Plan Review Details - Permit 06050593
Plan Review Stops For Permit 06050593
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-01-24 Cont ID  
Sent By lmartine Date 2007-01-24 Time 17:31 Rev Time 0.00
Received By lmartine Date 2007-01-24 Time 17:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-10-03 Cont ID  
Sent By jleech Date 2007-01-24 Time 13:02 Rev Time 1.50
Received By alange Date 2006-10-03 Time 09:27 Sent To  
Notes
2006-10-03 00:00:00DENIED
  
  
  
 4.SUBMIT TWO COPIES OF ENERGY CALCS
 PER 2004 FBC.SEE MECHANICAL REVIEW
 NOTES.
  
 5.PRODUCT APPROVALS REQUIRED FOR
 STRAPS AND TIE-DOWNS.
  
 6.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 7.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 8.SUBMIT TWO SETS OF TRUSS DRAWINGS
 FOR REVIEW PER 2004 FBC R-802.10.1
 TRUSS DRAWING REQUIRED TO BE APPROVED
 PRIOR TO INSTALLATION.
  
  
 9.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 10.R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A
 STORM SEWER CONVEYANCE OR OTHER APPROVED
 POINT OF COLLECTION SO AS TO NOT CREATE
 A HAZARD. LOTS SHALL BE GRADED SO AS TO
 DRAIN SURFACE WATER AWAY FROM FOUNDATION
 WALLS. THE GRADE AWAY FROM FOUNDATION
 WALLS SHALL FALL A MINIMUM OF 6 INCHES
 WITHIN THE FIRST 10 FEET.
  
 12.SAFTEY GLAZING REQUIRED FOR WINDOW
 AT TUB LOCATION.R308.4
  
 13.SHOW SIZE AND LOCATION OF ATTIC
 ACCESS.R-807.1
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-06-12 Cont ID  
Sent By alange Date 2006-06-12 Time 09:04 Rev Time 2.00
Received By alange Date 2006-06-12 Time 09:01 Sent To  
Notes
2006-06-12 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.BASED ON ICC BUILDING VALUATION DATA
 THE PERMIT VALUE HAS BEEN REVISED TO
 $63,837.00.ADDITIONAL PERMIT FEES ARE
 DUE.
  
 4.SUBMIT TWO COPIES OF ENERGY CALCS
 PER 2004 FBC.
  
 5.PRODUCT APPROVALS REQUIRED FOR
 SINGLE HUNG WINDOWS, LINTELS, SHUTTERS
 AND STRAPS AND TIE-DOWNS.
  
 6.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 7.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 8.SUBMIT TWO SETS OF TRUSS DRAWINGS
 FOR REVIEW PER 2004 FBC R-802.10.1
  
 9.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 10.R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A
 STORM SEWER CONVEYANCE OR OTHER APPROVED
 POINT OF COLLECTION SO AS TO NOT CREATE
 A HAZARD. LOTS SHALL BE GRADED SO AS TO
 DRAIN SURFACE WATER AWAY FROM FOUNDATION
 WALLS. THE GRADE AWAY FROM FOUNDATION
 WALLS SHALL FALL A MINIMUM OF 6 INCHES
 WITHIN THE FIRST 10 FEET.
  
 11. SUBMIT TWO ORIGONAL SIGNED AND
 SEALED SURVEYS.FS 472.025
  
 12.SAFTEY GLAZING REQUIRED FOR WINDOW
 AT TUB LOCATION.R308.4
  
 13.SHOW SIZE AND LOCATION OF ATTIC
 ACCESS.R-807.1
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-01-02 Cont ID  
Sent By btrobaug Date 2007-01-02 Time 15:10 Rev Time 0.50
Received By btrobaug Date 2006-09-11 Time 12:02 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-06-02 Cont ID  
Sent By btrobaug Date 2006-06-02 Time 12:42 Rev Time 0.50
Received By btrobaug Date 2006-06-02 Time 12:23 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-12-29 Cont ID  
Sent By adarroug Date 2006-12-29 Time 09:49 Rev Time 0.00
Received By adarroug Date 2006-12-29 Time 09:49 Sent To E
Notes
2006-12-29 09:50:07TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-12-21 Cont ID  
Sent By adarroug Date 2006-12-21 Time 11:25 Rev Time 0.00
Received By adarroug Date 2006-12-21 Time 11:25 Sent To Z
Notes
2006-12-21 11:26:08TO "Z" BOX/RESUB--NEW SHEETS FOR ALL TRADES

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-09-08 Cont ID  
Sent By adarroug Date 2006-09-08 Time 18:04 Rev Time 0.00
Received By adarroug Date 2006-09-08 Time 18:04 Sent To E
Notes
2006-09-08 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-05-31 Cont ID  
Sent By adarroug Date 2006-05-31 Time 14:29 Rev Time 0.00
Received By adarroug Date 2006-05-31 Time 14:28 Sent To E
Notes
2006-05-31 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-12 Cont ID  
Sent By alange Date 2006-06-12 Time 09:10 Rev Time 0.00
Received By alange Date 2006-05-16 Time 09:44 Sent To  
Notes
2006-05-16 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-03-06 Cont ID  
Sent By tgordon Date 2007-03-06 Time 08:41 Rev Time 0.30
Received By tgordon Date 2007-03-06 Time 08:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-01-03 Cont ID  
Sent By jleech Date 2007-01-24 Time 13:01 Rev Time 0.30
Received By tgordon Date 2007-01-03 Time 08:15 Sent To P
Notes
2007-01-03 08:29:04*** DENIED ***
 1) AS NOTED IN LAST TWO REVIEWS 6-7-06 AND 9-12-06,
 ENERGY CALCULATIONS MAY NOT BE ON FORM 600C-01 AS THE
 ADDITION IS OVER 600 SQUARE FEET SEE PLANS. THE ENERGY
 CALCULATIONS WILL NEED TO BE ON FORM 600A-04 (2004),
 PER FBC 13-600.3.A .
  
 2) A/C DUCT DESIGN WILL NOT WORK AS DRAWING ON
 MECHANICAL PLANS, PLEASE CORRECT.
  
 3) NEED TO SHOW THE CFM'S AT EACH SUPPLY AIR GRILL.
  
 4)SEE ATTACHED NOTICE FS 553.80(2)(B)
 REGARDING FOUR TIMES THE FEE (IN REFERENCE TO NOTE
 #1).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-09-12 Cont ID  
Sent By tgordon Date 2006-09-12 Time 09:50 Rev Time 0.30
Received By tgordon Date 2006-09-12 Time 09:50 Sent To P
Notes
2006-09-12 00:00:00*** DENIED ***
 *** AS NOTED IN LAST REVIEW 6-7-06 ***
 1) ENERGY CALCULATIONS CAN NOT BE DONE
 ON FORM 'C' AS THE ADDITION IS OVER 600
 SQ. FEET. PER 2004 FBC 13-600.3.C .
  
 2) ENERGY CALCULATIONS NEED TO BE ON
 FORM 600A OR B -04 (2004) PER FBC
 13-600.3.A .
  
 3) A/C PLANS SUBMITTED ARE FOR AN
 ADDITION DONE LAST YEAR, PLEASE SUBMIT
 A/C PLANS FOR THIS ADDITION (MASTER
 BEDROOM).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-06-07 Cont ID  
Sent By tgordon Date 2006-06-07 Time 13:38 Rev Time 0.45
Received By tgordon Date 2006-06-07 Time 13:38 Sent To B
Notes
2006-06-07 00:00:00*** DENIED ***
 1) ENERGY CALCULATIONS CAN NOT BE DONE
 ON FORM 'C' AS THE ADDITION IS OVER 600
 SQ. FEET. PER 2004 FBC 13-600.3.C .
  
 2) ENERGY CALCULATIONS NEED TO BE ON
 FORM 600A OR B -04 (2004) PER FBC
 13-600.3.A .
  
 3) A/C PLANS SUBMITTED ARE FOR AN
 ADDITION DONE LAST YEAR, PLEASE SUBMIT
 A/C PLANS FOR THIS ADDITION.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-01-24 Cont ID  
Sent By jleech Date 2007-01-04 Time 09:36 Rev Time 0.00
Received By jleech Date 2007-01-04 Time 09:36 Sent To B
Notes
2007-01-04 09:47:51DENIED;
 1. PLANS TO SIGNED BY PERSON THAT IS RESPONSIBLE FOR
 PLANS NOT A PHOTOCOPY.
 2. NO PLUMBING RISER DIAGRAM SHOWN ON PLANS. PAGE5 OF
 5 WAS NOT SUBMITED WITH NEW PLANS
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-10-02 Cont ID  
Sent By jleech Date 2006-10-02 Time 14:05 Rev Time 0.00
Received By jleech Date 2006-10-02 Time 14:05 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-01-24 Cont ID  
Sent By jleech Date 2006-06-06 Time 17:30 Rev Time 0.00
Received By jleech Date 2006-06-06 Time 17:30 Sent To B
Notes
2006-06-06 00:00:00 
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2007-01-24 Cont ID  
Sent By mmclean Date 2007-01-24 Time 14:06 Rev Time 0.00
Received By mmclean Date 2007-01-24 Time 14:06 Sent To  
Notes
2007-01-24 14:07:23APPROVED PLANS DATED 5/30/06 (FULL SET)

Review Stop Z ZONING
Rev No 2 Status F Date 2006-12-27 Cont ID  
Sent By mmclean Date 2006-12-27 Time 17:28 Rev Time 0.00
Received By mmclean Date 2006-12-27 Time 17:28 Sent To I
Notes
2006-12-27 17:30:55DENIED,
 1. NEW SETS OF PLANS DOES NOT HAVE ELEVATIONS PLANS.
 2. PLEASE SUBMIT TWO COPIES OF ELEVATIONS PLANS SHOWING
 THE EXISTING STRUCTURE AND PROPOSED ADDITION.
 3. PLANS ARE NOT SIGNED AND SEALED (COPIES).
  
  
 NOTE: NO STRUCTURE ON EXISTING CONCRETE SLAB IN REAR OF
 PROPERTY.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status P Date 2006-05-30 Cont ID  
Sent By mmclean Date 2006-05-30 Time 16:42 Rev Time 0.00
Received By mmclean Date 2006-05-30 Time 16:42 Sent To I
Notes
***NONE***