Plan Review Details - Permit 06050541
Plan Review Stops For Permit 06050541
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-09-01 Cont ID  
Sent By shill Date 2006-09-01 Time 08:51 Rev Time 0.00
Received By shill Date 2006-09-01 Time 08:51 Sent To  
Notes
2006-09-01 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)THE PRODUCT APPROVALS ARE
 INCOMPLETE, TOP PART OF EACH SHEET IS
 CUT OFF.LEGIBLE PRODUCT APPROVALS ARE
 AVAILABLE AT WWW.MIAMIDADE.GOV (FIND A
 DEPT, BUILDING CODE COMPLIANCE)
  
 2.)WHEN RESUBMITTING, SUBMIT ONLY TWO
 COPIES OF PAPERWORK YOU ARE REVISING.
 OTHER PAPERWORK (EXTRA COPIES OF THE
 PRODUCT WHICH IS NOT CHANGING) IS
 UNNECESSARY.
  
 3.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED.IF A FLORIDA STATE
 PRODUCT APPROVAL IS NOT AVAILABLE,
 PLEASE ADVISE AND A LOCAL PRODUCT
 APPROVAL WILL BE ISSUED USING THE NOA.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-06-14 Cont ID  
Sent By shill Date 2006-06-14 Time 15:15 Rev Time 0.00
Received By shill Date 2006-06-14 Time 15:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-31 Cont ID  
Sent By shill Date 2006-05-31 Time 14:44 Rev Time 0.00
Received By shill Date 2006-05-31 Time 14:44 Sent To  
Notes
2006-05-31 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2004
  
 1.)CODE COMPLIANCE CANNOT BE
 DETERMINED DUE TO CONFLICTING
 INFORMATION IN THE PERMIT PACKAGE.
  
 YOU HAVE DECLARED WIND PRESSURES USING
 SOFTWARE; THESE PRESSURES APPEAR
 COMPLIANT.ON THE PRODUCT APPROVAL, YOU
 HAVE CIRCLED -31.2, WHICH IS TOO LOW FOR
 140MPH.
  
 YOU HAVE CIRCLED THE NUMBER -31.2 IN
 SEVERAL DIFFERENT PLACES, SHOWING TWO
 DIFFERENT EDGE DISTANCES AND TWO
 DIFFERENT FASTENERS.
  
 THE SPACING OF 12"/12" SPECIFIED ON THE
 SCHEDULE IS NOT COMPLIANT FOR ALL
 OPENINGS.SEE THE ANCHOR SPACING
 REQUIRED FOR -47.2.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-11 Cont ID  
Sent By adarroug Date 2006-08-11 Time 17:11 Rev Time 0.00
Received By adarroug Date 2006-08-11 Time 17:11 Sent To B
Notes
2006-08-11 00:00:00TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-08 Cont ID  
Sent By adarroug Date 2006-06-08 Time 16:35 Rev Time 0.00
Received By adarroug Date 2006-06-08 Time 16:35 Sent To B
Notes
2006-06-08 00:00:00TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-31 Cont ID  
Sent By shill Date 2006-05-31 Time 14:44 Rev Time 0.00
Received By shill Date 2006-05-15 Time 15:20 Sent To  
Notes
2006-05-15 00:00:00TO "MISC" BOX#1