2006-10-31 |
Time |
15:28 |
Sent To |
|
|
| Notes |
| 2006-10-31 15:31:58 | 1. A LANDSCAPE PLAN IS REQUIRED TO BE SUBMITTED BEFORE | | | THE ISSUANCE OF A BUILDING PERMIT. | | | | | | 2. ON-STREET PARKING SHALL BE APPROVED BY THE CITY'S | | | ENGINEERING DEPARTMENT AND FDOT. | | | | | | 3. A LETTER FROM THE CITY SANITATION DEPARTMENT MUST BE | | | PROVIDED APPROVING THE LOCATION OF THE DUMPSTER. | | | | | | 4. ALL LANDSCAPED AREAS MUST BE PROTECTED BY WHEEL | | | STOPS OR D CURB. THERE IS NOTHING SHOWN IN THE BUMPOUT | | | AREAS TO PROTECT THE LANDSCAPING FROM INTRUSION. | | | | | | 5. PLEASE REMOVE ANY OLD/VOIDED SHEETS FROM SETS AND | | | INSERT ONLY THE NEW SHEETS. ONE COPY OF THE OLD/VOIDED | | | REMOVED SHEETS SHOULD ACCOMPANY THE NEW SETS FOR | | | REFERENCE. | | | | | | PLEASE CONTACT KELLY FREEMAN, PLANNER, WITH ANY | | | QUESTIONS YOU HAVE. 822-1435 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2006-07-27 |
|
|
Cont ID |
|
| Sent By |
kdfreema |
Date |
2006-07-27 |
Time |
14:21 |
Rev Time |
0.00 |
| Received By |
kdfreema |
Date |
2006-07-27 |
Time |
14:21 |
Sent To |
|
|
| Notes |
| 2006-07-27 00:00:00 | 1810 S DIXIE HIGHWAY: | | | | | | 1. PLEASE PROVIDE A LANDSCAPE PLAN FOR | | | THE PROPERTY, A LANDSCAPE PLAN IS | | | REQUIRED AND MUST BE SIGNED AND SEALED | | | BY A REGISTERED LANDSCAPE ARCHITECT. | | | | | | 2. HOW WILL BIKE RACK BE CONFIGURED? | | | PLEASE PROVIDE DETAILS. | | | | | | | | | 3. THE THREE SPACES ON THE SOUTH SIDE OF | | | THE BUILDING MUST BE RELOCATED. BACKING | | | ONTO THE PUBLIC RIGHT-OF-WAY IS NOT | | | ALLOWED. | | | | | | 4. DUMPSTER ENCLOSURE DOES NOT MEET | | | MINIMUM DIMENSIONS. | | | | | | 5. DUMPSTER ENCLOSURES MUST BE | | | LANDSCAPED ON THREE SIDES BY SHRUBS OR | | | HEDGES PLACED AT A 2? ON-CENTER | | | INTERVAL. | | | | | | 6. A LETTER FROM THE CITY SANITATION | | | DEPARTMENT MUST BE SUPPLIED APPROVING | | | THE LOCATION OF THE DUMPSTER. | | | | | | 7. ALL LANDSCAPED AREAS MUST BE | | | PROTECTED BY WHEEL STOPS OR CONCRETE ?D? | | | CURBING. | | | | | | 8. SHOW LOADING ZONE DETAIL. THE LOADING | | | ZONE MUST BE DEMARCATED BY SIGNAGE OR | | | STRIPING. | | | | | | 9. A 5? SCREEN WALL IS REQUIRED ALONG | | | THE EAST LOT LINE ABUTTING THE | | | RESIDENTIAL USE. | | | | | | 10. IS MEZZANINE SQUARE FOOTAGE INCLUDED | | | IN THE PARKING REQUIREMENT? PLANS ARE | | | UNCLEAR IN THAT RESPECT. PARKING | | | REQUIREMENTS MUST BE CALCULATED USING | | | FINISHED SQUARE FOOTAGES. | | | | | | 11. WHEEL STOPS MUST BE 2? FROM FRONT | | | EDGE OF PARKING SPACE. | | | | | | 12. PARKING AND STRIPING DETAILS WITH | | | DIMENSIONS MUST BE SHOWN. | | | | | | 13. HANDICAP SPACE DOES NOT MEET MINIMUM | | | DIMENSIONS. | | | | | | 14. ENSURE THAT ALL REGULAR PARKING | | | SPACES MEET THE MINIMUM DIMENSIONS. | | | | | | 15. WILL PARKING LOT LIGHTING BE | | | PROVIDED? IF SO, A PHOTOMETRIC PLAN IS | | | REQUIRED. | | | | | | 16. A VICINITY MAP SHOWING THE PROPERTY | | | IN RELATION ITS SURROUNDINGS IS | | | REQUIRED. | | | | | | 17. PLEASE SHOW EASEMENTS AND THEIR | | | CLASSIFICATIONS ON THE SITE PLAN. | | | | | | 18. A DATA TABLE MUST BE PROVIDED TO | | | INCLUDE THE FOLLOWING: | | | A. EXISTING AND PROPOSED LAND USE. | | | B. TOTAL PROJECT ACREAGE. | | | C. TOTAL GROSS BUILDING SQUARE FOOTAGE. | | | D. PERCENT OF OPEN SPACE, LANDSCAPING, | | | BUILDING COVERAGE, AND IMPERMEABLE | | | SURFACE. | | | E. DENSITY AND NUMBER OF DWELLING UNITS. | | | F. PARKING COMPUTATIONS (PARKING | | | REQUIRED, PROVIDED, ETC.) | | | G. FLOOR AREA RATIO (FAR). | | | | | | 19. A MAXIMUM OF 25% OF THE BUFFER STRIP | | | ALONG THE SOUTH LOT LINE MAY BE | | | INTERRUPTED, PLANS SHOW 33% OF THE | | | BUFFER STRIP INTERRUPTED. NOTE: THE 33% | | | DOES NOT INCLUDE THE INTERRUPTION CAUSED | | | BY THE 3 PARKING SPACES WHICH MUST BE | | | RELOCATED. |
|
|
|
Account Summary | Usage Policy | Privacy Policy