Plan Review Details - Permit 06050526
Plan Review Stops For Permit 06050526
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-01-12 Cont ID  
Sent By lmartine Date 2007-01-12 Time 11:48 Rev Time 0.00
Received By lmartine Date 2007-01-12 Time 11:48 Sent To  
Notes
2007-01-12 11:49:00REVISION #2 OK LM

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-10-06 Cont ID  
Sent By amorse Date 2006-10-06 Time 14:22 Rev Time 0.00
Received By amorse Date 2006-10-06 Time 14:22 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-09-26 Cont ID  
Sent By amorse Date 2006-09-26 Time 15:50 Rev Time 0.00
Received By amorse Date 2006-09-26 Time 15:50 Sent To M
Notes
2006-09-26 00:00:00 
  
 DENIED
  
 1) NO PRODUCT APPROVALS WERE SUBMITTED
 FOR THE SECTIONAL GARAGE DOORS #'S 103,
 104 AND 106
  
 2) CECO SWINGING DOORS ARE HOLLOW METAL
 FOR #'S 100 AND 101 AND DRAWING STATES
 WOOD PLEASE CORRECT
  
 3) DRAWINGS SPECIFY IMPACT RESISTANT
 WINDOWS AND THE PRODUCT APPROVALS THAT
 ARE SUBMITTED ARE FOR NON IMPACT, PLEASE
 CORRECT (FLORIDA COVER IS THE SAME)
  
 4) PROVIDE TYPE OF ROOF COVERING AND
 PRODUCT APPROVAL FOR BREEZEWAY
  
 5) ONLY ONE COPY OF ROOFING PRODUCT
 APPROVAL WAS SUBMITTED. PLEASE CONFIRM
 THIS TYPE OF ROOF COVERING IS TO BE USED
 AS IT IS FASTENED THROUGH THE MEMBRANE
 AND INSULATION INTO DECK. THE RAS 117
 CALCULATIONS DO NOT MEET THE REQUIRED
 AMOUNT OF FASTENERS (SEE PAGE 5 OF NOA)
 FASTENERS AND PLATES ARE MECHANICALLY
 ATTACHED SPACED AT 6" ON CENTER TO MEET
 THE -45 PSF
  
 6) PLEASE REMOVE ANY ROOM DESIGNATIONS
 AND WALLS FROM DRAWINGS AS THE CITY CODE
 STATES THAT THE GARAGE FLOOR IS EXEMPT
 FROM BEING 6" ABOVE FLOOD ELEVATION WHEN
 ITS SOLE USE IS FOR VEHICLE PARKING
  
 7) PLEASE REMOVE ALL NON USED PRODUCT
 APPROVALS FROM THE SUBMITTAL. ONLY RE
 SUBMIT 2 COMPLETE SETS OF PRODUCT
 APPROVALS AND DRAWINGS ALONG WITH THE
 OLD PAGES THAT ARE CHANGED AND THE OLD
 PAGES WITH THE IMPACT FEE STAMPS
  
 8) PER 713.13(2) F.S.
 IF THE IMPROVEMENT DESCRIBED IN THE NOC
 HAS NOT COMMENCED WITHIN 90 DAYS OF
 RECORDING THE NOTICE IS VOID
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-06-28 Cont ID  
Sent By amorse Date 2006-06-28 Time 15:06 Rev Time 2.00
Received By amorse Date 2006-06-28 Time 15:06 Sent To PC
Notes
2006-06-28 00:00:00 
  
 DENIED
  
 1) A CERTIFICATE OF AUTHORIZATION SHALL
 BE REQUIRED FOR A CORPORATION, LIMITED
 LIABILITY COMPANY, OR PARTNERSHIP,
 OFFERING ARCHITECTURAL SERVICES TO THE
 PUBLIC JOINTLY OR SEPARATELY.
 PER 481.219(2) F.S.
  
 2) WIND DESIGN CRITERIA SHALL CARRY
 RVISED REFERENCE STANDARD 7-02
  
 3) THE STATE OF FLORIDA REQUIRES
 COLLECTION OF A RADON SURCHARGE ON ALL
 NEW CONSTRUCTION COMPUTED ON UNDER ROOF
 FLOOR SPACE PER 10D-91 FAC
  
 4) THE SURVEY FOR THE PROPOSED ADDITION
 SHOWS THE NGVD BASE FLOOD ELEVATION AS
 7' THE CITY CODE REQUIRES THE FLOOR
 ELEVATION TO BE 6" ABOVE THIS LEVEL. PER
 CITY CODES THE EXISTING STRUCTURE MUST
 ALSO MEET THIS REQUIREMENT WHEN THEIR IS
 SUBSTANTIAL IMPROVEMENT (MORE THAN 50%
 OF THE VALUE OF THE EXISTING STRUCTURE.)
 SECTION 94-546
  
 5) BEFORE A CO IS ISSUED AN ELEVATION
 CERTIFICATE WILL BE REQUIRED
  
 6) IN AREAS OF QUESTIONABLE SOILS A SOIL
 REPORT IS REQUIRED PER R401.1 FBC
  
 7) THE FOLLOWING CORRECTION ARE REQUIRED
 ON THE PRODUCT APPROVALS
 A) GAF ROOFING: PROVIDE FASTENER SYSTEM
 BEING USED AND CALCULATIONS FOR THE
 ENHANCED FASTENING FOR PERIMITER ZONE 2
 AND CORNER ZONE 3
 B) CLOPAY GARAGE DOORS: NOA'S DO NOT
 MEET THE DESIGN PRESSURES AS STATED IN
 THE ENGINEERED DRAWINGS ON S/3. ALSO
 BOTH NOA'S ARE FOR METAL DOORS AND
 DRAWINGS HAVE WOOD AND ALUMINUM. DOORS
 WITH GLAZING THE GLASS SHALL BE IMPACT
 RATED
 C) MADDEN MFG: SHUTTER PRODUCT APPROVALS
 SHALL BE SUBMITTED WITH A KEY PLAN,
 SCEDULE AND THE NOA DRAWING CLEARLY
 MARKED/CIRCLED SHOWING THE COMPONENTS,
 TYPE OF MOUNTING, TYPE OF ANCHOR, ETC
 D) PGT WINDOWS: REQUIRE AN UPDATED
 FLORIDA COVER AND NOA (FL#243-R3 & NOA#
 03-1105.01)
 E) CECO DOORS: NOA STATES A MAXIMUM
 HEIGHT OF 7'-0" AND DRAWING SPECIFY
 7'-6" ON THE DOOR AND WINDOW SCHEDULE ON
 A/1.
  
 8) WINDOW SCHEDULE SHOWS WINDOW A AS
 CASEMENT, ELEVATION SHOWS FIXED, NO NOA
 FOR CASEMENT, PLEASE CLARIFY
  
 9) SECTION 05/S1 SHOWS TB2 AND ROOF
 FRAMING PLAN SHOWS TB1 PLEASE CLARIFY,
 ALSO THERE IS NO TB2 ON THE BEAM
 SCHEDULE ON S/2
  
 10) PROVIDE DETAIL ON ATTACHMENT OF 4X10
 BEAM TO POST (ASSUME THERE IS POST UNDER
 THE DECORATIVE WOOD POSTS) IF SO SHOW
 PAD/FOOTING AND ATTACHMENT
  
 11) ALSO CONFIRM WITH THE ENGINEER THAT
 THE SPANS ON 4X10 BEAMS WITH OUTLOOKERS
 WILL BE ADEQUATE AS THE UNSUPPORTED
 SPANS ARE LARGER THAN WOULD BE ALLOWABLE
 FOR BUILT UP BEAMS
  
 12) SCTION 02/S1 AND 03/S1 SEEM SIMILAR
 BUT BEAM ATTACHMENT DETAIL SHOULD BE
 DIFFERENT AT EXISTING GARAGE WALL,
 PLEASE CLARIFY
  
 13) WEST ELEVATION ON A/2 STATES
 DIFFERENT ROOFING APPLICATION THAN NORTH
 ELEVATION AND BUILDING SECTIONS ON A/3
 PLEASE CLARIFY
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-09-22 Cont ID  
Sent By btrobaug Date 2006-09-22 Time 14:22 Rev Time 0.50
Received By btrobaug Date 2006-09-22 Time 13:18 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-06-08 Cont ID  
Sent By btrobaug Date 2006-06-08 Time 13:24 Rev Time 0.50
Received By btrobaug Date 2006-06-08 Time 12:09 Sent To P
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2007-01-02 Cont ID  
Sent By jleech Date 2007-01-02 Time 12:20 Rev Time 0.00
Received By jleech Date 2007-01-02 Time 12:20 Sent To P
Notes
2007-01-02 12:22:44REVISION DELETED TANKLESS GAS HEATERS. TO RELOCATE OLD
 GAS HEATERS.

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-09-23 Cont ID  
Sent By jleech Date 2006-09-23 Time 07:04 Rev Time 0.00
Received By jleech Date 2006-09-23 Time 07:04 Sent To P
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-06-13 Cont ID  
Sent By jleech Date 2006-06-13 Time 13:44 Rev Time 0.00
Received By jleech Date 2006-06-13 Time 13:44 Sent To B
Notes
2006-06-13 00:00:00DENIED;
  
 1. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). INCLUDE
 EXISTING GAS APPLIANCES AND THE LONGEST
 RUN. NEW HEATERS AND DRYER WILL BE ADDED
 TO OLD SYSTEM.
 2. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 3. SUBMIT MANUFACTURE SHEETS FOR WATER
 HEATERSTO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. MOST
 INST. HOT HEATERS ARE AROUND 200,000
 BTU'S.
 4. UNDER GROUND GAS PIPE TO BE (PE)
 POLYETHYLENE PLASTIC PIPE.
 GAS PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-12-26 Cont ID  
Sent By adarroug Date 2006-12-26 Time 11:50 Rev Time 0.00
Received By adarroug Date 2006-12-26 Time 11:50 Sent To M
Notes
2006-12-26 11:51:16TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-10-04 Cont ID  
Sent By adarroug Date 2006-10-04 Time 16:22 Rev Time 0.00
Received By adarroug Date 2006-10-04 Time 16:22 Sent To P
Notes
2006-10-04 00:00:00TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-09-19 Cont ID  
Sent By adarroug Date 2006-09-19 Time 14:52 Rev Time 0.00
Received By adarroug Date 2006-09-19 Time 14:52 Sent To E
Notes
2006-09-19 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-09-15 Cont ID  
Sent By adarroug Date 2006-09-15 Time 08:25 Rev Time 0.00
Received By adarroug Date 2006-09-15 Time 08:25 Sent To Z
Notes
2006-09-15 00:00:00TO "Z" BOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-18 Cont ID  
Sent By adarroug Date 2006-08-18 Time 14:48 Rev Time 0.00
Received By adarroug Date 2006-08-18 Time 14:48 Sent To Z
Notes
2006-08-18 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-06 Cont ID  
Sent By adarroug Date 2006-06-06 Time 12:25 Rev Time 0.00
Received By adarroug Date 2006-06-06 Time 12:25 Sent To E
Notes
2006-06-06 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-06-28 Time   Rev Time 0.00
Received By adarroug Date 2006-05-15 Time 15:17 Sent To  
Notes
2006-05-15 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2006-09-27 Cont ID  
Sent By tgordon Date 2006-09-27 Time 09:39 Rev Time 0.20
Received By tgordon Date 2006-09-27 Time 09:39 Sent To  
Notes
2006-09-27 00:00:00NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-06-14 Cont ID  
Sent By tgordon Date 2006-06-14 Time 08:55 Rev Time 0.30
Received By tgordon Date 2006-06-14 Time 08:55 Sent To B
Notes
2006-06-14 00:00:00*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE ON
 FORM 600A-04 (2004) PER FBC 13-600.3.A .
  
 2) ENERGY CAL'S. NEED TO BE SIGNED BY
 OWNER/AGENT, PER 2004 FBC 13-600.3.ABC.2
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-01-02 Cont ID  
Sent By jleech Date 2007-01-02 Time 12:23 Rev Time 0.00
Received By jleech Date 2007-01-02 Time 12:22 Sent To B
Notes
2007-01-02 12:24:32CHANGED LOCATION OF WASHER AND DRYER. REVISION

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-10-06 Cont ID  
Sent By jleech Date 2006-10-06 Time 14:56 Rev Time 0.00
Received By jleech Date 2006-10-06 Time 14:56 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-09-23 Cont ID  
Sent By jleech Date 2006-09-23 Time 07:06 Rev Time 0.00
Received By jleech Date 2006-09-23 Time 07:06 Sent To M
Notes
2006-09-23 00:00:00DENIED;
 1.THE AUTOMATIC CLOTHES WASHER THAT IS
 TO BE REMOVED MUST BE RELOCATED IN THE
 HOUSE. MINIMUM REQUIRED PLUMBING
 FIXTURES REQUIRES A WASHER HOOK UP. SEE
 FBC-2004 PLUMBING TABLE 403.1(7)R-3.
 WASHER IS NOT SHOWN ON ELECTRICAL PANEL
 SCHEDULE.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-06-13 Cont ID  
Sent By jleech Date 2006-06-13 Time 13:36 Rev Time 0.00
Received By jleech Date 2006-06-13 Time 13:36 Sent To G
Notes
2006-06-13 00:00:00DENIED;
 1.THE AUTOMATIC CLOTHES WASHER FIXTURE
 DRAIN SHALL CONNECT TO A BRANCH DRAIN OR
 DRANAGE STACK A MINIMUM OF 3" IN
 DIAMETER. FHC-2004 PLUMBING SEC.406.3.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 3 Status P Date 2006-10-06 Cont ID  
Sent By lmartine Date 2006-10-06 Time 16:44 Rev Time 0.00
Received By lmartine Date 2006-09-15 Time 17:56 Sent To  
Notes
2006-10-06 00:00:00SEE MICHELLE'S APPROVAL ON PLANSLM

Review Stop Z ZONING
Rev No 2 Status F Date 2006-08-21 Cont ID  
Sent By mmclean Date 2006-08-21 Time 18:57 Rev Time 0.00
Received By mmclean Date 2006-08-21 Time 18:57 Sent To  
Notes
2006-08-21 00:00:00DENIED,
 1. THE PROPOSED ACCESSORY STRUCTURE IS
 OVER THE ZONING REQUIREMENTS OF 1000SQ
 FT INCLUDING THE EXISTING GARAGE. SEC
 94-304 (B)(1)
  
 2. APPLICANT MAY APPLY FOR A VARIANCE
 FOR EXCEEDING THE SQUARE FOOTAGE
 REQUIREMNTS.
 3. APPLICANT MAY ATTACH TO EXISTING
 STRUCTURE AND PROPOSED TO THE EXISTING
 MAIN STRUCTURE.THIS CAN BE ATTACHED
 WITH A SOLID ROOF BREEZEWAY AND MUST
 MEET THE SETBACKS FOR SF7 (FRONT SETBACK
 15FT, SIDE(BOTH SIDE TOTALLY 15FT) AND
 REAR SETBACK 10% LOT DEPTH OR 15FT
 WHICHEVER IS LESS.
 4. SITEPLAN DOES NOT SHOW THE LOCATION
 OF THE PROPOSED A/C UNIT
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2006-06-05 Cont ID  
Sent By mmclean Date 2006-06-05 Time 15:51 Rev Time 0.00
Received By mmclean Date 2006-06-05 Time 15:51 Sent To  
Notes
2006-06-05 00:00:00DENIED,
 1. MUST PROVIDE THE FRONT SETBACK OF THE
 PROPOSED TWO CAR GARAGE ON THE TWO SET
 OF SITEPLANS CLEARLY (NOT CLEARLY SHOWN
 ON THE SITEPLAN)
 2. THE NEW A/C MUST BE SHOWN ON THE TWO
 SET OF SITEPLANS WITH THE SETBACK ON THE
 SIDE (FROM A/C TO PROPERTY LINE)
  
 NOTE: SEC 94-303 MECHANICAL/POOL
 EQUIPMENT/GENERATOR MAY NOT PROJECT MORE
 THAN FOUR FEET INTO A SETBACK.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720
  