Plan Review Details - Permit 06050565
Plan Review Stops For Permit 06050565
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-09-20 Cont ID  
Sent By jwitmer Date 2006-09-20 Time 12:25 Rev Time 1.11
Received By jwitmer Date 2006-09-20 Time 12:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-06-01 Cont ID  
Sent By jwitmer Date 2006-06-01 Time 07:54 Rev Time 0.77
Received By jwitmer Date 2006-06-01 Time 07:52 Sent To  
Notes
2006-06-01 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06050565
 ADD: 2013 PONCE DE LEON
 CONT: PERSONALIZED A/C
 TEL: (561)239-1340
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) HILLMAN ENGINEERING INC,
 MISSINGCERTIFICATE OF AUTHORIZATION IN
 TITLE BLOCK. REPORT AND PLANS.
 471.023 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ENGINEER
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING
 ENGINEERING SERVICES, SHALL INCLUDE THE
 CERTIFICATE OF AUTHORIZATION NUMBER.
 ADD THE NUMBER TO EACH SHEET.THIS MAY
 BE ADDED BY HAND.
  
 2) HILLMAN ENGINEERING PLANS NOT SIGNED,
 RAISED SEAL NOR DATE.
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-08-11 Cont ID  
Sent By dpalmer Date 2006-08-11 Time 21:06 Rev Time 0.00
Received By dpalmer Date 2006-08-25 Time 20:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-10 Cont ID  
Sent By dpalmer Date 2006-06-10 Time 14:59 Rev Time 0.00
Received By dpalmer Date 2006-06-10 Time 14:37 Sent To  
Notes
2006-06-10 00:00:00***** UNSAT ******
  
 1) NOTE: PLEASE PROVIDE A MORE DETAILED
 LAYOUT/OVERVIEW OF EQUIPMENT LOCATIONS.
 SURVEY SEEMS TO LOCATION OF THE NEW CT
 AND ATS, BUT THE DISCONNECT ON RISER
 COULD NOT BE SEEN.
 PLEASE PROVIDE PERHAPS A "BLOW-UP" OF
 THIS AREA.
 THIS IS NEEDED TO VERIFY THE GROUPING OF
 MAINS AS REQUIRED PER 230.72,225.34
  
 2) NOTE: PLEASE SPECIFY ON RISER THE AIC
 RATINGS FOR ALL NEW SERVICE EQUIPMENT.
 PLEASE SEE THE DISC FOR THE FEEDERS
 COMING FROM GEN SHALL BE RATED FOR THE
 VAILABLE FAULT CURRENT FROM GEN AND THE
 NEW SE RATED ATS SHALL ALSO BE RATED FOR
 THE AVAILABLE FROM FPL.
 110.9,702.5
  
 3) NOTE: PLEASE SEE AN "EQUIPMENT
 GROUNDING CONDUCTOR" SHALL NOT BE
 INSTALLED BEFORE TH FIRST MEANS OF
 DISCONNECT. PER 250.6,250.24B
  
 4) NOTE: PLEASE SEE THE MAIN AT THE NEW
 SE RATE ATS NEEDS TO BE NOTED AND
 VERIFIED ANS CONTAINING A MANUAL MEANS
 OF DICONNECT, RATED FOR THE LOAD SERVED
 AND ON THE OUTSIDE OF THE EQUIPEMNT NOT
 EXPOSING ANY LIVE PARTS INORDER TO
 SHUT DOWN POWER.
 PLEASE SEE 230.76,230.79, 110.27
 THIS SEEMS TO BE THE CASE, HOWEVER IT IS
 NOT CLEAR AT THIS TIME BY THE SPECS AND
 RISER SUBMITTED.
  
 5) NOTE: PLEASE KNOW, IF USING THE
 ONE-YEAR FPL USEAGE FOR SIZING THE GEN,
 THEN THIS SHALL CONTAIN A STATEMENT FROM
 THE RESPONSIBLE DESIGNER WHICH STATED
 THE AVG OVERALL KW USAGE AND THE RATING
 FOR NEW GEN WITH THE PRINTED NAME AND
 SIGNATURE ON THE LOAD SHEETS PROVIDED
 FROM FPL.
  
 6) NOTE: PLEASE SEE PLUMB REVIEW
 COMMENTS AS THE VALUE STATED ON
 APPLIACTION SHALL INCLUDE ALL LABOR AND
 MATERIALS WHICH OULD INCLUDE THE COST OF
 THE PROPOSED TANKS.
 FBC 108.3 ADMINISTRATIVE SECTION AS
 ADOPTED BY THE CITY OF WEST PALM BEACH.
  
 ** PLEASE SEE FIRE REVIEW COMMENTS AS
 THESE MAY HAVE AN AFFECT ON
 DESIGN/INSTALLATION.
  
  
 ** PLEASE KNOW, THIS ADDRESS IS NOT
 LOCATED IN A FLOOD ZONE. AN ELEVATION
 CERTIFICATE WILL NOT BE REQUIRED BEFORE
 FINAL.
  
 PLEASE SUBMIT THE ABOVE CORRECTIONS AND
 INFORMATION FOR REVIEW. IF THERE ARE ANY
 QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-09-11 Cont ID  
Sent By mawillia Date 2006-09-11 Time 11:55 Rev Time 0.00
Received By mawillia Date 2006-09-11 Time 11:55 Sent To  
Notes
2006-09-11 00:00:00*****APPROVED*****
  
  
  
  
  
  
 NOTES/CONCERNS OF 06/19/2006'S FIRE PLAN
 REVIEW HAVE BEEN ADDRESSED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-06-19 Cont ID  
Sent By mcarsill Date 2006-06-19 Time 10:40 Rev Time 0.00
Received By mcarsill Date 2006-06-19 Time 10:34 Sent To  
Notes
2006-06-19 00:00:001. PLEASE SPECIY CATEGORY OF GENERATOR
 USE PER NFPA 110.
  
 2. SURVEY AND EQUIPMENT LAYOUT IS
 DIFFICULT TO FOLLOW DUE TO SIZE AND HAND
 NOTED APPLIED TO THE DRAWING. PLEASE
 PROVIDE A MORE DETAILED ILLUSTRATION.
  
 3. ANOTHER PERMIT APPLICATION PROVIDED
 DISPLAYING PROPANE SUPPLY FOR THE
 GENERATOR. THE VALUE APPEARS TO BE TOO
 LOW FOR THE WORK BEING PROPOSED.
  
 4. PLEASE LOCATE EXIT DOORS AND ANY
 WINDOWS FOR THE ONE-STORY BUILDING SHOWN
 ON THE SURVEY.
  
 5. ALL ELECTRICAL WORK TO COMPLY WITH
 NFPA 70, THE NATIONAL ELECTRICAL CODE
 AND ALL ACCEPTED RECOGNIZED STANDARDS
 FOR ELECTRICAL WORK.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-08-12 Cont ID  
Sent By pschmitz Date 2006-08-12 Time 13:30 Rev Time 0.00
Received By pschmitz Date 2006-08-12 Time 13:38 Sent To  
Notes
2006-08-12 00:00:00PERMIT VALUE TO LOW.
 COPY OF CONTRACT REQUIRED TO GET CORRECT
 VALUE FOR PERMIT FEE.
 OK TO PRINT PERMIT WHEN VALUE HAS BEEN
 CORRECTED.PES

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-07-01 Cont ID  
Sent By pschmitz Date 2006-07-01 Time 09:39 Rev Time 0.00
Received By pschmitz Date 2006-07-01 Time 09:21 Sent To  
Notes
2006-07-01 00:00:00PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
 UNSAT
  
 PLEASE SEE COMMENTS FROM OTHER PLAN
 REVIWERS, BUILDING,ELECTRICAL,FIRE.
 WHICH MAY EFFECT THE GAS PLAN REVIEW.
  
 ESTIMATED VALUE.
 CLARITY OF PLANS.
 ENGINEER OF RECORD, SIGN AND SEAL.
 CURRENT GAS CODE: FBC 2004 FUEL GAS.
  
 END OF COMMENTS QUESTIONS 561-805-6692

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-07-31 Cont ID  
Sent By adarroug Date 2006-07-31 Time 16:13 Rev Time 0.00
Received By adarroug Date 2006-07-31 Time 16:13 Sent To  
Notes
2006-08-11 00:00:00TO "COMM" BD#12
2006-07-31 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-05-31 Cont ID  
Sent By adarroug Date 2006-05-31 Time 14:25 Rev Time 0.00
Received By adarroug Date 2006-05-31 Time 14:25 Sent To  
Notes
2006-06-01 00:00:00TO "COMM" BD#10
2006-05-31 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-01 Cont ID  
Sent By pschmitz Date 2006-07-01 Time 09:58 Rev Time 0.00
Received By pschmitz Date 2006-05-16 Time 09:32 Sent To  
Notes
2006-05-16 00:00:00TO "Z" BOX"N" ADDED PES
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-09-20 Cont ID  
Sent By tgordon Date 2006-09-20 Time 12:09 Rev Time 0.25
Received By tgordon Date 2006-09-20 Time 12:09 Sent To  
Notes
2006-09-20 00:00:00*** PROVISO ***
 1) PER 2004 FBC, FUEL GAS - POWERED
 EQUIPMENT - PERMANENTLY INSTALLED
 EQUIPMENT POWERED BY INTERNAL COMBUSTION
 ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AND NFPA 37.
  
 NFPA 37 INSTALLATION & USE OF STATIONARY
 COMBUSTION ENGINES & GAS TURBINES:
 4.1.4ENGINES (GENERATORS) LOCATED
 OUTDOORS SHALL BE MINIMUM OF 5 FT FROM
 OPENINGS IN WALLS & AT LEAST 5 FT FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS.A
 MINIMUM CLEARANCE IS NOT REQUIRED WHEN
 (1) THE ADJACENT WALL HAS A MINIMUM FIRE
 RESISTANCE RATING OF 1 HOUR OR (2) THE
 WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF
 NON-COMBUSTIBLE MATERIALS, AND IT HAS
 BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE.
 INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS
 SHOULD NOT TERMINATE UNDER STRUCTURES OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO
 THE VENTILATION INTAKES.
  
 2004 FMC 804.3.5 #3, WHERE THE
 TERMINATION IS LOCATED BELOW AN ADJACENT
 ROOF STRUCTURE, THE TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE
 ROOF STRUCTURE.
  
 PLEASE NOTE, WHILE ZONING ALLOWS
 MECHANICAL EQUIPMENT TO ENCROACH 4 FT
 INTO THE REQUIRED SETBACK, GENERATORS
 SHALL MAINTAIN THE REQUIRED ABOVE
 MENTIONED CLEARANCES TO THE ADJACENT
 PROPERTY STRUCTURES, I.E. FENCE,
 BUILDING, WINDOWS, DOORS, OR OPENINGS.
  
 FOLLOW MANUFACTURE'S RECOMMENDED
 CLEARANCES AROUND EQUIPMENT FOR
 SERVICING,AND PROVIDE MANUFACTURE'S
 INSTALLATION INSTRUCTIONS AT THE JOBSITE
 FOR THE FIELD INSPECTOR.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 2 Status P Date 2006-08-28 Cont ID  
Sent By kdfreema Date 2006-08-28 Time 09:22 Rev Time 0.00
Received By kdfreema Date 2006-08-28 Time 09:22 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2006-05-30 Cont ID  
Sent By mmclean Date 2006-05-30 Time 16:46 Rev Time 0.00
Received By mmclean Date 2006-05-30 Time 16:46 Sent To I
Notes
2006-05-30 00:00:00NOTE: THE PROPOSED GENERATOR IS 12FT
 FROM PROPERTY LINE.