| Plan Review Stops For Permit 06050565 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2006-09-20 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-09-20 |
Time |
12:25 |
Rev Time |
1.11 |
| Received By |
jwitmer |
Date |
2006-09-20 |
Time |
12:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-06-01 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-06-01 |
Time |
07:54 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2006-06-01 |
Time |
07:52 |
Sent To |
|
|
| Notes |
| 2006-06-01 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 06050565 | | | ADD: 2013 PONCE DE LEON | | | CONT: PERSONALIZED A/C | | | TEL: (561)239-1340 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1) HILLMAN ENGINEERING INC, | | | MISSINGCERTIFICATE OF AUTHORIZATION IN | | | TITLE BLOCK. REPORT AND PLANS. | | | 471.023 F.S.CERTIFICATE OF | | | AUTHORIZATION.THE TITLE BLOCK FOR ANY | | | SHEET BEARING THE NAME OF AN ENGINEER | | | PRACTICING UNDER A FICTITIOUS NAME, A | | | CORPORATION, OR A PARTNERSHIP, OFFERING | | | ENGINEERING SERVICES, SHALL INCLUDE THE | | | CERTIFICATE OF AUTHORIZATION NUMBER. | | | ADD THE NUMBER TO EACH SHEET.THIS MAY | | | BE ADDED BY HAND. | | | | | | 2) HILLMAN ENGINEERING PLANS NOT SIGNED, | | | RAISED SEAL NOR DATE. | | | PLANS, SPECIFICATIONS,REPORTS OR | | | OTHER DOCUMENTS PREPARED BY THE DESIGN | | | PROFESSIONAL AND BEING FILED FOR PUBLIC | | | RECORD SHALL HAVE THE SIGNATURE AND | | | SEAL OF THE DESIGN PROFESSIONAL AFFIXED | | | TO THE DOCUMENT. | | | FL STATE STAT: 61G15-23.002 ENGINEERS | | | FL ATATE STAT: 61G16.003 ARCHITECTS | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2006-08-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-08-11 |
Time |
21:06 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-08-25 |
Time |
20:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-06-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-06-10 |
Time |
14:59 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-06-10 |
Time |
14:37 |
Sent To |
|
|
| Notes |
| 2006-06-10 00:00:00 | ***** UNSAT ****** | | | | | | 1) NOTE: PLEASE PROVIDE A MORE DETAILED | | | LAYOUT/OVERVIEW OF EQUIPMENT LOCATIONS. | | | SURVEY SEEMS TO LOCATION OF THE NEW CT | | | AND ATS, BUT THE DISCONNECT ON RISER | | | COULD NOT BE SEEN. | | | PLEASE PROVIDE PERHAPS A "BLOW-UP" OF | | | THIS AREA. | | | THIS IS NEEDED TO VERIFY THE GROUPING OF | | | MAINS AS REQUIRED PER 230.72,225.34 | | | | | | 2) NOTE: PLEASE SPECIFY ON RISER THE AIC | | | RATINGS FOR ALL NEW SERVICE EQUIPMENT. | | | PLEASE SEE THE DISC FOR THE FEEDERS | | | COMING FROM GEN SHALL BE RATED FOR THE | | | VAILABLE FAULT CURRENT FROM GEN AND THE | | | NEW SE RATED ATS SHALL ALSO BE RATED FOR | | | THE AVAILABLE FROM FPL. | | | 110.9,702.5 | | | | | | 3) NOTE: PLEASE SEE AN "EQUIPMENT | | | GROUNDING CONDUCTOR" SHALL NOT BE | | | INSTALLED BEFORE TH FIRST MEANS OF | | | DISCONNECT. PER 250.6,250.24B | | | | | | 4) NOTE: PLEASE SEE THE MAIN AT THE NEW | | | SE RATE ATS NEEDS TO BE NOTED AND | | | VERIFIED ANS CONTAINING A MANUAL MEANS | | | OF DICONNECT, RATED FOR THE LOAD SERVED | | | AND ON THE OUTSIDE OF THE EQUIPEMNT NOT | | | EXPOSING ANY LIVE PARTS INORDER TO | | | SHUT DOWN POWER. | | | PLEASE SEE 230.76,230.79, 110.27 | | | THIS SEEMS TO BE THE CASE, HOWEVER IT IS | | | NOT CLEAR AT THIS TIME BY THE SPECS AND | | | RISER SUBMITTED. | | | | | | 5) NOTE: PLEASE KNOW, IF USING THE | | | ONE-YEAR FPL USEAGE FOR SIZING THE GEN, | | | THEN THIS SHALL CONTAIN A STATEMENT FROM | | | THE RESPONSIBLE DESIGNER WHICH STATED | | | THE AVG OVERALL KW USAGE AND THE RATING | | | FOR NEW GEN WITH THE PRINTED NAME AND | | | SIGNATURE ON THE LOAD SHEETS PROVIDED | | | FROM FPL. | | | | | | 6) NOTE: PLEASE SEE PLUMB REVIEW | | | COMMENTS AS THE VALUE STATED ON | | | APPLIACTION SHALL INCLUDE ALL LABOR AND | | | MATERIALS WHICH OULD INCLUDE THE COST OF | | | THE PROPOSED TANKS. | | | FBC 108.3 ADMINISTRATIVE SECTION AS | | | ADOPTED BY THE CITY OF WEST PALM BEACH. | | | | | | ** PLEASE SEE FIRE REVIEW COMMENTS AS | | | THESE MAY HAVE AN AFFECT ON | | | DESIGN/INSTALLATION. | | | | | | | | | ** PLEASE KNOW, THIS ADDRESS IS NOT | | | LOCATED IN A FLOOD ZONE. AN ELEVATION | | | CERTIFICATE WILL NOT BE REQUIRED BEFORE | | | FINAL. | | | | | | PLEASE SUBMIT THE ABOVE CORRECTIONS AND | | | INFORMATION FOR REVIEW. IF THERE ARE ANY | | | QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2006-09-11 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2006-09-11 |
Time |
11:55 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2006-09-11 |
Time |
11:55 |
Sent To |
|
|
| Notes |
| 2006-09-11 00:00:00 | *****APPROVED***** | | | | | | | | | | | | | | | | | | | | | NOTES/CONCERNS OF 06/19/2006'S FIRE PLAN | | | REVIEW HAVE BEEN ADDRESSED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2006-06-19 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2006-06-19 |
Time |
10:40 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2006-06-19 |
Time |
10:34 |
Sent To |
|
|
| Notes |
| 2006-06-19 00:00:00 | 1. PLEASE SPECIY CATEGORY OF GENERATOR | | | USE PER NFPA 110. | | | | | | 2. SURVEY AND EQUIPMENT LAYOUT IS | | | DIFFICULT TO FOLLOW DUE TO SIZE AND HAND | | | NOTED APPLIED TO THE DRAWING. PLEASE | | | PROVIDE A MORE DETAILED ILLUSTRATION. | | | | | | 3. ANOTHER PERMIT APPLICATION PROVIDED | | | DISPLAYING PROPANE SUPPLY FOR THE | | | GENERATOR. THE VALUE APPEARS TO BE TOO | | | LOW FOR THE WORK BEING PROPOSED. | | | | | | 4. PLEASE LOCATE EXIT DOORS AND ANY | | | WINDOWS FOR THE ONE-STORY BUILDING SHOWN | | | ON THE SURVEY. | | | | | | 5. ALL ELECTRICAL WORK TO COMPLY WITH | | | NFPA 70, THE NATIONAL ELECTRICAL CODE | | | AND ALL ACCEPTED RECOGNIZED STANDARDS | | | FOR ELECTRICAL WORK. | | | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | | OFFICER | | | 804-4709 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2006-08-12 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-08-12 |
Time |
13:30 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-08-12 |
Time |
13:38 |
Sent To |
|
|
| Notes |
| 2006-08-12 00:00:00 | PERMIT VALUE TO LOW. | | | COPY OF CONTRACT REQUIRED TO GET CORRECT | | | VALUE FOR PERMIT FEE. | | | OK TO PRINT PERMIT WHEN VALUE HAS BEEN | | | CORRECTED.PES |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2006-07-01 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-07-01 |
Time |
09:39 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-07-01 |
Time |
09:21 |
Sent To |
|
|
| Notes |
| 2006-07-01 00:00:00 | PAUL SCHMITZ | | | [email protected] | | | FBC 2004 PLUMBING CODE PLAN REVIEW | | | FBC2004 FUEL GAS CODEPLAN REVIEW | | | FBC 2004 CH 11, FL ACESSIBILITY CODE | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPT.1, ADMINISTRATION, 2004 EDITION | | | | | | UNSAT | | | | | | PLEASE SEE COMMENTS FROM OTHER PLAN | | | REVIWERS, BUILDING,ELECTRICAL,FIRE. | | | WHICH MAY EFFECT THE GAS PLAN REVIEW. | | | | | | ESTIMATED VALUE. | | | CLARITY OF PLANS. | | | ENGINEER OF RECORD, SIGN AND SEAL. | | | CURRENT GAS CODE: FBC 2004 FUEL GAS. | | | | | | END OF COMMENTS QUESTIONS 561-805-6692 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-07-31 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-07-31 |
Time |
16:13 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-07-31 |
Time |
16:13 |
Sent To |
|
|
| Notes |
| 2006-08-11 00:00:00 | TO "COMM" BD#12 | | 2006-07-31 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-05-31 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-05-31 |
Time |
14:25 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-05-31 |
Time |
14:25 |
Sent To |
|
|
| Notes |
| 2006-06-01 00:00:00 | TO "COMM" BD#10 | | 2006-05-31 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-07-01 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-07-01 |
Time |
09:58 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-05-16 |
Time |
09:32 |
Sent To |
|
|
| Notes |
| 2006-05-16 00:00:00 | TO "Z" BOX"N" ADDED PES | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2006-09-20 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-09-20 |
Time |
12:09 |
Rev Time |
0.25 |
| Received By |
tgordon |
Date |
2006-09-20 |
Time |
12:09 |
Sent To |
|
|
| Notes |
| 2006-09-20 00:00:00 | *** PROVISO *** | | | 1) PER 2004 FBC, FUEL GAS - POWERED | | | EQUIPMENT - PERMANENTLY INSTALLED | | | EQUIPMENT POWERED BY INTERNAL COMBUSTION | | | ENGINES SHALL BE INSTALLED IN ACCORDANCE | | | WITH MANUFACTURE'S INSTALLATION | | | INSTRUCTIONS AND NFPA 37. | | | | | | NFPA 37 INSTALLATION & USE OF STATIONARY | | | COMBUSTION ENGINES & GAS TURBINES: | | | 4.1.4ENGINES (GENERATORS) LOCATED | | | OUTDOORS SHALL BE MINIMUM OF 5 FT FROM | | | OPENINGS IN WALLS & AT LEAST 5 FT FROM | | | STRUCTURES HAVING COMBUSTIBLE WALLS.A | | | MINIMUM CLEARANCE IS NOT REQUIRED WHEN | | | (1) THE ADJACENT WALL HAS A MINIMUM FIRE | | | RESISTANCE RATING OF 1 HOUR OR (2) THE | | | WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF | | | NON-COMBUSTIBLE MATERIALS, AND IT HAS | | | BEEN DEMONSTRATED THAT A FIRE WITHIN THE | | | ENCLOSURE WILL NOT IGNITE COMBUSTIBLE | | | MATERIALS OUTSIDE THE ENCLOSURE. | | | INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS | | | SHOULD NOT TERMINATE UNDER STRUCTURES OR | | | WHERE THE EXHAUST MIGHT BE DRAWN INTO | | | THE VENTILATION INTAKES. | | | | | | 2004 FMC 804.3.5 #3, WHERE THE | | | TERMINATION IS LOCATED BELOW AN ADJACENT | | | ROOF STRUCTURE, THE TERMINATION POINT | | | SHALL BE LOCATED AT LEAST 3 FT FROM THE | | | ROOF STRUCTURE. | | | | | | PLEASE NOTE, WHILE ZONING ALLOWS | | | MECHANICAL EQUIPMENT TO ENCROACH 4 FT | | | INTO THE REQUIRED SETBACK, GENERATORS | | | SHALL MAINTAIN THE REQUIRED ABOVE | | | MENTIONED CLEARANCES TO THE ADJACENT | | | PROPERTY STRUCTURES, I.E. FENCE, | | | BUILDING, WINDOWS, DOORS, OR OPENINGS. | | | | | | FOLLOW MANUFACTURE'S RECOMMENDED | | | CLEARANCES AROUND EQUIPMENT FOR | | | SERVICING,AND PROVIDE MANUFACTURE'S | | | INSTALLATION INSTRUCTIONS AT THE JOBSITE | | | FOR THE FIELD INSPECTOR. | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2006-08-28 |
|
|
Cont ID |
|
| Sent By |
kdfreema |
Date |
2006-08-28 |
Time |
09:22 |
Rev Time |
0.00 |
| Received By |
kdfreema |
Date |
2006-08-28 |
Time |
09:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2006-05-30 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-05-30 |
Time |
16:46 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-05-30 |
Time |
16:46 |
Sent To |
I |
|
| Notes |
| 2006-05-30 00:00:00 | NOTE: THE PROPOSED GENERATOR IS 12FT | | | FROM PROPERTY LINE. |
|
|