Plan Review Details - Permit 06050604
Plan Review Stops For Permit 06050604
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-12-13 Cont ID  
Sent By jwitmer Date 2007-12-13 Time 09:47 Rev Time 2.22
Received By jwitmer Date 2007-12-13 Time 09:46 Sent To  
Notes
2007-12-12 13:10:16BLDG REVISIONS 9-29-07

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2007-11-08 Cont ID  
Sent By jwitmer Date 2007-11-08 Time 09:34 Rev Time  
Received By jwitmer Date 2007-11-08 Time 09:34 Sent To  
Notes
2007-11-08 14:14:51BUILDING PLAN REVIEW
 PERMIT: 06050604
 ADD: 1810 S DIXIE HWY
 CONT: BATTEN CONSTRUCTION
 TEL: (561)662-0309
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ NOV. 21 2005 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION REVIEW
 ACTION: DENIED
  
 1A) SITE PLAN, INDICATES THE DELETION OF THE
 HANDICAPPED RAMP TO SPACE # 1 AND THE NEW DOOR TO THE
 REAR OF SPACE # 1 IS ALSO NOT ON AN ACCESSIBLE ROUTE
 PLEASE SEE , 11-4.1.6(A) NO ALTERATION SHALL BE
 UNDERTAKEN WHICH DECREASES OR HAS THE EFFECT OF
 DECRESING ACCESSIBILITY OR USABILITY OF A BUILDING.
  
 1B) SITE PLAN, THE TENANT SEPERATION LINE ON THIS SHEET
 DOES NOT MATCH WITH SHEET# 3. IT APPEARS ON SHEET # 3
 TENANT SPACE # 2 HAS THE FRONT ENTRY DELETED AND THE
 INTERIOR FOYER. THE NEW ENTRY WILDEMERE AVENUE BUT THE
 SITE PLAN HAS NOT BEEN UPDATED
 TO REFLECT A NEW ENTRY OR WALKWAY FROM THE PUBLIC WAY.
 11-4.1.6(A) NO ALTERATION SHALL BE UNDERTAKEN WHICH
 DECREASES OR HAS THE EFFECT OF DECRESING ACCESSIBILITY
 OR USABILITY OF A BUILDING.
  
 1C) SITE PLAN, PLEASE UPDATE THE SITE PLAN SHOWING AN
 ACCESSIBLE ROUTE TO BOTH SPACE NUMBER 1 & 2. THE ISSUE
 NOW CREATED WITH THE REMOVAL OF THE HANDICAPPED RAMP
 AND NOT INDICATING THE ACCESSIBLE ROUTE TO SPACE NUMBER
 ONE WHERE THE NEW DOOR IS
 LOCATED IN THE REAR OF THE BUILDING IT WILL CAUSE THE
 DISABLED INDIVIDUAL TO TRAVEL BEHIND PARKED VEHICLE,
 PLEASE SEE 11-4.6.2 ACCESSIBLE PARKING SPACES SERVING A
 PARTICULAR BUILDING SHALL BE LOCATED ON THE SHOREST
 SAFELY ACCESSIBLE ROUTE TRAVELED FROM ADJACENT PARKING
 TO AN ACCESSIBLE ENTRANCE. WITH THE DELETION OF THE
 FRONT ENTRY LOBBY IT COULD BE ARGUED THAT EQUIVALENT
 FACILITATION 11-2.2 IS NOT BEING MET,
  
 2) SHEET NUMBER THREE PLEASE SHOW THE REVISION TO THE
 PLAN HIGHLIGHT WITH EITHER A CLOUD OR DELTA WHATTHE
 SCOPE OF WORK TO BE COMPLETED UNDER THIS REVISION,
 PLANS ARE UNCLEAR, EXAMPLE IF THERE IS TO BE NO TENANT
 BUILDOUT IN SPACE # 1 THEN DO NOT SHOW A
 FINISHED INTERIOR, OR IF THE FRONT ENTRY AND LOBBY ARE
 DELETED THEN REMOVE FROM THE PROJECT. 106.1.1
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE.\
  
 3)SHEET # 5 INDICATES THE REMOVAL OF ROOF DRAINS, AND
 SHEET # 10 INDICATES THE REMOVAL OF THE PARAPET, PLEASE
 SHOW HOW AND OR WHERE THE WATER WILL BE REOMVED FROM
 THE ROOF. EITHER SHOW THE SLOPE WHERE ATER WILL OVER
 FLOW THE EDGE OF THE ROOF, WHERE A GUTTER AND ROOF
 LEADERS1503.4 ROOF DRAINAGE, 1503.4.1 GUTTERS. 1503.3.6
 PROTECTION AGAINST DECAY & TERMITES. CONDENSATE LINES &
 ROOF DOWN SPOUTS SHALL DISCHARGE AT LEAST 1 FT. AWAY
 FROM THE STRUCTURE SIDEWALL, WHETHER BY UNDERGROUND
 PIPING, TAIL EXTENSIONS, OR SPLASH BLOCKS. 102.1*
 WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS OF THIS
 CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAILCOMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-09-18 Cont ID  
Sent By jwitmer Date 2007-09-18 Time 07:49 Rev Time 1.37
Received By jwitmer Date 2007-09-18 Time 07:49 Sent To  
Notes
2007-09-18 07:54:41BUILDING PLAN REVIEW
 PERMIT: 06050604
 ADD: 1810 S DIXIE HWY
 CONT: BATTEN CONSTRUCTION
 TEL: (561)820-0027
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVISIONREVIEW: 7-26-07
 ACTION: DENIED
  
  
 1) THE FLOOR PLAN AND NEW ELEVATIONS ON SHEETS 20 AND
 21 DO NOT MATCH UPPER OPENING. PLEASE REVIEW AND ON THE
 BUILDING CALCULATE THE PERCENT OF OPENINGS
 TABLE 704.8 MAXIMUM AREA OF WALL OPENINGS.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-01-16 Cont ID  
Sent By jwitmer Date 2007-01-03 Time 14:24 Rev Time 0.00
Received By jwitmer Date 2007-01-02 Time 14:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-10-25 Cont ID  
Sent By jwitmer Date 2006-10-25 Time 16:33 Rev Time 3.33
Received By jwitmer Date 2006-10-25 Time 16:33 Sent To  
Notes
2006-10-25 16:57:29PERMIT: 06050604
 ADD: 1810 S DIXIE HWY
 CONT: BATTEN CONSTRUCTION
 TEL: (561)820-0027
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) SHEET# 1 CODE DATA INDICATES A
 TYPE III BUILDING BUT NO DESIGNATION TO
 "A" OR "B".
  
 4) COMPLIED.
  
 5)2ND REQUEST, SHEET 1B INDICATES AS DEPICTED A 2" DROP
 FROM THE INTERIOR FINISH SLAB TO THE EXTERIOR OF THE
 BUILDING.
 SHEET# 1B INDICATES ELEVATIONS ON
 THE INTERIOR FINISH FLOOR OF 16.76'AND
 THE EXTERIOR ELEVATION OF 16.64'.
 11-4.3.8 CHANGES IN LEVEL.
 CHANGES IN LEVELS ALONG AN ACCESSIBLE
 ROUTE SHALL COMPLY WITH SECTION 11-4.5.2
 . IF AN ACCESSIBLE ROUTE HAS CHANGES IN
 LEVEL GREATER THAN ? INCH (13 MM), THEN
 A CURB RAMP, RAMP, ELEVATOR, OR PLATFORM
 LIFT (AS PERMITTED IN SECTION 11-4.1.3
 AND 11-4.1.6 ) SHALL BE PROVIDED THAT
 COMPLIES WITH SECTION 11-4.7 , 11-4.8 ,
 11-4.10 , OR 11-4.11 , RESPECTIVELY. AN
 ACCESSIBLE ROUTE DOES NOT INCLUDE
 STAIRS, STEPS, OR ESCALATORS. SEE
 DEFINITION OF ?EGRESS, MEANS OF? IN
 SECTION 11-3.5 [SEE FIGURE 11-7 (C) AND
 FIGURE 11-7 (D)].
  
 6) COMPLIED.
  
 7) COMPLIED.
  
 8) COMPLIED.
  
 9) COMPLIED.
  
 10) SHEET 3, 4 AND SHEET 11 ALL DETECT A MEZANINE
 LEVEL. AS ASKED IN REVIEW COMMENT
 NUMBER 1 PLEASE REMOVE ALL OLD SHEETS FROM THE PERMIT
 PACKAGE. SHEET 11 ALSO NEEDS TO BE REMOVED.
  
 11)COMPLIED, ONCE ALL REFRENCE TO MEZZANINE IS
 REMOVED FROM PLANS.
  
 12) COMPLIED, ONCE ALL REFRENCE TO MEZZANINE
  
 13) 2ND REQUEST, SHEET#3 DOESN'T PROVIDE ANY CUT
 SECTION THROUGH THE TENANT
 SEPERATION WALL PROVIDING A 1 HR TENANT SEPERATION.
 EITHER PROVIDE THE UL LISTING AND
 DESCRIPTION OF WALL OR TAKE THE PERSCRIPTIVE MEETHOD IN
 TABLE 720.1(2).
  
 14) COMPLIED.
  
 15) COMPLIED.
  
 16) COMPLIED, ONCE ALL REFRENCES TO THE MEZZANINE LEVEL
 ARE REMOVED.
  
 17)) 1209.3 MECHANICAL APPLIANCES.
 ACCESS TO MECHANICAL APPLIANCES INSTALLED IN
 UNDER-FLOOR AREAS, IN ATTICS SPACES AND ON ROOFS OR
 ELEVATED STRUCTURES SHALL BE IN ACCORDANCE WITH THE
 FLORIDA BUILDING MECHANICAL CODE.
  
 18) COMPLIED ONCE ALL REFRENCES TO THE MEZZANINE ARE
 REMOVED.
  
 19) COMPLIED.
  
 20) COMPLIED.
  
 21) COMPLIED.
  
 22) COMPLIED, ONCE ALL REFRENCES TO THE MEZZANINE ARE
 REMOVED.
  
 23)COMPLIED.
  
 24) COMPLIED.
  
 25) 2ND REQUEST,) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 26)2ND REQUEST, UNTIL REVIEWD BY THE DESIGNED
 PROFESSIONAL
 AND SIGNED OFF ACCEPTED THIS COMMENT WILL REMAIN. FL
 BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) FIXED WINDOWS
 B) MULLIONS
 C) GLAZED DOORS
 D) HOLLOW METAL DOORS SINGLE & PAIR
 E) ROOF ASSEMBLIES
 1) FLAT ROOF INSULATION
 2) MODIFIED SINGLE PLY
 3) SLOPED ROOFING APPLICATION
 4) ROOF TILE REPORT
  
 27) THIS ROOF IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
 ___ CONTRACTOR FAILED TO SUBMIT PRODUCT APPROVALS.
  
 _X_ CONTRACTOR FAILED TO INDICATE WHICH
 SYSTEM TO BE USED.
  
 _X_ THE SYSTEM PROVIDED HAS A LOW
 PRESSURE FOR ZONE ___ .
  
 _X_ NO SYSTEMS WERE SUBMITTED IN REPORT. MISSING
 SUBREPORTS LISTED PAGE9-18.
 NO SUBREPORT WAS HIGHLIGHTED.WITH THE REPORT
 SUBMITTED, THIS MAY BE A
 SITUATION:
 THE SYSTEM PROVIDED STATES
 LIMITATION# 7, SHOULD THE FASTENER
 RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THE
 BUILDING OFFICIAL, A REVISED
 FASTENER SPACING, PREPARED , SIGNED
  
 AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF
 CONSULTANT MAY BE SUBMITTED.
  
 _X_NO SUBSYSTEMS SUBMITTED, MAYBE A
 SITUATION.
 THE SYSTEM PROVIDED INDICATES
 LIMITATION# 9, NO ENHANCED
 FASTENING ALLOWED.
  
 _X_ HIP OR RIDGE TILE INDICATE WHAT TYPE
 OF HIP BOARD TO BE USED, ALSO
 INDICATE TYPE OF FASTENING.
 CLAY AND CONCRETE ROOF TILES SHALL BE
 FASTENED IN ACCORDANCE WITH SECTION 1609
 OR IN ACCORDANCE WITH FRSA/RTI
 07320/08/05 INSTALLATION MANUAL.
  
 1507.3.8 APPLICATION.
 TILE SHALL BE APPLIED ACCORDING TO THE MANUFACTURER?S
 INSTALLATION INSTRUCTIONS
 OR RECOMMENDATIONS OF THE FRSA/RTI
 07320/08/05.
  
 28) COMPLIED.
  
 29) PROVISO: TO BE CHECKED BY INSPECTOR BEFORE C.O.:
 804.5.1 MINIMUM CRITICAL RADIANT FLUX .
 INTERIOR FLOOR FINISH IN VERTICAL EXITS,
 EXIT PASSAGEWAYS AND EXIT ACCESS
 CORRIDORS SHALL NOT BE LESS THAN CLASS I
 IN GROUPS I-2 AND I-3 AND NOT LESS THAN
 CLASS II IN GROUPS A, B, E, H, I- 4, M,
 R-1, R-2 AND S. IN ALL OTHER AREAS, THE
 INTERIOR FLOOR FINISH SHALL COMPLY WITH
 THE DOC FF-1 ?PILL TEST? (CPSC 16 CFR,
 PART 1630).
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-06-01 Cont ID  
Sent By jwitmer Date 2006-06-01 Time 13:24 Rev Time 4.44
Received By jwitmer Date 2006-06-01 Time 13:24 Sent To  
Notes
2006-06-01 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06050604
 ADD: 1810 S DIXIE HWY
 CONT: BATTEN CONSTRUCTION
 TEL: (561)820-0027
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) SHEET# 1 CODE DATA INDICATES A
 TYPE III BUILDING BUT NO DESIGNATION TO
 "A" OR "B".
  
 4) MISSING FROM CODE DATA SHEET# 1 IS
 FROM THE 2004 EXISTING BUILDING CODE,
 TO WHAT LEVEL OF REMODELING, LEVEL 1,
 LEVEL 2 OR LEVEL 3? SEE EXISTING
 BUILDING CODE SECTIONS 303, 304 & 305.
  
 5) SHEET # 1B INDICATES ELEVATIONS ON
 THE INTERIOR FINISH FLOOR OF 16.76'AND
 THE EXTERIOR ELEVATION OF 16.64'.
 11-4.3.8 CHANGES IN LEVEL.
 CHANGES IN LEVELS ALONG AN ACCESSIBLE
 ROUTE SHALL COMPLY WITH SECTION 11-4.5.2
 . IF AN ACCESSIBLE ROUTE HAS CHANGES IN
 LEVEL GREATER THAN ? INCH (13 MM), THEN
 A CURB RAMP, RAMP, ELEVATOR, OR PLATFORM
 LIFT (AS PERMITTED IN SECTION 11-4.1.3
 AND 11-4.1.6 ) SHALL BE PROVIDED THAT
 COMPLIES WITH SECTION 11-4.7 , 11-4.8 ,
 11-4.10 , OR 11-4.11 , RESPECTIVELY. AN
 ACCESSIBLE ROUTE DOES NOT INCLUDE
 STAIRS, STEPS, OR ESCALATORS. SEE
 DEFINITION OF ?EGRESS, MEANS OF? IN
 SECTION 11-3.5 [SEE FIGURE 11-7 (C) AND
 FIGURE 11-7 (D)].
  
 6) SHEET# 3, PLANS INDICATE AREAS OF
 WALLS WHERE NEW OPENINGS ARE BEING
 CREATED. ON THE NORTH WALL THERE IS A
 SECTION 3/10 WITH A NOTE NEW #6 NEXT TO
 OPENINGS, DOES MEAN IF A #6 REBAR IS
 DEPICTED NEXT TO AN OPENING THIS IS A
 NEW OPENING?
  
 7) OFFICE WITH DOOR# 7 PRIVATE RESTROOM
 TO BE ADAPTABLE, REQUIRING BACKING &
 TURNING RADIUS.
 11-4.1.3(11) TOILET FACILITIES. IF
 TOILET ROOMS ARE PROVIDED, THEN EACH
 PUBLIC AND COMMON USE TOILET ROOM SHALL
 COMPLY WITH SECTION 11-4.22 . OTHER
 TOILET ROOMS PROVIDED FOR THE USE OF
 OCCUPANTS OF SPECIFIC SPACES (I.E., A
 PRIVATE TOILET ROOM FOR THE OCCUPANT OF
 A PRIVATE OFFICE) SHALL BE ADAPTABLE .
 IF BATHING ROOMS ARE PROVIDED, THEN EACH
 PUBLIC AND COMMON USE BATHROOM SHALL
 COMPLY WITH SECTION 11-4.23 . ACCESSIBLE
 TOILET ROOMS AND BATHING FACILITIES
 SHALL BE ON AN ACCESSIBLE ROUTE.
  
 8) SHEET# 3 CONFERENCE ROOM DOOR# 22
 MISSING THE REQUIRED 18" ON PULL SIDE.
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 9) RESTROOM DOORS 12& 13 SWING OVER THE
 1/2 THE REQUIRED EGRESS WIDTH.
 1008.1.8.8
 DURING ITS SWING, ANY DOOR IN A MEANS OF
 EGRESS SHALL LEAVE UNOBSTRUCTED AT LEAST
 ONE HALF OF THE REQUIRED WIDTH OF AN
 AISLE, CORRIDOR, PASSAGEWAY, OR LANDING,
 NOR PROJECT MORE THAN 7 INCHES (178 MM)
 INTO THE REQUIRED WIDTH OF AN AISLE,
 CORRIDOR, PASSAGEWAY OR LANDING, WHEN
 FULLY OPEN
  
 10) SHEET# 3 & 4 BOTH INDICATE A
 MEZZANINE BUT PLANS DO NOT INDICATE WHAT
 TYPE OF OCCUPANCY WILL TAKE PLACE
 MEZZANINE LEVEL?
  
 11)MEZZANINE IF STORAGE:
 106.4.2 STORAGE & FACTORY- INDUSTRIAL OCCUPANCIES. IT
 SHALL BE THE
 RESPONSIBILITY OF THE OWNER, AGENT,
 PROPIETOR OR OCCUPANT OF GROUP S AND
 GROUP F OCCUPANCIES, OR ANY OCCUPANCY
 WHERE EXCESSIVE FLOOR LOADING IS LIKELY
 TO OCCUR, TO EMPLOY A COMPETENT ARCHI-
 TECT OR ENGINEER IN COMPUTING THE SAFE
 FLOOR LOAD CAPACITY. ALL SUCH COMPUTA-
 TIONS SHALL BE ACCOMPANIED BY AN AFFA-
 DAVIT FROM THE ARCHITECT OR ENGINEER
 STATING THE SAFE ALLOWABLE FLOOR LOADS
 ON EACH FLOOR IN POUNDS PER SQ FT.THE
 COMPUTATIONS & AFFADAVIT SHALL BE FILED
 AS A PERMANENT RECORD OF THE BLDG DEPT.
  
 12) MEZZANINE: IF STORAGE:
 106.4.3.SIGNS REQUIRED. IN EVERY
 BUILDING OR PART OF A BUILDING USED FOR
 STORAGE, INDUSTRIAL OR HAZARDOUS PUR-
 POSES, THE SAFE FLOOR LOADS, AS REVIEWED
 BY THE BUILDING OFFICIAL ON THE PLAN,
 SHALL BE MARKED ON PLATES OF APPROVED DE
 SIGN WHICH SHALL BE SUPPLIED & SECURELY
 AFFIXED BY THE OWNER OF THE BUILDING IN
 A CONSPICUOUS PLACE IN EACH STORY TO
 WHICH THEY RELATE. SUCH PLATES SHALL NOT
 BE REMOVEDOR DEFACED, & IF LOST,
 REMOVED THE OWNER OF THE BUILDING SHALL
 REPLACE THEM.
  
 13) SHEET#3 DOESN'T PROVIDE ANY CUT
 SECTIONS THROUGH TENANT SEPARATION WALL
 PROVIDING 1HR TENANT SEPERTION.
 708.1(5)
  
 14) DOOR SCHEDULE DOESN'T INDICATE THE
 RATING FOR DOORS 2 & 3.
  
 15) OVERFLOW SCUPPERS, SHEET 4,6 AND 6A
 DO NOT PROVIDE ENOUGH INFORMATION AS TO
 THE LOCATION THE OVERFLOW SCUPPERS ARE
 TO BE PLACED IN RELATION TO THE ROOF
 DECK.
 1503.4.3
 WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW
 WATER IS NOT PROVIDED, OVERFLOW SCUPPERS
 SHALL BE PLACED IN WALLS OR PARAPETS NOT
 LESS THAN 2 INCHES (51 MM) NOR MORE THAN
 4 INCHES (102 MM) ABOVE THE FINISHED
 ROOF COVERING AND SHALL BE LOCATED AS
 CLOSE AS PRACTICAL TO REQUIRED VERTICAL
 LEADERS OR DOWNSPOUTS OR WALL AND
 PARAPET SCUPPERS. AN OVERFLOW SCUPPER
 SHALL BE SIZED IN ACCORDANCE WITH THE
 FLORIDA BUILDING CODE, PLUMBING.
  
 16) PLANS DO NOT PROVIDE THE FINISHED
 HEIGTH FLOOR TO CEILING BENEATH THE
 MEZZANINE. 1208.2 MINIMUM CEILING
 HEIGHTS.
 OCCUPIABLE SPACES, HABITABLE SPACES AND
 CORRIDORS SHALL HAVE A CEILING HEIGHT OF
 NOT LESS THAN 7 FEET 6 INCHES (2286 MM). BATHROOMS,
 TOILET ROOMS, KITCHENS,
 STORAGE ROOMS AND LAUNDRY ROOMS SHALL BE
 PERMITTED TO HAVE A CEILING HEIGHT OF
 NOT LESS THAN 7 FEET (2134 MM).
  
 17) 1209.3 MECHANICAL APPLIANCES.
 ACCESS TO MECHANICAL APPLIANCES
 INSTALLED IN UNDER-FLOOR AREAS, IN ATTIC
 SPACES AND ON ROOFS OR ELEVATED
 STRUCTURES SHALL BE IN ACCORDANCE WITH
 THE FLORIDA BUILDING CODE, MECHANICAL.
  
 18) SHEET# 9 DETAIL# 2, IS MISSING THE
 HANDRAIL COTINUING TO THE BOTTOM OF
 STAIR LEFT SIDE OF DETAIL.
 1009.11 HANDRAILS. STAIRWAYS SHALL HAVE
 HANDRAILS ON EACH SIDE.
  
 19) SHEET# 10 INDICATES A 12"X12"
 EXTERIOR MOLDING, PROVIDE DETAILS, AND
 TYPE OF MATERIAL?
  
 20) SHEET# 12 WIND INFORMATION
 REFREENCES THE FBC 2001 CODE.
  
 21) SHEET# 12 NO MENTION OF THE LIVE
 FLOOR LOADS REQUIRED FOR THE MECANICAL
 CLOSETS 60 PSF TABLE 1607.1.
  
 22) SHEET# 12 NO MENTION TO THE LIVE
 LOADS TO BE RESISTED FOR THE STAIRS.
 TABLE 1607.1.
  
 23) SHEET 18 INDICATES A/C DUCT
 PENETRATING TENANT SEPERATION WALL AND
 TRANSFER GRILLE NO FIRE DAMPERS.716.1.1
 DUCTS AND AIR TRANSFER OPENINGS WITHOUT
 DAMPERS. DUCTS AND AIR TRANSFER OPENINGS
 THAT PENETRATE FIRE-RESISTANCE-RATED
 ASSEMBLIES AND ARE NOT REQUIRED BY THIS
 SECTION TO HAVE DAMPERS SHALL COMPLY
 WITH THE REQUIREMENTS OF SECTION 712
  
 24) SHEET 18 ALSO INDICATES A/C
 CONDENSATE PENETRATING 1 HR TENANT
 SEPERATION WALL.
 712.3.1.2 THROUGH-PENETRATION FIRESTOP
 SYSTEM. THROUGH PENETRATIONS SHALL BE
 PROTECTED BY AN APPROVED PENETRATION
 FIRESTOP SYSTEM INSTALLED AS TESTED IN
 ACCORDANCE WITH ASTM E 814 OR UL 1479,
 WITH A MINIMUM POSITIVE PRESSURE
 DIFFERENTIAL OF 0.01 INCH (2.49 PA) OF
 WATER AND SHALL HAVE AN F RATING OF NOT
 LESS THAN THE REQUIRED FIRE-RESISTANCE
 RATING OF THE WALL PENETRATED.
  
 25) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 26) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) FIXED WINDOWS
 B) MULLIONS
 C) GLAZED DOORS
 D) HOLLOW METAL DOORS SINGLE & PAIR
 E) ROOF ASSEMBLIES
 1) FLAT ROOF INSULATION
 2) MODIFIED SINGLE PLY
 3) SLOPED ROOFING APPLICATION
 4) ROOF TILE REPORT
  
 27) THIS ROOF IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
 _X_ CONTRACTOR FAILED TO SUBMIT PRODUCT APPROVALS.
  
 _X_ CONTRACTOR FAILED TO INDICATE WHICH
 SYSTEM TO BE USED.
  
 _X_ THE SYSTEM PROVIDED HAS A LOW
 PRESSURE FOR ZONE ___ .
  
 _X_ NO REPORT SUBMITTED,MAY BE A
 SITUATION:
 THE SYSTEM PROVIDED STATES
 LIMITATION# 7, SHOULD THE FASTENER
 RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THE
 BUILDING OFFICIAL, A REVISED
 FASTENER SPACING, PREPARED , SIGNED
  
 AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF
 CONSULTANT MAY BE SUBMITTED.
  
 _X_NO REPORT SUBMITTED, MAYBE A
 SITUATION.
 THE SYSTEM PROVIDED INDICATES
 LIMITATION# 9, NO ENHANCED
 FASTENING ALLOWED.
  
 _X_ HIP OR RIDGE TILE INDICATE WHAT TYPE
  
 OF HIP BOARD TO BE USED, ALSO
 INDICATE TYPE OF FASTENING.
 CLAY AND CONCRETE ROOF TILES SHALL BE
 FASTENED IN ACCORDANCE WITH SECTION 1609
 OR IN ACCORDANCE WITH FRSA/RTI
 07320/08/05 INSTALLATION MANUAL.
  
 1507.3.8 APPLICATION.
 TILE SHALL BE APPLIED ACCORDING TO THE MANUFACTURER?S
 INSTALLATION INSTRUCTIONS
 OR RECOMMENDATIONS OF THE FRSA/RTI
 07320/08/05.
  
 28)SHEET 11 DETAILS D/E GLASS IN GUARD
 RAILS:
 1607.7.1.1 CONCENTRATED LOAD.
 HANDRAIL ASSEMBLIES AND GUARDS SHALL BE
 ABLE TO RESIST A SINGLE CONCENTRATED
 LOAD OF 200 POUNDS (0.89 KN), APPLIED IN
 ANY DIRECTION AT ANY POINT ALONG THE
 TOP, AND HAVE ATTACHMENT DEVICES AND
 SUPPORTING STRUCTURE TO TRANSFER THIS
 LOADING TO APPROPRIATE STRUCTURAL
 ELEMENTS OF THE BUILDING. THIS LOAD NEED
 NOT BE ASSUMED TO ACT CONCURRENTLY WITH
 THE LOADS SPECIFIED IN THE PRECEDING
 PARAGRAPH.
 2407.1.1 LOADS.
 THE PANELS AND THEIR SUPPORT SYSTEM
 SHALL BE DESIGNED TO WITHSTAND THE LOADS
 SPECIFIED IN SECTION 1607.7 . A SAFETY
 FACTOR OF FOUR SHALL BE USED.
 2407.1.2 SUPPORT.
 EACH HANDRAIL OR GUARD SECTION SHALL BE
 SUPPORTED BY A MINIMUM OF THREE GLASS
 BALUSTERS OR SHALL BE OTHERWISE
 SUPPORTED TO REMAIN IN PLACE SHOULD ONE
 BALUSTER PANEL FAIL. GLASS BALUSTERS
 SHALL NOT BE INSTALLED WITHOUT AN
 ATTACHED HANDRAIL OR GUARD.
  
 29) NOTE TO BE CHECKED WITH INSPECTOR:
 FLUX
 804.5.1 MINIMUM CRITICAL RADIANT FLUX .
 INTERIOR FLOOR FINISH IN VERTICAL EXITS,
 EXIT PASSAGEWAYS AND EXIT ACCESS
 CORRIDORS SHALL NOT BE LESS THAN CLASS I
 IN GROUPS I-2 AND I-3 AND NOT LESS THAN
 CLASS II IN GROUPS A, B, E, H, I- 4, M,
 R-1, R-2 AND S. IN ALL OTHER AREAS, THE
 INTERIOR FLOOR FINISH SHALL COMPLY WITH
 THE DOC FF-1 ?PILL TEST? (CPSC 16 CFR,
 PART 1630).
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-10-26 Cont ID  
Sent By dpalmer Date 2007-10-26 Time 08:07 Rev Time 0.00
Received By dpalmer Date 2007-10-25 Time 16:56 Sent To  
Notes
2007-10-26 08:14:16PREVIOUSLY REVIEWED AND STAMPED ON 9/8/07.
 SAME SHEETS, NO NEW SHEETS.
 RETAINED ELECTRICAL FROM ONE SET FOR FILING.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-09-08 Cont ID  
Sent By dpalmer Date 2007-09-08 Time 19:13 Rev Time 0.00
Received By dpalmer Date 2007-09-08 Time 19:13 Sent To  
Notes
2007-09-08 19:15:292007-09-08 19:15:29
  
 SCOPE OF WORK DECREASED.
 HIGH-LIGHTED AND REDLINED PLANS FOR SCOPE OF ELECTRICAL
 NO LONGER INCLUDED.
 ELECTRICAL PLANS STAMPED. NEED TO RETAIN ONE COPY OF
 ELECTRICLA ONCE FIRE REVIEW IS COMPLETED.
  
 ** PLEASE KNOW REVISED ENERGY CALCULATIONS FOR ACTUALL
 SCOPE OF WORK WILL BE REQUIRED BEFORE FINAL.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-02-14 Cont ID  
Sent By dpalmer Date 2007-02-14 Time 11:57 Rev Time 0.00
Received By dpalmer Date 2007-02-14 Time 11:47 Sent To  
Notes
2007-02-14 11:58:49HAND WRITTEN OC SENSOR ADDED TO PLANS OK AND REDLINED.
  
 MIN 2GRND RODS REQUIRED FOR GROUNDING ELECTRODE SYSTEM.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-12-17 Cont ID  
Sent By dpalmer Date 2006-12-17 Time 15:18 Rev Time 0.00
Received By dpalmer Date 2006-12-17 Time 14:32 Sent To  
Notes
2006-12-17 15:19:38*** UNSAT 3RD REVIEW ***
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEWS HAVE NOT
 YET BEEN FULLY ADDRESSED.
 PLEASE SEE NEW COMMENTS WHICH SHOULD BE NOTED AS THIS
 REVIEWER GOING THROUGH PLANS SUBMITTED.
  
 1) NOTE: PLEASE SEE AREA FOR INGRESS/EGRESS AT THE REAR
 OF BUILD OUT WHICH DOES NOT SEEM TO INDICATE ANY DEVICE
 TO TURN ON OR OFF LIGHTING AUTOMATICALLY. ( AREA
 REDLINED)
 PLEASE SEE RESPONSE AND CONVERSATION ON PHONE WITH MR.
 JIMMY EDWARDS WAS THAT METHOD "B" WAS GOING TO BE USED
 AND SUBMITTED.
 PLEASE THE ORIGINAL ENERGY CALCULATIONS DATED 5-1-06
 ARE STILL BEING ATTACHED INDICATING A METHOD "A".
 PLEASE SEE THIS DOES NOT COMPLY OR PROVIDE THE
 INFORMATION AS NEEDED AND NOTED IN PREVIOUS REVIEWS.
 PLEASE SEE THIS METHOD AS ATTACHED STILL INDICATES ALL
 LIGHTING BEING MANUALLY CONTROLLED WHICH BY PLANS AND
 DESIGN IS NOT THE CASE.
 PLEASE SEE 13-415.1.ABC.1.1, AND 13-415.2.ABC.1 FOR
 MINIMUM CALCULATIONS FOR LIGHTING POWER DENSITIES.
  
 ** NEW NOTES NOTED BY THIS REVIEWER WHICH DO NOT APPLY
 TO CHANE ENGINEERING**
  
 1) NOTE: PLEASE SEE MISSING TITLE BLOCKS FROM LANDSCAPE
 SHEETS WHICH ARE SIGNED, AND SEALED BY A LANDSCAPE
 ARCHITECT. PLEASE SEE FLORIDA ADMINISTRATIVE CODE
 61G1-16.004 AND FS 481.219
  
 2) NOTE: PLEASE SEE MISSING INFORMATION REQUIRED ON
 TITLE BLOCKS FOR THE CIVIL ENGINEERING/SITE SHEETS.
 PLEASE SEE MISSING PRINTED NAME AND LICENSE NUMBER.
  
 ** THESE TWO COMMENTS ARE REQUIRED TO BE DONE WHETHER
 OR NOT COMMENT IS MADE BY ANY OTHER TRADE.
 PLEASE KNOW SAID INFORMATION MAY BE STAMPED, LABELED,
 OR HANDWRITTEN ON SHEETS AS LONG AS THERE ARE NOT
 COMMENTS WHICH WILL REQUIRE SHEETS TO BE CHANGED.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-10-15 Cont ID  
Sent By dpalmer Date 2006-10-15 Time 14:16 Rev Time 0.00
Received By dpalmer Date 2006-10-15 Time 12:35 Sent To  
Notes
2006-10-15 14:16:59********* UNSAT2ND REVIEW ***********
  
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW WHICH ARE
 STILL IN NEED OF ADDRESSING ALONG WITH NEW NOTES DUE TO
 INFORMATION NOW SHOWN OR CHANGES MADE.
  
  
 1) NOTE: NO, SAME NOTE .
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THE FOLLOWING
 MININUM CODES SHALL BE SPECIFIED ON THE
 PLANS FOR DESIGN AND BUILDING.
 NFPA-70 2002, NFPA-101 2003, NFPA-72
 2002.
  
 2) NOTE:NO, COULD NOT LOCATE ANY INFORMATION ON
 SUMMARY OR BREAK DOWN OFLOADS AND HOW THEY HAVE BEEN
 FIGURED OR DERIVED? PLEASE ALSO SEE COMMENT FOR SIGN
 CIRCUIT. PLEASE SEE BOTH ARE BEING SHOWN ON THE SAME
 CIRCUIT NOW ON PANEL "L" WHICH PANEL "M" STILL SHOWS
 THE CIRCUITING WHICH WAS DONE ON PREVIOUS PLANS( M-15)
 ?? PLEASE SEE ALL NOTES PERTAINIGN TO THESE ADJUST AND
 CORRELATE.
  
 **PREVIOUS REVIEW NOTE **
 PLEASE SEE THE SHOW WINDOW
 REQUIRED DEDICATED CIRCUITS MAY NOT BE
 SHARED AS/OR WITH THE REQUIRED SIGN
 CIRCUITS. PLEASE SHOW LOADS PER 220.12A
 ON CALCS FOR "WATTS" PER LINEAR FT.
  
 3) NOTE:NO, PLEASE SEE NOTE ABOVE, ALSO PLEASE SEE
 600.5, AS PERVIOUSLY NOTED FOR LOCATION(S) OF REQUIRED
 CIRCUIT. PLEASE SEE THE SAME 600.5 WHICH REFERENCES
 220.3B6 FOR MIN VA REQUIRED FOR THIS. PLEASE SEE PANEL
 SCHEDULE EITHER "M" OR "L" EACH SHOWS A 4A LOAD?? HOW
 IS THIS POSSIBLE WHEN THE MIN VA IS REQUIRED TO BE
 FIGURED AT 1200VA.PLEASE ADJUST.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THE REQUIRED
 DEDICATED SIGN CIRCUITS SHALL BE SIZED
 AND CIRCUITED PER 600.5 WHETHER OR NOT
 AN ELECTRICAL TYPE SIGN WILL BE
 INSTALLED.
  
 4) NOTE: ? SEE NEW NOTES AS THIS NOTE WAS ADDED ON
 PANEL SCHEDULE FOR "PLUGMOLD"??
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 220.12B, TRACK LTS
 SHALL BE SHOWN IN CALCULATIONS .
  
 5) NOTE:NO, SAME NOTE, ALONG WIHT NOTES ABOVE ABOUT
 SIGNS, SHOW WINDOWS ETC, PLEASE PROVIDE A LOAD SUMMARY
 ON HOW LOADS WERE DERIVED. SHOWING A CONNECTED AMERAGE
 LOAD DOES NOTPROVIDE INFORMATION.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THAT LOAD
 CALCULATIONS SHALL BE SHOWN. RECEPTS
 WHEN KNOWN ARE TO BE SHOWN, LIGHTING
 LOADS SHALL BE SHOWN AND IF CONTINUOUS
 THESE SHALL BE IDENTIFIED WITH 125% FIG.
 PLEASE SEE CALCUALTIONS WILL BE REQUIRED
 EVEN IF NO DERATINGS ARE GOING TO BE
 DONE. PLEASE SEE THE LOADS ON PANELS NOW
 ARE NOT COMPLETE AT THIS TIME.
 220.3,220.10,220.11,220.13,,
 215.3,230.42 ETC.
 215.5
  
 6) NOTE:NO, PLEASE SEE THESE ARE STILL BEING SHOWN
 WITH TWO SEPARATE LOADS, WHERE THE MECHANICAL PLANS
 STILL INDICATE BOTH OF THESE BEING SAME??
 PLEASE ADJUST.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CORRELATE LOADS AND OCP
 FOR ALL AHU'S. PLEASE SEE UNIT 1 AND 2
 ARE THE SAME , YET THE AMPERAGE IS NOT
 THE SAME AND THE OCP IS DIFFERENT?
 PLEASE SEE MECHANICAL PLANS AND
 CORRELATE.
 PLEASE BE SURE TO SEE 424.3B FOR 125%
 OCP MIN.
 PLEASE ADJUST AWG PER 310.16
  
 7) NOTE:NO, THIS IS UNCLEAR AT THIS TIME AS THE
 STAIRS AND MEZZ LEVELS ARE UNCLEAR IF THEY EVEN EXIST
 ANYMORE AS SHEETS ARE STILL BEING SUBMITTED SHOWING A
 MEZZ LEVEL, YET NO LIGHTING OR STAIRS ARE SHOWN??
 PLEASE ALSO SEE NEW NOTES.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SHOW THE NORMAL AND
 EMERGENCY FT CANDLES FOR STAIRS. PLEASE
 SEE NFPA-101 2003, 708.1.3,709.2.2 WHICH
 NOW REQUIRES 10FT CANDLES (108LUX) UNDER
 NORMAL AND 10.8 FT CANDLES (10.8) UNDER
 EM CONDITIONS.
 PLEASE SHOW THE PHOTO-METRICS FOR THE
 EGRESS PATHS TO THE PUBLIC RIGHT OF WAY
 AS REQUIRED.
  
 8) NOTE: ? NO, ?PANEL HAS NOT MOVED AND ROOM
 DESIGNATION HAS BEEN REMOVED FROM PLANS ALL TOGETHER??
 THE ROOM SHALL BE IDENTIFIED ON PLANS FOR USE AND
 OCCUPANCY. IF INDEED THIS IS GOING TO BE USED AS A
 STORAGE ROOM, PLEASE RELOCATE PANELS AS THIS IS A LIFE
 SAFETY ISSUE AND AT THE VERY LEAST A FIRE HAZARD TO THE
 OCCUPANTS AND PROPERTY DAMAGE POTENTIAL.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE LOCATION OF PANEL
 "L" SHALL NOT BE LOCATED IN STORAGE
 ROOM.
 PLEASE RELOCATE.110.26,408.7, 240.24
 ETC.
 PLEASE ALSO SHOW SECTION #2 OF PANEL "L"
 ON PLANS.
  
 9) NOTE: OK, HOWEVER DUE TO PLANS NOT BEING COMPLETE
 FOR CLEAR REVIEW, PLEASE SEE PLANS WHICH STILL INDICATE
 A MEZZ LEVEL IN SETS DO NOT CONTAIN SOME ITEMS
 IDENTIFIED TO BE ON FIXTURE SCHEDULE. FIXTURE FOR
 POSSIBLE STAIR AREA IS NTO SHOWN, PLEASE SEE OTHER
 NOTES FOR COORDINATION.
  
 ** PREIVOUS REVIEW NOTE **
 PLEASE COMPLETE FIXTURE
 IDENTIFICATION ON PLANS. PLEASE SEE SOME
 ARE MISSING FIX DESIGNATIONS.
 PLEASE ALSO SEE SOME FIXTURES ON FIX
 SCHEDULE COULD NOT BE LOCATED ON PLANS?
  
 10) NOTE: OK.
  
 11) NOTE: OK, CIRCUITING WAS COMPLETED HOWEVER WILL BE
 REVISED BASED ON OTHER COMMENTS.
  
 12) NOTE: OK, HOWEVER SEE ONE NEW NOTE AS "FYI".
  
 13) NOTE: OK, HOWEVER PROVIDE A GROUNDING ELECTRODE
 ATTACHMENT DETAIL FOR A NEW BUILDING? PLEASE KNOW IT
 SEEMS THIS BUILDING IS EXISTING AND TO SHOW AN
 ATTACHMENT TO THE FOOTER STEELMAY NOT BE DESIRED.
 PLEASE KNOW ON AN EXISTING OLDER BLDG WHERE THE FOOTER
 STEEL IS NOT AVAILABLE, IT IS NOT REQUIRED TO CHIP
 OUT/EXPOSE THE EXISTING FOOTER STEEL (IF THERE IS ONE)
 AS THIS MAY AFFECT THE STRUCTURAL INTEGRITY OF THE
 EXSITING FOOTER AND HAVING TO SEAL THIS AREA BACKSO
 THAT MOISTURE AND SPALDING DOES NOT OCCUR. PLEASE ONLY
 INCLUDETHE LOCATIONS WHICH WILL BE AVAILABLE ETC PER
 250.50 2002 NEC. CODES ARE NOTE REQUIRED TO BE ON
 DETAIL HOWEVER MAY.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SHOW THE LOCATION OF
 THE ATTACHMENT OF THE GROUNDING
 ELECTRODE CONDUCTOR.
 250.24B,250.6,215.5
  
 14) NOTE: OK, HOWEVER SEE 240.12 FOR SELECTIVE
 COORDINATION FOR DESIGNER TO VERIFY. THISNOTE WAS FOR
 AIC RATINGS.110.9 AND IS OK.
  
  
 15) NOTE: OK.
  
 16) NOTE:NO/OK, OCCUPANT DEVICES HAVE BEEN USED AND
 ADDED TO ALMOST ALL LOCATIONS, HOWEVER AS THE MEZZ
 LEVEL IS NOT CLEAR THIS CAN NOT BE REVIEWED. PLEASE
 ALSO SEE NO LIGHTING POWER DENSITIES WERE LOCATED FOR
 MAX WATTAGE ALLOWED . 13-415.2.ABC.1 PLEASE ALSO
 SPECIFY THE MAX TIMES ON DEVICES CHOSEN. (TIMER TYPE
 4HRS MAX, OS TYPE 30 MINS MAX).
 PLEASE SEE CIRCUITING OF EM/ EXT LTS WILL BE AFFECT AS
 SHOWN. MUST BE WIRED INTO BRANCH CIRCUIT AHEAD OF ANY
 CONTROL DEVICE. PLEASE INDICATE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THIS NOTE IS VERY
 IMPORTANT AND WILL REQUIRE MANY CHANGES
 IN THE ELECTRICAL LIGHTING SYSTEM AS
 SHOWN.
 PLEASE SEE FBC 2004 CHAPTER 13. PLEASE
 SEE THIS IS NEW IN THE 2004 CODE AND
 MANY CHANGES WERE MADE TO THE ELECTRICAL
 SECTION FROM THE 2001 FBC. THESE CHANGES
 BECAME FEDERALLY MANDATED IN JULY 04 FOR
 EACH STATE TO ADOPT THESE MIN
 REQUIREMENTS BY THE NEXT CODE CYCLE.
  
 **PLEASE SEE 13-101.1.3 THE ENERGY CODE
 COMPLIANCE FORM SHALL BE "C".
 PLEASE SEE 13-413.1.ABC.1, A WORST CASE
 VOLTAGE DROP CALCULATION WILL BE
 REQUIRED TO BE SHOWN ON PLANS FOR
 FEEDERS AND BRANCH CIRCUITS.
 PLEASE SEE 13-415.1.ABC.1.1,
 13-415.1.ABC.1.2, 13-415.1.ABC.1.3, ALL
 OF WHICH REQUUIRES MANY ITEMS ON PLANS
 TO BE CHANGED. PLEASE INDICATE THE TYPE
 OF SYSTEM WHICH WILL BE USED,
 SCHEDULING, THE LOCATIONS OF THE
 REQUIRED OVER RIDE SWITCHES, THE
 LOCATIONS OF THE OCCUPANCY SENSORS(IF
 USED) AND PLEASE SEE THE REQUIREMENTS OF
 THE MULTIPLE FLOORS. ETC
 PLEASE BE SURE TO INCLUDE DEVICES FOR
 SEPARATE SPACES.
  
  
 17) NOTE: OK.
  
  
 18) NOTE:NO, THIS WAS NOT DONE,.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 **PREVIOUS REVIEW NOTE **
 PLEASE KNOW, BEFORE
 RESUBMITTING PLANS, PLEASE BE SURE TO
 COMPLETELY REMOVE ANY OLD/VOIDED SHEETS
 FROM SETS AND ONLY INSERT THE "NEW"
 SHEETS INTO SETS FOR REVIEW AND
 STAMPING. THIS WILL HELP TO ALLEAVAITE
 DELAYS IN REVIEW OF SAID PROJECT. ONE
 COPY OF THE OLD/VOIDED REMOVED SHEETS
 SHOULD ACCOMPANY THE NEW SETS FOR
 REFERENCE.
  
 ** NEW NOTES **
  
 19) NOTE: PLEASE SEE ALL NOTES ABOVE WITH REPSETC TO
 MEZZ LEVEL AND COMPLETE PLANS ACCORDINGLY.
  
 20) NOTE: ** THIS IS ONLY A NOTE: PLEASE SEE A 1/0
 EQUIPMENT GROUNDING CONDUCTOR IS BEING SHOWN FROM MAIN
 TO PANEL "L". PLEASE SEE 250.122 FOR MIN REQUIRED. SIZE
 IS MUCH LARGER THAN NEEDED, HOWEVER MAY BE USED. PLEASE
 KNOW, IF SHOWN ON PLANS LIKE THIS, THEN THE 1/0 WILL BE
 REQUIRED OT BE INSTALLED. THIS IS FOR INFORMATIONAL
 PURPOSE ONLY AND DOES NOT NEED TO BE REVISED.
  
 21) NOTE: PLEASE SEE A NOTE WAS ADDED TO PANEL WITH A
 DOUBLE "* *" NEXT TO CIRCUIT FOR PLUGMOLD WHICH NOTES
 LOADS ALL FIGURED PER 220.12B AND 150WATTS PER 2'??
 PLEASE SEE 220.12B IS FOR TRACK LIGHTING AND MAY NOT BE
 USED FOR PLUGMOLD. PLEASE SEE PREVIOUS NOTE FOR LOAD
 CALCULATIONS AND REVISE.
  
 22) NOTE: PLEASE SEE FOYER/ENTRANCE AREA SHALL CONTAIN
 AN EM LT AS THERE DOORS FROM OTHER AREAS WHICH DO
 SUPPLY THE NEEDED ILLUMINATION FOR REQUIRED EGRESS.
 PLEASE SEE NFPA-101 7.8, 7.9
  
 23) NOTE: PLEASE SEE COPY OF FLORIDA STATUES ATTACHED
 553.80(2)(B) WITH RESPECTTO REPEAT COMMENTS FOR CODE
 COMPLIANCE.
  
 24) NOTE: PLEASE SEE 422.17 FOR WHAT APPEARS TO BE A
 WATER HEATER IN A STORAGE CLOSET.PLEASE RELOCATE.
  
  
 PLEASE SEE ANY COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS/ DESIGN.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-10 Cont ID  
Sent By dpalmer Date 2006-06-10 Time 13:55 Rev Time 0.00
Received By dpalmer Date 2006-06-10 Time 12:39 Sent To  
Notes
2006-06-10 00:00:00IN ELEC
 ********* UNSAT ***********
  
 1) NOTE: PLEASE SEE THE FOLLOWING
 MININUM CODES SHALL BE SPECIFIED ON THE
 PLANS FOR DESIGN AND BUILDING.
 NFPA-70 2002, NFPA-101 2003, NFPA-72
 2002.
  
 2) NOTE: PLEASE SEE THE SHOW WINDOW
 REQUIRED DEDICATED CIRCUITS MAY NOT BE
 SHARED AS/OR WITH THE REQUIRED SIGN
 CIRCUITS. PLEASE SHOW LOADS PER 220.12A
 ON CALCS FOR "WATTS" PER LINEAR FT.
  
 3) NOTE: PLEASE SEE THE REQUIRED
 DEDICATED SIGN CIRCUITS SHALL BE SIZED
 AND CIRCUITED PER 600.5 WHETHER OR NOT
 AN ELECTRICAL TYPE SIGN WILL BE
 INSTALLED.
  
 4) NOTE: PLEASE SEE 220.12B, TRACK LTS
 SHALL BE SHOWN IN CALCULATIONS .
  
 5) NOTE: PLEASE SEE THAT LOAD
 CALCULATIONS SHALL BE SHOWN. RECEPTS
 WHEN KNOWN ARE TO BE SHOWN, LIGHTING
 LOADS SHALL BE SHOWN AND IF CONTINUOUS
 THESE SHALL BE IDENTIFIED WITH 125% FIG.
 PLEASE SEE CALCUALTIONS WILL BE REQUIRED
 EVEN IF NO DERATINGS ARE GOING TO BE
 DONE. PLEASE SEE THE LOADS ON PANELS NOW
 ARE NOT COMPLETE AT THIS TIME.
 220.3,220.10,220.11,220.13,,
 215.3,230.42 ETC.
 215.5
  
 6) NOTE: PLEASE CORRELATE LOADS AND OCP
 FOR ALL AHU'S. PLEASE SEE UNIT 1 AND 2
 ARE THE SAME , YET THE AMPERAGE IS NOT
 THE SAME AND THE OCP IS DIFFERENT?
 PLEASE SEE MECHANICAL PLANS AND
 CORRELATE.
 PLEASE BE SURE TO SEE 424.3B FOR 125%
 OCP MIN.
 PLEASE ADJUST AWG PER 310.16
  
 7) NOTE: PLEASE SHOW THE NORMAL AND
 EMERGENCY FT CANDLES FOR STAIRS. PLEASE
 SEE NFPA-101 2003, 708.1.3,709.2.2 WHICH
 NOW REQUIRES 10FT CANDLES (108LUX) UNDER
 NORMAL AND 10.8 FT CANDLES (10.8) UNDER
 EM CONDITIONS.
 PLEASE SHOW THE PHOTO-METRICS FOR THE
 EGRESS PATHS TO THE PUBLIC RIGHT OF WAY
 AS REQUIRED.
  
 8) NOTE: PLEASE SEE LOCATION OF PANEL
 "L" SHALL NOT BE LOCATED IN STORAGE
 ROOM.
 PLEASE RELOCATE.110.26,408.7, 240.24
 ETC.
 PLEASE ALSO SHOW SECTION #2 OF PANEL "L"
 ON PLANS.
  
 9) NOTE: PLEASE COMPLETE FIXTURE
 IDENTIFICATION ON PLANS. PLEASE SEE SOME
 ARE MISSING FIX DESIGNATIONS.
 PLEASE ALSO SEE SOME FIXTURES ON FIX
 SCHEDULE COULD NOT BE LOCATED ON PLANS?
  
 10) NOTE: PLEASE IDENTIFY ALL FIXTURES
 WHICH ARE EM TYPE, WITH THE REQUIRED
 NOTED BATTERY BACK UP.
 215.5
  
 11) NOTE: PLEASE COMPLETE ALL CIRCUITING
 ON PLANS. PLEASE BE SURE TO SEE 700.12E
 FOR EM/EXT LTS WHICH ARE REQUIRED TO BE
 CIRCUITED TO THE NORMAL BRANCH CIRCUIT
 IN THE AREA IN WHICH THESE FIXTURES ARE
 LOCATED.
  
 12) NOTE: PLEASE COMPLETE RISER DIAGRAM.
 PLEASE INCLUDE ALL SEC'S ON RISER FROM
 METER TO GUTTER AND FROM GUTTER TO EACH
 MAIN(S).
 310.16,215.5
  
 13) NOTE: PLEASE SHOW THE LOCATION OF
 THE ATTACHMENT OF THE GROUNDING
 ELECTRODE CONDUCTOR.
 250.24B,250.6,215.5
  
 14) NOTE: PLEASE INDICATE THE AIC
 RATINGS FOR ALL SERVICE EQUIPMENT PER
 110.9, 215.5
 THIS IS SHOWN FOR PANELS, BUT NOT FOR
 MAINS??
  
 15) NOTE: PLEASE COMPLETE PANEL SCHEDULE
 FOR ALL CIRCUITS. PLEASE KNOW, THE AREA,
 ROOM, IDENTIFICATION OF EACH CIRCUIT IS
 REQUIRED. IE: CONFERENCE RM RECEPTS,
 OFFICE #2 RECEPTS, BREAK RM RECEPTS,,
 ETC ETC.
 PLEASE KNOW, GENERAL "RECEPTS" OR
 "LIGHTS" ARE NO LONGER ACCEPTABLE.408.4,
 215.5
 ** PLEASE KNOW, IT IS KNOWN AND COMMON
 THAT THESE WILL CHANGE DURING THE
 CONSTRUCTION AND WILL BE REQUIED TO BE
 REVISED ALONG WITH ANY OTHER CHANGES AT
 A LATER DATE. THIS IS HOWEVER REQ'D AT
 THIS TIME. PLEASE BE SURE ALL AREA AND
 ROOM DESIGNATIONS ARE ON PLANS.
  
 16) NOTE: PLEASE SEE THIS NOTE IS VERY
 IMPORTANT AND WILL REQUIRE MANY CHANGES
 IN THE ELECTRICAL LIGHTING SYSTEM AS
 SHOWN.
 PLEASE SEE FBC 2004 CHAPTER 13. PLEASE
 SEE THIS IS NEW IN THE 2004 CODE AND
 MANY CHANGES WERE MADE TO THE ELECTRICAL
 SECTION FROM THE 2001 FBC. THESE CHANGES
 BECAME FEDERALLY MANDATED IN JULY 04 FOR
 EACH STATE TO ADOPT THESE MIN
 REQUIREMENTS BY THE NEXT CODE CYCLE.
  
 **PLEASE SEE 13-101.1.3 THE ENERGY CODE
 COMPLIANCE FORM SHALL BE "C".
 PLEASE SEE 13-413.1.ABC.1, A WORST CASE
 VOLTAGE DROP CALCULATION WILL BE
 REQUIRED TO BE SHOWN ON PLANS FOR
 FEEDERS AND BRANCH CIRCUITS.
 PLEASE SEE 13-415.1.ABC.1.1,
 13-415.1.ABC.1.2, 13-415.1.ABC.1.3, ALL
 OF WHICH REQUUIRES MANY ITEMS ON PLANS
 TO BE CHANGED. PLEASE INDICATE THE TYPE
 OF SYSTEM WHICH WILL BE USED,
 SCHEDULING, THE LOCATIONS OF THE
 REQUIRED OVER RIDE SWITCHES, THE
 LOCATIONS OF THE OCCUPANCY SENSORS(IF
 USED) AND PLEASE SEE THE REQUIREMENTS OF
 THE MULTIPLE FLOORS. ETC
 PLEASE BE SURE TO INCLUDE DEVICES FOR
 SEPARATE SPACES.
  
  
 17) NOTE: PLEASE SEE THIS COMMENT IS NOT
 FOR ELECTRICAL ENGINEER.
 PLEASE SEE ALL COPIES OF PLANS DONE BY
 AN ENGINEER IS REQUIRED TO CONTAIN AND
 ORIGINAL SIGNATURE AND SEAL AND DATE.
 PLEASE SEE DRAINAGE CALCUALTIONS WHICH
 ARE "PHOTO-COPIES" OF SIGNED AND SEALED
 SHEETS. THIS IS REQUIRED PER FAC
 61G15-23.002, FS 471.025 WHETHER OR NOT
 COMMENT IS MADE BY OTHER
 ENGINEERING/CIVIL REVIEWER.
  
  
 18) NOTE: PLEASE KNOW, BEFORE
 RESUBMITTING PLANS, PLEASE BE SURE TO
 COMPLETELY REMOVE ANY OLD/VOIDED SHEETS
 FROM SETS AND ONLY INSERT THE "NEW"
 SHEETS INTO SETS FOR REVIEW AND
 STAMPING. THIS WILL HELP TO ALLEAVAITE
 DELAYS IN REVIEW OF SAID PROJECT. ONE
 COPY OF THE OLD/VOIDED REMOVED SHEETS
 SHOULD ACCOMPANY THE NEW SETS FOR
 REFERENCE.
  
  
 PLEASE SEE ANY COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS/ DESIGN.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE NAY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2007-02-16 Cont ID  
Sent By rchokshi Date 2007-02-16 Time 10:40 Rev Time 0.00
Received By rchokshi Date 2007-02-16 Time 10:40 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2007-01-12 Cont ID  
Sent By rchokshi Date 2007-01-12 Time 09:28 Rev Time 0.00
Received By rchokshi Date 2007-01-12 Time 09:28 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2006-10-23 Cont ID  
Sent By rchokshi Date 2006-10-23 Time 13:17 Rev Time 0.00
Received By rchokshi Date 2006-10-23 Time 13:03 Sent To  
Notes
2006-10-23 13:17:28FAILED FOR FOLLOWING REASONS:
  
 1 PLEASE CALCULATE THE WORST CASE EITHER 1" OVER ENTIRE
 SITE OR 2.5" CRITERIA. EXFILTRATION TRENCH LENGTH WOULD
 BE LOT MORE THAN YOU CALCULATED.
 2.PLEASE ADD IN DRAWING SET CITY OF WPB STANDARDS FOR
 DUMPSTER ENCLOSURE,
 SIDEWALK,DRIVEWAY,APPROACH,PARKING,HANDICAP PARKING,
 ADA, STANDARDS.
 3 NEED POLLUTION PREVENTION PLAN DETAILS
 4 NEED UTILITY REVIEW FROM 45TH STREET
 5 PLEASE SHOW STORM WATER CATCH BASINS & OUTLETS AROUND
 YOUR SITE
  
 PLEASE RESPOND EACH ITEM TO EXPEDITE PERMITTING
 PROCESS.
  
 RASIKCHOKSHI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2006-07-18 Cont ID  
Sent By   Date 2006-07-18 Time   Rev Time 0.00
Received By   Date 2006-07-18 Time   Sent To  
Notes
2006-07-18 00:00:00REVISE DRAINAGE CAL TO RETAIN 1" OF
 RUNOFF OVER THE ENTIRE SITE.
 PLEASE INDICATE LOCATION OF
 EXFILTRATION TRENCH, SHOW FLOW
 DIRECTION,ON SHEET 1 OF STORM WATER
 MANAGEMENT,
 ALSO, SHOW APPLICABLE RAMP/ACCESSIBLE
 DETAIL, CITY STANDARD SHEET ATTACHED FOR
 YOUR USE
  
  
 PLEASE CALL IF YOU HAVE ANY QUESTIONS,
 RASIK CHOKSHI 805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2007-11-05 Cont ID  
Sent By mawillia Date 2007-11-05 Time 15:44 Rev Time 0.00
Received By mawillia Date 2007-11-05 Time 15:37 Sent To  
Notes
2007-11-05 15:43:53*****APPROVED*****
  
 REVISED PLAN SHEET 20 STAMPED, INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2007-09-24 Cont ID  
Sent By mawillia Date 2007-09-24 Time 15:22 Rev Time 0.00
Received By mawillia Date 2007-09-24 Time 14:57 Sent To  
Notes
2007-09-24 15:03:29*****UNSAT*****
  
 REVISED PLAN SHEET 15 STAMPED, INITIALED, AND DATED;
 HOWEVER REVISED PLAN SHEET 20 (WHICH REPLACES SHEET 6)
 DOES NOT DISPLAY/SHOW THE NUMERICAL ADDRESS.AS PER
 WEST PALM BEACH CODE, BUILDING ADDRESS NUMBERS SHALL BE
 NO LESS THAN 6" IN HEIGHT AND 1" IN WIDTH.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-01-08 Cont ID  
Sent By mawillia Date 2007-01-08 Time 17:54 Rev Time 0.00
Received By mawillia Date 2007-01-08 Time 17:54 Sent To  
Notes
2007-01-08 18:04:43*** AS PER WEST PALM BEACH CODE, BUILDING ADDRESS
 NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND 1" IN
 WIDTH

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-10-25 Cont ID  
Sent By mcarsill Date 2006-10-25 Time 07:35 Rev Time 0.00
Received By mcarsill Date 2006-10-25 Time 07:35 Sent To  
Notes
2006-10-25 07:39:041) EXIT SIGNAGE AND EMERGENCY LIGHTING NEEDED FOR
 MEZZANINE AREA.
 2) PORTABLE FIRE EXTINGUISHERS THAT ARE CURRENTLY
 SERVICE TAGGED AND MOUNTED SHALL BE PROVIDED
 THROUGHOUT.
 3) SUBJECT TO FIELD INSPECTION AND APPROVAL.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION OFFICER 804-4709

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-06-16 Cont ID  
Sent By mcarsill Date 2006-06-16 Time 11:00 Rev Time 0.00
Received By mcarsill Date 2006-10-25 Time 07:34 Sent To  
Notes
2006-06-16 00:00:001. DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2. DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY.
  
 3. GASOLINE POWERED DEMOLITION EQUIPMENT
 SHALL NOT BE USED WITHOUT PROPER
 VENTILATION TO PREVENT CARBON MONOXIDE
 BUILD-UP OF VAPORS.
  
 4. ADDITIONAL EXIT SIGNS APPEAR TO BE
 NEEDED TO DIRECT PERSONS TO EXITS THAT
 ARE BEYOND CORNERS AND ROOMS.
  
 5. NEW STAIRS UP SHALL MEET MINIMUM CODE
 REQUIREMENTS. ANY HANDRAILS AND
 GUARDRAILS SHALL COMPLY WITH THE
 PRESCRIPTIVE STRENGTH REQUIREMENTS.
  
 6. THE MEZZANINE IS TO BE USED FOR WHAT
 PURPOSES. PLEASE INDICATE THE PURPOSE ON
 THE PLANS.
  
 7. PLEASE REVIEW DOORS SWINGS FOR
 RESTROOMS THAT OPEN ONTO THE CORRIDOR
 PROVIDING ACCESS TO THEM.
  
 8. ENSURE THAT THE EXISTING ADDRESS
 DISPLAYEED ON PAGE 6A MEETS MINIMUM CODE
 REQUIREMENTS OF AT LEAST 6" HIGH WITH
 THE PROPER WIDTH STROKE.
  
 9. FLOOR PLANS DOES NOT ILLUSTRATE ANY
 NEW OR EXISTING PORTABLE FIRE
 EXTINGUISHERS. PLEASE DISPLAY.
  
 10. PLEASE INDICATE INTERIOR FINISH FOR
 WALLS AND CEILINGS.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop HIST HISTORICAL
Rev No 1 Status P Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2006-05-16 00:00:00OK PER F MITNER NO FEE

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-12-10 Cont ID  
Sent By adarroug Date 2007-12-10 Time 09:27 Rev Time 0.00
Received By adarroug Date 2007-12-10 Time 09:27 Sent To  
Notes
2007-12-10 09:28:08TO "COMM" BD#16

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-10-03 Cont ID  
Sent By adarroug Date 2007-10-03 Time 17:36 Rev Time 0.00
Received By adarroug Date 2007-10-03 Time 17:36 Sent To  
Notes
2007-10-25 15:05:16TO "COMM" BD#18
2007-10-03 17:37:08WAITING FOR "COMM" BD-REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-08-08 Cont ID  
Sent By mmiller Date 2007-08-08 Time 18:55 Rev Time 0.00
Received By mmiller Date 2007-08-08 Time 18:55 Sent To  
Notes
2007-09-07 16:02:10TO "COMM" BD#29
2007-08-08 18:55:45WAITING FOR COMMERCIAL BOARD

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-03-26 Cont ID  
Sent By mmiller Date 2007-03-26 Time 18:43 Rev Time 0.00
Received By mmiller Date 2007-03-26 Time 18:41 Sent To  
Notes
2007-03-26 18:43:41SENT TO ZONING MMILLER

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-02-06 Cont ID  
Sent By adarroug Date 2007-02-06 Time 13:44 Rev Time 0.00
Received By adarroug Date 2007-02-06 Time 13:44 Sent To  
Notes
2007-02-13 14:40:43TO "COMM" BD#57
2007-02-06 13:44:18WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status   Date 2006-11-29 Cont ID  
Sent By mmiller Date 2006-11-29 Time 19:40 Rev Time 0.00
Received By mmiller Date 2006-11-29 Time 19:40 Sent To  
Notes
2006-12-13 14:47:53TO "COMM" BD#23
2006-11-29 19:40:49WAITING FOR COMMERCIAL BOARD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-22 Cont ID  
Sent By adarroug Date 2006-09-22 Time 10:59 Rev Time 0.00
Received By adarroug Date 2006-09-22 Time 10:59 Sent To  
Notes
2006-10-11 14:52:38TO "COMM" BD#60
2006-09-22 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-27 Cont ID  
Sent By adarroug Date 2006-07-27 Time 16:58 Rev Time 0.00
Received By adarroug Date 2006-05-18 Time 15:48 Sent To  
Notes
2006-06-01 00:00:00TO "COMM" BD#11
2006-05-18 00:00:00**THIS IS NOT A "BOB" APPLICATION PER
 "RBROWN"
 WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-11-01 Cont ID  
Sent By tgordon Date 2007-11-01 Time 08:10 Rev Time 0.20
Received By tgordon Date 2007-11-01 Time 08:10 Sent To  
Notes
2007-11-01 08:11:26REVISED MECH. PLANS PAGE 17 AND 18. REVIEWED AND
 APPROVED 9-11-07.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-12-21 Cont ID  
Sent By tgordon Date 2006-12-21 Time 14:34 Rev Time 0.25
Received By tgordon Date 2006-12-21 Time 14:34 Sent To  
Notes
2006-12-17 14:53:43NEW SHEETS IN SETS

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-10-12 Cont ID  
Sent By tgordon Date 2006-10-12 Time 09:38 Rev Time 0.45
Received By tgordon Date 2006-10-12 Time 09:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-06-23 Cont ID  
Sent By tgordon Date 2006-06-23 Time 13:35 Rev Time 0.45
Received By tgordon Date 2006-06-23 Time 13:35 Sent To  
Notes
2006-06-23 00:00:00*** DENIED ***
 1) AHU #1 SHOW SIZE OF MAIN RETURN AIR
 DUCT TO 42"X24" R.A. GRILL IN MEZZANINE.
  
 2) AHU #2 SHOW SIZE OF MAIN RETURN AIR
 DUCT FROM AHU TO 12"X8" DUCTS.
  
 3) AHU #3 SUPPLY AIR TO OFFICE CAN NOT
 RETURN TO AHU #1, 10'X10" TRANSFER GRILL
 DOES NOT OPEN TO AHU #3 ZONE.
  
 4) A/C SUPPLY AIR DUCT AND RETURN AIR
 TRANSFER GRILL GOING TO LOBBY ARE
 PENETRATING A FIRE RATED WALL, AND
 REQUIRE FIRE DAMPERS, PER 2004 FBC/M 607
  
 5) SEE BUILDING REVIEW NOTES #23 & #24.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-09-22 Cont ID  
Sent By kstevens Date 2007-09-22 Time 05:58 Rev Time 0.00
Received By kstevens Date 2007-09-21 Time 18:52 Sent To  
Notes
2007-09-22 05:59:11REVISION OK--SHT 19

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-01-23 Cont ID  
Sent By kstevens Date 2007-01-23 Time 17:29 Rev Time 0.00
Received By kstevens Date 2007-01-23 Time 17:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-10-28 Cont ID  
Sent By pschmitz Date 2006-10-28 Time 13:28 Rev Time 0.00
Received By pschmitz Date 2006-10-28 Time 12:44 Sent To  
Notes
2006-10-28 14:02:03PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
 UNSAT
 NEW COMMENT, SAYING WILL COMPLY, IS NOT ACCEPTABLE,
 PROVIDE THE INFORMATIOIN ON THE PLANS.
  
 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL (SEE ALSO SECTION
 106.3.5).
  
  
 1) INCLUDE NOTE BELOW ONSHT 2. DEMOLITION
 SEC 704.5DEAD ENDS.IN THE INSTALLATION
 OR REMOVAL OF ANY PART OF THE DRAINAGE
 SYSTEM, DEAD ENDS SHALL BE PROHIBITED.
  
 2) PROVIDE THE INFORMATION AS REQUIRED FOR EACH
 SEPERATE OCCUPANCY, (SPACE #1,#2)
 SHT 3. SEC 403.1MINIMUM NUMBER OF
 PLUMBING FIXTURES SHALL BE PROVIDED FOR
 THEOCCUPANT LOAD BASED ON TABLE 403.1
  
 3) DOOR SWINGS IN CLEAR FLOOR SPACE FOR D/F BY UNISEX
 REST RM.
 SHT 3.SEC 410.1 DRINKING FOUNTAIN
  
 4) COMPLIED
 SHT 3. SEC 11-4.1.3 PRIVATE TOILET ROOM(DELETED)
  
 5) SHOWDIMENSIONS FOR FIXTURES OFF WALLS
 SHT 3 SEC 11-4.22, UNISEX TOILET
 ROOM, EACH PUBLIC AND COMMON USE TOILET
 ROOM SHALL COMPLY WITH SEC 11-4.1.3
  
 6) SHT 5. ROOF PLAN: COMPLIED
  
 7) SHT 19 SEC 606.1 (4) FULLY OPEN VALVES, COMPLIED
  
 END OF COMMENTS QUESTIONS 561-805-6692

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-07-01 Cont ID  
Sent By pschmitz Date 2006-07-01 Time 10:38 Rev Time 0.00
Received By pschmitz Date 2006-07-01 Time 10:26 Sent To  
Notes
2006-07-01 00:00:00PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
 UNSAT
  
 1) SHT 2. DEMOLITION
 SEC 704.5DEAD ENDS.IN THE INSTALLATION
 OR REMOVAL OF ANY PART OF THE DRAINAGE
 SYSTEM, DEAD ENDS SHALL BE PROHIBITED.
  
 2) SHT 3. SEC 403.1MINIMUM NUMBER OF
 PLUMBING FIXTURES SHALL BE PROVIDED FOR
 THEOCCUPANT LOAD BASED ON TABLE 403.1
  
 3) SHT 3.SEC 410.1 DRINKING FOUNTAIN
 REQUIRED. BOTTLED WATER DISPENSER SHALL
 BE PERMITTED, FOR NOT MORE THAN 50% OF
 REQUIRED DRINKING FOUNTAINS.
  
 4) SHT 3. SEC 11-4.1.3 PRIVATE TOILET
 ROOM FOR THE OCCUPANT OF A PRIVATE
 OFFICE, SHALL BE ADAPTABLE.
  
 5) SHT 3 SEC 11-4.22, UNISEX TOILET
 ROOM, EACH PUBLIC AND COMMON USE TOILET
 ROOM SHALL COMPLY WITH SEC 11-4.1.3
  
 6) SHT 5. ROOF PLAN: SEC 1106 PROVIDE
 THE CALCULATIONS FOR THE PRIMARY AND
 SECONDARY ROOF DRAINAGE.
 TABLE 1106.2,1106.3 AND 1106.7
 PROVIDE AN ISOMETRIC DRAWING ALL PIPE
 SIZES. INCLUDE POINT OF DISPOSAL.
  
 7) SHT 19 SEC 606.1 (4) FULLY OPEN
 VALVES SHALL BE INSTALLEDON THE TOP OF
 EVERY WATER DOWN FEED PIPE.
  
 END OF COMMENTS QUESTIONS 561-805-6692

Review Stop Z ZONING
Rev No 8 Status P Date 2007-12-11 Cont ID  
Sent By kdfreema Date 2007-12-11 Time 10:46 Rev Time 0.00
Received By kdfreema Date 2007-12-11 Time 10:46 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 7 Status F Date 2007-11-06 Cont ID  
Sent By kdfreema Date 2007-11-06 Time 14:49 Rev Time 0.00
Received By kdfreema Date 2007-11-06 Time 14:49 Sent To  
Notes
2007-11-06 14:50:25***FAILED***
  
 PLEASE RECONFIGURE PARKING CONFIGURATION AS DISCUSSED
 11/6/07.

Review Stop Z ZONING
Rev No 6 Status F Date 2007-09-25 Cont ID  
Sent By kdfreema Date 2007-09-25 Time 09:38 Rev Time 0.00
Received By kdfreema Date 2007-09-19 Time 13:12 Sent To  
Notes
2007-09-19 13:12:57***FAILED***
  
 1. THE DUMPSTER ENCLOSURE SHALL REMAIN. SECTION 94-444
 OF THE ZONING AND LAND DEVELOPMENT REGULATIONS REQUIRES
 GARBAGE AND TRASH RECEPTACLES TO BE SCREENED.
  
 2. PLEASE UPDATE THE SITE DATA TABLE TO REFLECT THE
 CHANGES IN SCOPE OF WORK.
  
 3. PLEASE CLARIFY THE SITUATION WITH THE HANDICAP
 PARKING. THE AREA WHERE THE HANDICAP PARKING SPACES ARE
 CURRENTLY LOCATED IS SLATED TO BECOME LANDSCAPING.
 WHERE ARE THESE SPACES BEING MOVED?
  
 4. AS THE SPACES ON THE SOUTH SIDE OF THE BUILDING ARE
 BEING REMOVED, THEY MUST BE ACCOUNTED FOR ELSEWHERE ON
 THE PROPERTY.
  
 5. PLEASE SUBMIT A REVISED LANDSCAPE PLAN REFLECTING
 THE CHANGES IN THE SCOPE OF WORK. PLEASE NOTE AS THE
 PERMIT VALUE REMAINS IN EXCESS OF 50% OF THE VALUE OF
 THE STRUCTURE, THE LANDSCAPING MUST BE BROUGHT UP TO
 CODE.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1435
 OR [email protected] WITH QUESTIONS.

Review Stop Z ZONING
Rev No 5 Status P Date 2007-03-27 Cont ID  
Sent By kdfreema Date 2007-03-27 Time 08:56 Rev Time 0.00
Received By kdfreema Date 2007-03-27 Time 08:56 Sent To  
Notes
2007-03-27 09:00:16PROVISO: PARKING DETAIL SHOWN ON SITE PLAN SHALL
 PREVAIL OVER PARKING DETAILS SHOWN ON THE CIVIL
 ENGINEERING PLANS.

Review Stop Z ZONING
Rev No 4 Status F Date 2007-02-23 Cont ID  
Sent By kdfreema Date 2007-02-23 Time 10:24 Rev Time 0.00
Received By kdfreema Date 2007-02-23 Time 10:24 Sent To  
Notes
2007-02-23 10:25:11**FAILED**
  
 1) THE PERMIT DOCUMENTATION FROM FDOT MAKES NO MENTION
 OF ON-STREET PARKING SPACES, ADDITIONALLY; THE PLANS
 STAMPED BY FDOT DO NOT SHOW THE PROPOSED PARKING
 SPACES. WRITTEN PERMISSION MUST BE PROVIDED FROM FDOT
 TO ALLOW THE ON-STREET PARKING SPACES.
  
 2) THE PERIMETER LANDSCAPE REQUIREMENT IS NOT MET. ALL
 PERIMETER TREES MUST BE PLANTED WITHIN 5 FEET OF THE
 PROPERTY LINE TO SATISFY THIS REQUIREMENT.
  
 3) A MAXIMUM OF 35% OF THE PERIMETER TREES REQUIRED MAY
 BE SUBSTITUTED WITH PALM TREES. YOU?RE ALLOWED 7 PALMS
 MAXIMUM AND THE PLANS SHOW 8 PALMS.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1435
 WITH ANY QUESTIONS.

Review Stop Z ZONING
Rev No 3 Status F Date 2007-01-17 Cont ID  
Sent By kdfreema Date 2007-01-17 Time 08:46 Rev Time 0.00
Received By kdfreema Date 2007-01-17 Time 08:46 Sent To  
Notes
2007-01-17 08:51:04**FAILED**
  
 1) REGARDING THE ON-STREET PARKING SPACES, NO APPROVAL
 HAS BEEN PROVIDED BY EITHER THE CITY?S ENGINEERING
 DEPARTMENT OR FDOT. THE APPLICANT MUST PROVIDE BOTH IN
 WRITING AT THE TIME OF RESUBMISSION TO SATISFY THIS
 REQUIREMENT.
  
 2) ALL IMPROVEMENTS SHOWN ON THE SITE PLAN SHALL BE
 SHOWN ON THE LANDSCAPE PLAN.
  
 3) A HEDGE MUST BE PLANTED ALONG THE EASTERN PROPERTY
 BOUNDARY. BOTH A WALL (WHICH CURRENTLY EXISTS) AND A
 HEDGE ARE REQUIRED ALONG THAT BOUNDARY.
  
 4) THE PERIMETER LANDSCAPE REQUIREMENT IS NOT MET. TO
 COUNT TOWARD MEETING THE REQUIREMENT, THE TREES MUST BE
 PLANTED WITHIN THE 5 FOOT LANDSCAPE BUFFER.
  
 5) THE PERIMETER LANDSCAPE BUFFER MUST CONTAIN EITHER
 SHADE TREES OR FLOWERING TREES. THE FOXTAIL PALMS SHOWN
 ON THE PLAN DO NOT SATISFY THIS REQUIREMENT.
  
 6) A MAXIMUM OF 35% OF THE PERIMETER TREES REQUIRED MAY
 BE SUBSTITUTED WITH PALM TREES. PLEASE REFER TO SECTION
 94-442(C) FOR MORE DETAILS.
  
 7) PLEASE PROVIDE A DATA TABLE ON THE LANDSCAPE PLAN
 SHOWING PERVIOUS/IMPERVIOUS AREAS AS WELL AS OPEN SPACE
 SQUARE FOOTAGE. PLEASE PROVIDE AN ADDITIONAL TABLE
 SHOWING HOW THE PLANTS PROVIDED COMPARE TO WHAT IS
 REQUIRED BY CODE. PLEASE SEE SECTION 94-448(D)(2) FOR
 MORE INFORMATION RELATING TO THE ITEMS REQUIRED TO BE
 SHOWN ON A LANDSCAPE PLAN.
  
 8) SOME OF THE PLANTS PROPOSED TO NOT MEET MINIMUM
 SIZE/HEIGHT STANDARDS. PLEASE REFER TO SECTION 94-445
 FOR INFORMATION ON PLANT MATERIAL STANDARDS AND
 SPECIFICATIONS.
  
 9) PLEASE SHOW POWER LINES ON LANDSCAPE PLAN.
  
 10) REPLACE TWO THE WESTERN-MOST LIVE OAK TREES ALONG
 NORTH PROPERTY LINE AND LIVE OAKS IN TERMINAL ISLANDS
 WITH SMALLER TREES, THERE IS NOT ENOUGH ROOM FOR THEM.
  
 11) PLEASE INDICATE WHICH PLANTS ARE DROUGHT TOLERANT.
  
 12) FOR FOXTAILS PLEASE CLARIFY HEIGHT, PLANS SHOW 12'
 HEIGHT AND 12' CLEAR TRUNK.
  
 13) PLEASE ADJUST PLANTING DIAGRAMS TO REFLECT THOSE
 FOUND ON THE CITY'S WEBSITE:
 HTTP://WWW.WPB.ORG/PLAN/SUGGESTEDTREELIST.PDF
  
 14) ADD THE FOLLOWING VERBIAGE TO THE LANDSCAPE PLAN:
 LANDSCAPE INSTALLER SHALL CHECK ALL CONTAINERIZED
 MATERIAL FOR CIRCLING ROOTS. REJECT MATERIAL OR CUT
 ROOTS PER THE FLORIDA DEPARTMENT OF AGRICULTURE
 APPROVED GRADES AND STANDARDS.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1435
 WITH ANY QUESTIONS.

Review Stop Z ZONING
Rev No 2 Status F Date 2006-10-31 Cont ID  
Sent By kdfreema Date 2006-10-31 Time 15:28 Rev Time 0.00
Received By kdfreema Date 2006-10-31 Time 15:28 Sent To  
Notes
2006-10-31 15:31:581. A LANDSCAPE PLAN IS REQUIRED TO BE SUBMITTED BEFORE
 THE ISSUANCE OF A BUILDING PERMIT.
  
 2. ON-STREET PARKING SHALL BE APPROVED BY THE CITY'S
 ENGINEERING DEPARTMENT AND FDOT.
  
 3. A LETTER FROM THE CITY SANITATION DEPARTMENT MUST BE
 PROVIDED APPROVING THE LOCATION OF THE DUMPSTER.
  
 4. ALL LANDSCAPED AREAS MUST BE PROTECTED BY WHEEL
 STOPS OR D CURB. THERE IS NOTHING SHOWN IN THE BUMPOUT
 AREAS TO PROTECT THE LANDSCAPING FROM INTRUSION.
  
 5. PLEASE REMOVE ANY OLD/VOIDED SHEETS FROM SETS AND
 INSERT ONLY THE NEW SHEETS. ONE COPY OF THE OLD/VOIDED
 REMOVED SHEETS SHOULD ACCOMPANY THE NEW SETS FOR
 REFERENCE.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, WITH ANY
 QUESTIONS YOU HAVE. 822-1435

Review Stop Z ZONING
Rev No 1 Status F Date 2006-07-27 Cont ID  
Sent By kdfreema Date 2006-07-27 Time 14:21 Rev Time 0.00
Received By kdfreema Date 2006-07-27 Time 14:21 Sent To  
Notes
2006-07-27 00:00:001810 S DIXIE HIGHWAY:
  
 1. PLEASE PROVIDE A LANDSCAPE PLAN FOR
 THE PROPERTY, A LANDSCAPE PLAN IS
 REQUIRED AND MUST BE SIGNED AND SEALED
 BY A REGISTERED LANDSCAPE ARCHITECT.
  
 2. HOW WILL BIKE RACK BE CONFIGURED?
 PLEASE PROVIDE DETAILS.
  
  
 3. THE THREE SPACES ON THE SOUTH SIDE OF
 THE BUILDING MUST BE RELOCATED. BACKING
 ONTO THE PUBLIC RIGHT-OF-WAY IS NOT
 ALLOWED.
  
 4. DUMPSTER ENCLOSURE DOES NOT MEET
 MINIMUM DIMENSIONS.
  
 5. DUMPSTER ENCLOSURES MUST BE
 LANDSCAPED ON THREE SIDES BY SHRUBS OR
 HEDGES PLACED AT A 2? ON-CENTER
 INTERVAL.
  
 6. A LETTER FROM THE CITY SANITATION
 DEPARTMENT MUST BE SUPPLIED APPROVING
 THE LOCATION OF THE DUMPSTER.
  
 7. ALL LANDSCAPED AREAS MUST BE
 PROTECTED BY WHEEL STOPS OR CONCRETE ?D?
 CURBING.
  
 8. SHOW LOADING ZONE DETAIL. THE LOADING
 ZONE MUST BE DEMARCATED BY SIGNAGE OR
 STRIPING.
  
 9. A 5? SCREEN WALL IS REQUIRED ALONG
 THE EAST LOT LINE ABUTTING THE
 RESIDENTIAL USE.
  
 10. IS MEZZANINE SQUARE FOOTAGE INCLUDED
 IN THE PARKING REQUIREMENT? PLANS ARE
 UNCLEAR IN THAT RESPECT. PARKING
 REQUIREMENTS MUST BE CALCULATED USING
 FINISHED SQUARE FOOTAGES.
  
 11. WHEEL STOPS MUST BE 2? FROM FRONT
 EDGE OF PARKING SPACE.
  
 12. PARKING AND STRIPING DETAILS WITH
 DIMENSIONS MUST BE SHOWN.
  
 13. HANDICAP SPACE DOES NOT MEET MINIMUM
 DIMENSIONS.
  
 14. ENSURE THAT ALL REGULAR PARKING
 SPACES MEET THE MINIMUM DIMENSIONS.
  
 15. WILL PARKING LOT LIGHTING BE
 PROVIDED? IF SO, A PHOTOMETRIC PLAN IS
 REQUIRED.
  
 16. A VICINITY MAP SHOWING THE PROPERTY
 IN RELATION ITS SURROUNDINGS IS
 REQUIRED.
  
 17. PLEASE SHOW EASEMENTS AND THEIR
 CLASSIFICATIONS ON THE SITE PLAN.
  
 18. A DATA TABLE MUST BE PROVIDED TO
 INCLUDE THE FOLLOWING:
 A. EXISTING AND PROPOSED LAND USE.
 B. TOTAL PROJECT ACREAGE.
 C. TOTAL GROSS BUILDING SQUARE FOOTAGE.
 D. PERCENT OF OPEN SPACE, LANDSCAPING,
 BUILDING COVERAGE, AND IMPERMEABLE
 SURFACE.
 E. DENSITY AND NUMBER OF DWELLING UNITS.
 F. PARKING COMPUTATIONS (PARKING
 REQUIRED, PROVIDED, ETC.)
 G. FLOOR AREA RATIO (FAR).
  
 19. A MAXIMUM OF 25% OF THE BUFFER STRIP
 ALONG THE SOUTH LOT LINE MAY BE
 INTERRUPTED, PLANS SHOW 33% OF THE
 BUFFER STRIP INTERRUPTED. NOTE: THE 33%
 DOES NOT INCLUDE THE INTERRUPTION CAUSED
 BY THE 3 PARKING SPACES WHICH MUST BE
 RELOCATED.