Plan Review Details - Permit 06050590
Plan Review Stops For Permit 06050590
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-02-27 Cont ID  
Sent By jwitmer Date 2007-02-27 Time 15:54 Rev Time 0.77
Received By jwitmer Date 2007-02-27 Time 15:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-09-15 Cont ID  
Sent By jwitmer Date 2006-09-15 Time 11:24 Rev Time 0.55
Received By jwitmer Date 2006-09-15 Time 11:24 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-06-02 Cont ID  
Sent By jwitmer Date 2006-06-02 Time 09:32 Rev Time 0.77
Received By jwitmer Date 2006-06-02 Time 09:32 Sent To  
Notes
2006-06-02 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06050590
 ADD: 250 S AUSTRALIAN AVE
 CONT: PROTON ELECTRIC
 TEL: (561)543-6671
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) GENERATOR SLAB & ANCHOR REQUIREMENT
 PLEASE PROVIDE SIZE OF GENERATOR(WXL),
 PLUS PROVIDE PLANS WITH THE INFORMATION
 DEPICTING HOLD DOWN BRACKETS, TYPE OF
 FASTENER, AND THE MINIMUM EDGE DISTANCE
 THE DEVICE REQUIRES WITHOUT LOAD
 REDUCTION.
 SECOND, PROVIDE INFORMATION ON THE
 SLAB, THICKNESS, WIDTH AND LENGTH, IF
 WIREMESH, FIBER MESH OR IF STEEL REBAR
 WILL BEUSED.
 THE NEW SLAB AND HOLD DOWN DETAILS:
 104.2.1* ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
  
 2) PLANS DO NOT INDICATE LOCATION OF
 GENERATOR AND RELATIONSHIP TO THE REST
 OF THE STRUCTURE OR STRUCTURES WITHIN
 10' OF GENERATOR.
 PROVIDE PLANS ENOUGH TO VERIFY LOCATION
 OF GENERATOR VERSES BUILDING OPENINGS
 WINDOWS, DOORS OR SOFFIT TYPE VENTS,
 ETC.
  
 MECHANICAL CODE
 804.3.4 HORIZONTAL TERMINATIONS.
 HORIZONTAL TERMINATIONS SHALL COMPLY
 WITH THE FOLLOWING REQUIREMENTS:
 1.WHERE LOCATED ADJACENT TO
 WALKWAYS, THE TERMINATION OF MECHANICAL
 DRAFT SYSTEMS SHALL BE NOT LESS THAN 7
 FEET (2134 MM) ABOVE THE LEVEL OF THE
 WALKWAY.
 2.VENTS SHALL TERMINATE AT LEAST 3
 FEET (914 MM) ABOVE ANY FORCED AIR INLET
 LOCATED WITHIN 10 FEET (3048 MM).
 3.THE VENT SYSTEM SHALL TERMINATE
 AT LEAST 4 FEET (1219 MM) BELOW, 4 FEET
 (1219 MM) HORIZONTALLY FROM OR 1 FOOT
 (305 MM) ABOVE ANY DOOR, WINDOW OR
 GRAVITY AIR INLET INTO THE BUILDING.
 4.THE VENT TERMINATION POINT SHALL
 NOT BE LOCATED CLOSER THAN 3 FEET (914
 MM) TO AN INTERIOR CORNER FORMED BY TWO
 WALLS PERPENDICULAR TO EACH OTHER.
 5.THE VENT TERMINATION SHALL NOT BE
 MOUNTED DIRECTLY ABOVE OR WITHIN 3 FEET
 (914 MM) HORIZONTALLY FROM AN OIL TANK
 VENT OR GAS METER.
 6.THE BOTTOM OF THE VENT
 TERMINATION SHALL BE LOCATED AT LEAST 12
 INCHES (305 MM) ABOVE FINISHED GRADE.
  
 804.3.5 VERTICAL TERMINATIONS.
 VERTICAL TERMINATIONS SHALL COMPLY WITH
 THE FOLLOWING REQUIREMENTS:
 1.WHERE LOCATED ADJACENT TO
 WALKWAYS, THE TERMINATION OF MECHANICAL
 DRAFT SYSTEMS SHALL BE NOT LESS THAN 7
 FEET (2134 MM) ABOVE THE LEVEL OF THE
 WALKWAY.
 2.VENTS SHALL TERMINATE AT LEAST 3
 FEET (914 MM) ABOVE ANY FORCED AIR INLET
 LOCATED WITHIN 10 FEET (3048 MM).
 3.WHERE THE VENT TERMINATION IS
 LOCATED BELOW AN ADJACENT ROOF
 STRUCTURE, THE TERMINATION POINT SHALL
 BE LOCATED AT LEAST 3 FEET (914 MM) FROM
 SUCH STRUCTURE.
 4.THE VENT SHALL TERMINATE AT LEAST
 4 FEET (1219 MM) BELOW, 4 FEET (1219 MM)
 HORIZONTALLY FROM, OR 1 FOOT (305 MM)
 ABOVE ANY DOOR, WINDOW OR GRAVITY AIR
 INLET FOR THE BUILDING.
 5.A VENT CAP SHALL BE INSTALLED TO
 PREVENT RAIN FROM ENTERING THE VENT
 SYSTEM.
 6.THE VENT TERMINATION SHALL BE
 LOCATED AT LEAST 3 FEET (914 MM)
 HORIZONTALLY FROM ANY PORTION OF THE
 ROOF STRUCTURE.
  
 501.2 OUTDOOR DISCHARGE.
  
 THE AIR REMOVED BY EVERY MECHANICAL
 EXHAUST SYSTEM SHALL BE DISCHARGED
 OUTDOORS AT A POINT WHERE IT WILL NOT
 CAUSE A NUISANCE AND FROM WHICH IT
 CANNOT AGAIN BE READILY DRAWN IN BY A
 VENTILATING SYSTEM. AIR SHALL NOT BE
 EXHAUSTED INTO AN ATTIC OR CRAWL SPACE
  
 401.5 OPENING LOCATION.
 OUTDOOR AIR EXHAUST AND INTAKE OPENINGS
 SHALL BE LOCATED A MINIMUM OF 10 FEET
 (3048 MM) FROM LOT LINES OR BUILDINGS ON
 THE SAME LOT. WHERE OPENINGS FRONT ON A
 STREET OR PUBLIC WAY, THE DISTANCE SHALL
 BE MEASURED TO THE CENTERLINE OF THE
 STREET OR PUBLIC WAY.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-02-06 Cont ID  
Sent By dpalmer Date 2007-02-06 Time 12:55 Rev Time 0.00
Received By dpalmer Date 2007-02-06 Time 11:56 Sent To  
Notes
2007-02-06 12:56:27ELEC OK,
  
 3RD SET FO MECH AND BLDG SHEETS ARE PHOTO-COPIES OF
 SIGNED AND SEALED PLANS.
 THE ELECTRICAL SHEETS IN THE THIRD SET ARE ORIGINAL.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-11-17 Cont ID  
Sent By dpalmer Date 2006-11-17 Time 15:15 Rev Time 0.00
Received By dpalmer Date 2006-11-17 Time 14:53 Sent To  
Notes
2006-11-17 15:16:21**** UNSAT 3RD REVIEW ****
  
 ***PLEASE SEE SOME NOTE FROM PREVIOUS REVIEW(S).
  
 1) NOTE:PLEASE SUBMIT PLANS SPECS/MANUFACTURE CUT
 SHEETS INTO THREE COMPLETE SETS, AS THREE SETS OF
 ELECTRICAL PLANS ARE BEING SUBMITTED, PLEASE ALSO
 SUBMIT THREE SETS OF ALL FOR STAMPING.
 PLEASE SUBMIT ALL PLANS IN A NEAT AND ORDERLY FASHION.
  
 ONLY ONE SET OF EACH OF THE OLD/VOIDED SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE. THESE SHALL BE LABELED
 "VOIDED/OLD" AND SHOULD BE PLACED TOGETHER SEPARATE
 FROM NEW SETS.
 ANY COMMENT RESPONSE LETTERS FRO DESIGN PROFESSIONAL
 SHALL BE KEPT SEPARATELY.
 THIS WAS REQUESTED ON PREVIOUS REVIEW.
  
 2) NOTE: PLEASE SEE AS STATED ON PREVIOUS REVIEWS, THE
 ELECTRICAL CONTRACTOR HAS NOT SIGNED ON THE ELECTRICAL
 LINE OF PERMIT APPLICATION FOR THE ELECTRICAL PERMIT AS
 PART OF THIS PACKAGE. IF THIS ELECTRICAL CONTRACTOR IS
 NOT DOING THE ELECTRICAL INSTALLATION AS SUBMITTED
 WHICH IS HIGHLY UNLIKELY, THEN PLEASE KNOW SEPARATE
 PERMIT APPLICATION WILL BE REQUIRED WITH SEPARATE FEES.
 THIS IS THE LAST NOTICE WHICH WILL BE GIVEN TO THIS.
  
 3) NOTE: PLEASE SEE FLOOR /SITE PLANS DO NOT CORRELATE
 WITH RISER DIAGRAM SUBMITTED. PLEASE SEE FIRST FLOOR
 ELECTRICAL ROOM IS NOT SHOWN ON E-2, AND THE FEEDERS DO
 NOT SHOW THESE GOING TO ANY DISCONNECTING MEANS AT THIS
 BUILDING WHICH IS PARTIALLY SHOWN ON RISER.
 225.31-225.39.
 PLEASE SEE PREVIOUS NOTES.
  
 4) NOTE: PLEASE SEE PREVIOUS NOTES FOR DETAILS WHICH IS
 REQUIRED PER NFPA-110 PLEASE SEE SECTIONS BELOW AS
 PLANS DO NOT PROVIDE ENOUGH INFORMATION FOR SEPARATION,
 ISOLATION, ETC. FROM THE STRUCTURAL ELEMENTS OF THE
 BUILDING.
 PLEASE SEE NFPA-110 2002 7.3, .4, .5, .6, .7 ETC.
 THIS WAS PAST BY THE BUILDING REVIEWER , HOWEVER IS
 STILL REQUIRED.
  
 ** ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
 **IF THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF
 THE NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE
 DO NOT HESITATEIN CONTACTING THIS REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-08-16 Cont ID  
Sent By dpalmer Date 2006-08-16 Time 18:31 Rev Time 0.00
Received By dpalmer Date 2006-08-16 Time 17:46 Sent To  
Notes
2006-08-16 00:00:00*** UNSAT 2ND REVIEW ***
  
 1) NOTE: PLEASE SEE MAINS AND
 DISCONNECTING MEANS FOR FEEDERES AND
 SEC'S SHALL BE GROUPED. THE MAINS ARE
 NOT GROUPED AND HAVING A BREAKER ON THE
 GEN IN THE GARAGE OR THE MAIN IN SB8 IS
 NOT PERMITTED.
 PLEASE SEE 225.31-225.39, 230.72 ETC.
 PLEASE KNOW THAT A DISCONNECTING MEANS
 FOR THE FEEDERS FROM THE GEN WILL BE
 REQUIRED IN CLOSE PROXIMITY TO THE
 EXISTING MAINS/DISCONNECTS.
 PLEASE ALSO KNOW THAT THE ATS IS NOT
 PERMITTED IN THE MECHANICAL EQUIPMENT
 ROOM AND SHALL BE LOCATED IN THE
 ELECTRICAL ROOM WITH OTHER ELECTRICAL
 EQUIPMENT WHICH IS IS BEIGN FED FROM AND
 WHICH IT IS FEEDING.
  
  
 2) NOTE: PLEASE SEE REVIEW COMMENTS FROM
 OTHER TRADES AS THE LOCATION OF THE
 GENERATOR IN THE PARKING GARAGE DOES NOT
 PROVIDE ENOUGH INFORMATION FOR
 SEPARATION, ISOLATION, ETC.
 PLEASE SEE NFPA-110 2002 7.3,.4,.5,.6,.7
 ETC.
  
 3) NOTE: PLEASE KNOW THAT ONLY TWO SETS
 OF ELECTRICAL PLANS ARE REQUIRED,
 HOWEVER THREE SETS ARE BEING SUBMITTED.
 IF SUBMITTING THREE FOR STAMPING, THEN
 PLEASE BE SURE THE THIRD SET IS SIGNED,
 DATED AND SEALED.
 FS 471.025, FAC 61G15-23.002
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-11 Cont ID  
Sent By adarroug Date 2006-06-11 Time 09:20 Rev Time  
Received By dpalmer Date 2006-06-11 Time 08:30 Sent To  
Notes
2006-06-11 00:00:00********** UNSAT *************
  
 ** PLEASE KNOW BESIDES THE BELOW
 COMMENTS, PLANS ARE NOT COMPLETE AT THIS
 TIME FOR COMPLETE REVIEW.
  
  
 1) NOTE: ATTENTION CONTRACTOR, IF PROTON
 ELECTRICAL IS ALSO DOING THE ELECTRICAL
 INSTALLATION FOR THE CONNECTIONS ON THE
 GENERATOR, THEN PLEASE SIGN ON THE
 ELECTRICAL LINE ON PERMIT APPLICATION SO
 AN ELECTRICAL PERMIT CAN BE ESTABLISHED.
 THIS WAS NOT
  
 2) NOTE: PLEASE SUBMIT SPECS FOR FUEL
 TANK. PLEASE SEE PLANS MUST INCLUDED
 LOCATION, VENTILATION, FIRE RATINGS ETC
 .
 PLEASE SEE NOTE #5 BELOW, IF THE GEN
 FEEDS ANY LEGALLY REQUIRED BACK UP
 LTS/SYSTEMS, THE AMOUNT OF FUEL, AND RUN
 TIMES SHALL BE CLEARLY INDICATED ON
 PLANS.
 PLEASE KNOW THERE IS NOTHING ON PLANS
 FOR INSTALLATIONOF GEN, FUEL, LOCATION
 ETC.
 PLEASE SEE COMMENTS FROM OTHER TRADES
 WHICH WILL AFFECT PLANS SUBMITTED.
 PLEASE BE SURE ALL TANK SPECS CONTAIN
 LISTING BY A NRTL.
 215.5
  
 3) NOTE: PLEASE SUBMIT A COMPLETEPLAN
 SHOWING THE LAYOUT FOR THE GENERATOR.
 PLEASE SEE THAT NO MEANS OF DISCOONECTS
 ARE BEING SHOWN FOR GROUPING OF MAINS IN
 THE BUILDING.
 PLEASE SHOW THE LOCATION OF ALL THE
 EXISTING GENERATORS FEEDING THIS
 BUILDING THE MEANS OF DICONNECT LOCAITON
 FOR ALL.
 230.72, 225.31-225.39, 230.2
  
 4) NOTE: PLEASE SEE THAT ALL SPECS
 SUBMITTED FOR GEN, ATS ETC SHALL CLEARLY
 BE HIGHLIGHTED FOR EACH UNIT EQUIPMENT
 BEING USED ON THIS JOBSITE.
 215.5
  
 5) NOTE: PLEASE VERIFY IF THIS GENERATOR
 WILL BE FEEDING ANY OF THE REQUIRED BACK
 UP POWER FROM LIGHTING ETC.
 PLEASE NOTE IF ALL LTS ARE BATTERY BACK
 UP, OR ARE THEY FED FROM A LEGALLY
 REQUIRED BACK UP SYSTEM NOW.
 PLEASE SEE SYSTEM INSTALLATION
 REQUIREMENTS PER 700,701, NFPA-110 ETC
  
  
 6) NOTE: PLEASE SEE PLANS INDICATE TWO
 TRANSFORMERS BEING FED, YET PANEL SB8
 DOES NOT CORRELATE.
 215.5
  
 7) NOTE: PLEASE PLACE NOTES ON PLANS FOR
 ALL SIGNAGE WHICH WILL BE REQUIRED.
 230.2E,702.8,701.9 ETC.
 PLEASE KNOW, THE LOCATIONS OF SUCH
 DISCONNECTS AND SYSTEMS HAVE NOT BEEN
 APPROVED AT THIS TIME.
  
 8) NOTE: PLEASE INDICATE THE OCP AT
 GENERATOR.
 215.5
  
 9) NOTE: PLEASE SEE MULTIPLE PANELS ON
 RISER WITH THE SAME IDENTIFICATION??
  
 10) NOTE: PLEASE SEE THAT ALL CONTINUOUS
 LOADS SHALL BE SHOWN AT 125%.
 215.3,230.42 ETC
  
 11) NOTE: PLEASE SEE MAX HEAT LOADS
 SHALL BE FIGURED FOR THE AHU'S OR LOAD
 SHEDDING IS PERMITTED. PLEASE PROVIDE A
 COMPLETE DETAIL FOR LOAD SHEDDING IF
 THIS OPTION IS TAKEN.
 THE WIRING SCHEMATIC WILL BE REQUIRED ON
 PLANS.
 702.5 ETC
  
 12) NOTE: PLEASE SEE GEN ANNUNCIATOR
 PANEL, CONTROLS,STATUS INDICATORS SHALL
 ALSO BE LOCATED IN THE EXISTING FIRE
 COMMAND ROOM WITH SIGNAGE AS REQUIRED.
 NFPA-72, NFPA-101, NFPA-110
  
 13) NOTE: PLEASE KNOW, A FUEL TYPE
 PERMIT MAY ALSO BE REQUIRED. SEE MECH
 REVIEW.
  
 14) NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTORS.
 250.110,250.122,250.6,250.24.
 PLEASE SEE NONE ARE BEING SHOWN AT THIS
 TIME. PLEASE KNOW, IF USING ALL METAL
 CONDUITS, THEN CONNECTORS ALL SHALL BE
 LISTED FOR "EQUIPMENT GROUNDING".
 STANDARD CONNECTORS ARE NO PERMITTED
 UNLESS LISTED AS NOTED.OR
 PLEASE INDICATE THE EQUIPMENT GROUNDING
 CONDUCTOR SIZED PER 250.122
  
 ** PLEASE SEE COMMENTS FROM OTHER TRADES
 WHICH WILL AFFECT THE PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-03-07 Cont ID  
Sent By mawillia Date 2007-03-07 Time 14:03 Rev Time 0.00
Received By mawillia Date 2007-03-07 Time 13:53 Sent To  
Notes
2007-03-07 14:03:36*****APPROVED*****
  
  
 ALL COMMENTS FROM PREVIOUS FIRE PLAN REVIEWS HAVE BEEN
 ADDRESSED.PLAN SHEET E3 WAS STAMPED, INITIALED, AND
 DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2006-12-22 Cont ID  
Sent By mawillia Date 2006-12-22 Time 11:03 Rev Time 0.00
Received By mawillia Date 2006-12-22 Time 11:03 Sent To  
Notes
2006-12-22 11:07:29*****DENIED*****
  
  
  
 PLEASE REVIEW THE PREVIOUS TWO FIRE PLAN REVIEWS FOR
 REFERENCE.TO EXPEDITE THE PLAN REVIEW PROCESS,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-09-15 Cont ID  
Sent By mwennerg Date 2006-09-15 Time 11:08 Rev Time 0.00
Received By mwennerg Date 2006-09-15 Time 11:08 Sent To  
Notes
2006-09-15 00:00:00***DENIED***
  
 PLEASE BE ADVISED THAT NO RESPONSE
 LETTER WAS SUBMITTED FOR FIRST FIRE
 REVIEW COMMENTS. IT WOULD APPEAR THAT
 SOME INFORMATION IS NOW SHOWING HOWEVER
 PLEASE RESPOND TO THE FOLLOWING:
  
 1) NOTE (3) WILL CONTROL PANELS BE
 PROVIDED IN THE FIRE COMMAND ROOM TO
 ADVISE STATUS OF THE SYSTEM?
  
 2) WHAT OTHER EQUIPMENT WILL BE
 CONTAINED WITHIN THE ROOM WHERE THE
 GENERATOR IS PLANNED?
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-06-16 Cont ID  
Sent By mcarsill Date 2006-06-16 Time 14:18 Rev Time 0.00
Received By mcarsill Date 2006-06-16 Time 14:04 Sent To  
Notes
2006-06-16 00:00:001. THE PLANS INDICATE THAT A NEW
 GENERATOR IS PLANNED FOR THE SECOND
 FLOOR GENERATOR ROOM OF THE PARKING
 GARAGE. INFORMATION INDICATES THAT THE
 GENERATOR IS TO BE SUPPLIED BY NATURAL
 GAS. NO DETAILS PROVIDED ON WHERE THE
 PROPOSED INSTALLATION ROOM IS LOCATED
 WITHIN THE GARAGE.
  
 2. NO DETAILS PROVIDED WITH REGARDS TO
 VENTING OF THE GENERATOR WHILE IT IS
 RUNNING. THE TERMINATION POINT OF THE
 EXHAUST IS TO BE SHOWN SO A BACK FEED OF
 DANGEROUS FUMES DOES NOT OCCUR.
 SOMETIMES ARCHITECTURAL ELEMENTS OF A
 BUILDING CAN CAUSE THIS TO OCCUR.
  
 3. WILL CONTROL PANELS BE PROVIDED IN
 THE FIRE COMMAND ROOM TO ADVISE STATUS
 OF THE SYSTEM.
  
 4. WHAT OTHER EQUIPMENT WILL BE
 CONTAINED WITHIN THE ROOM WHERE THE
 GENERATOR IS PLANNED.
  
 5. MORE DETAILS ARE NEEDED FOR THE PLAN
 REVIEW PROCESS.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop G GAS REVIEW
Rev No 5 Status P Date 2007-03-30 Cont ID  
Sent By kstevens Date 2007-03-30 Time 16:50 Rev Time 0.00
Received By kstevens Date 2007-03-30 Time 16:50 Sent To M
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2007-02-21 Cont ID  
Sent By kstevens Date 2007-02-21 Time 08:02 Rev Time 0.00
Received By kstevens Date 2007-02-21 Time 08:02 Sent To  
Notes
2007-02-21 08:33:10DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 FROM PREVIOUS REVIEWS:
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR THE SEPARATE GAS PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ****OK
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 ****OK
  
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 ****RESPONSE NOTED, BUT THE BTU INFORMATION SUBMITTED
 IS CONFLICTING FROM ONE PAGE TO THE OTHER. THE NEXT TO
 LAST SHEET INDICATES THE BTU LOAD TO BE 905,000 BTU'S,
 BUT THE FINAL PAGE INDICATES FUEL CONSUMPTION TO BE
 4200 CFH, (4,536,000 BTU'S). PLEASE CLARIFY AS THIS IS
 A LARGE DISCREPENCY.
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ****OK
  
 5. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
 ****NOT SUBMITTED.
  
 6. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 ****OK
  
 7. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
 ****OK
  
 8. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 MANUFACTURES INSTALLATION INSTRUCTIONS
 REQUIRE TO SHOW MINIMUM CLEARANCES FROM
 ALL STRUCTURES.
 ****OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2007-01-06 Cont ID  
Sent By kstevens Date 2007-01-06 Time 18:06 Rev Time 0.00
Received By kstevens Date 2007-01-06 Time 18:06 Sent To  
Notes
2007-01-06 18:06:59DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR THE SEPARATE GAS PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
  
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 5. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 6. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 7. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 8. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 MANUFACTURES INSTALLATION INSTRUCTIONS
 REQUIRE TO SHOW MINIMUM CLEARANCES FROM
 ALL STRUCTURES.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2007-01-06 Cont ID  
Sent By kstevens Date 2006-08-25 Time 07:42 Rev Time 0.00
Received By kstevens Date 2006-08-25 Time 07:42 Sent To  
Notes
2006-08-25 00:00:00DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR THE SEPARATE GAS PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
  
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 5. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 6. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 7. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 8. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 MANUFACTURES INSTALLATION INSTRUCTIONS
 REQUIRE TO SHOW MINIMUM CLEARANCES FROM
 ALL STRUCTURES.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-06-27 Cont ID  
Sent By kstevens Date 2006-06-27 Time 11:17 Rev Time 0.00
Received By kstevens Date 2006-06-27 Time 11:17 Sent To  
Notes
2006-06-27 00:00:00DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR THE SEPARATE GAS PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
  
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 5. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 6. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 7. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-05-16 Cont ID  
Sent By adarroug Date 2007-05-16 Time 09:05 Rev Time 0.00
Received By adarroug Date 2007-05-16 Time 09:05 Sent To M
Notes
2007-05-16 09:05:22TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-03-14 Cont ID  
Sent By adarroug Date 2007-03-14 Time 15:26 Rev Time 0.00
Received By adarroug Date 2007-03-14 Time 15:26 Sent To G
Notes
2007-03-14 15:26:36TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-01-25 Cont ID  
Sent By adarroug Date 2007-01-25 Time 11:01 Rev Time 0.00
Received By adarroug Date 2007-01-25 Time 11:01 Sent To  
Notes
2007-02-06 10:55:41TO "COMM" BD#15
2007-01-25 11:01:35WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-11-12 Cont ID  
Sent By adarroug Date 2006-11-12 Time 13:30 Rev Time 0.00
Received By adarroug Date 2006-11-12 Time 13:30 Sent To  
Notes
2006-11-14 10:14:26TO "COMM" BD#46
2006-11-12 13:30:24WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-04 Cont ID  
Sent By mmiller Date 2006-08-04 Time 13:45 Rev Time 0.00
Received By adarroug Date 2006-08-04 Time 13:45 Sent To  
Notes
2006-08-12 00:00:00TO "COMM" BD#27
2006-08-07 00:00:008/7/06-WAITING FOR "COMM" BD
2006-08-04 00:00:00SENT "DP" DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-27 Cont ID  
Sent By btrobaug Date 2006-06-27 Time 11:18 Rev Time 0.00
Received By kstevens Date 2006-05-17 Time 15:31 Sent To  
Notes
2006-06-01 00:00:00TO "COMM"BD#23
2006-05-17 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-05-30 Cont ID  
Sent By hmoser Date 2007-05-30 Time 10:38 Rev Time 0.00
Received By hmoser Date 2007-05-30 Time 10:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-04-02 Cont ID  
Sent By hmoser Date 2007-04-02 Time 09:42 Rev Time 0.00
Received By hmoser Date 2007-04-02 Time 09:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2007-02-24 Cont ID  
Sent By hmoser Date 2007-02-24 Time 08:59 Rev Time 0.00
Received By hmoser Date 2007-02-24 Time 08:59 Sent To  
Notes
2007-02-24 09:01:44NATURAL GAS MECHANICAL NOT REQUIRED
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-06-24 Cont ID  
Sent By hmoser Date 2006-06-24 Time 10:37 Rev Time 0.00
Received By hmoser Date 2006-06-24 Time 10:33 Sent To  
Notes
2006-06-24 00:00:00NATURAL GAS MECHANICAL NOT REQUIRED.

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-06-27 Cont ID  
Sent By kstevens Date 2006-06-27 Time 10:40 Rev Time 0.00
Received By kstevens Date 2006-06-27 Time 10:40 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status N Date 2006-11-16 Cont ID  
Sent By kdfreema Date 2006-11-16 Time 08:14 Rev Time 0.00
Received By kdfreema Date 2006-11-16 Time 08:14 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status N Date 2006-08-23 Cont ID  
Sent By mflis Date 2006-08-23 Time 10:22 Rev Time 0.00
Received By mflis Date 2006-08-23 Time 10:22 Sent To  
Notes
2006-08-23 00:00:00NO CHANGES TO PARKING LAYOUT OR EXTERIOR
 BUILDING. ANY EXPOSED CONDUIT SHOULD BE
 PAINTED TO MATCH EXISTING BUILDING.
 ZONING REVIEW NOT REQUIRED.
  
 MATTHEW FLIS

Review Stop Z ZONING
Rev No 1 Status N Date 2006-06-26 Cont ID  
Sent By dpalmer Date 2006-06-26 Time 18:58 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
***NONE***