Plan Review Details - Permit 06050519
Plan Review Stops For Permit 06050519
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-08-10 Cont ID  
Sent By mjacobs Date 2006-08-10 Time 08:56 Rev Time 0.00
Received By mjacobs Date 2006-08-10 Time 07:36 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-06-15 Cont ID  
Sent By mjacobs Date 2006-06-15 Time 08:57 Rev Time 0.00
Received By mjacobs Date 2006-06-15 Time 07:26 Sent To PC
Notes
2006-06-15 00:00:00 
 1) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 2) THE CLAIMED VALUATION ON THE PERMIT
 APPLICATION IS LOW. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT
 COST EXCLUDING LAND VALUE. OUR VALUATION
 REFERENCE IS ICC (BVD), MARSHALL-SWIFT
 AND MEANS COST ANALYSIS SERVICES PER FBC
 108.3*
 ADJUST THE VALUE TO A FAIR MARKET VALUE
 OR WILL USING THE MARSHALL-SWIFT VALUES
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-08-23 Cont ID  
Sent By btrobaug Date 2006-08-23 Time 17:51 Rev Time 0.50
Received By btrobaug Date 2006-08-23 Time 17:05 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-08-02 Cont ID  
Sent By btrobaug Date 2006-08-02 Time 11:19 Rev Time 0.33
Received By btrobaug Date 2006-08-02 Time 11:00 Sent To P
Notes
2006-08-02 00:00:00NONCOMPLIANT
  
  
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 PLEASE SUBMIT DETAILS FOR THE PANEL
 SHOWN ON THE SCHEMATIC, FEEDER AND CONDU
 IT SIZE AND TYPE, PANEL RATING AND OCP,
 PANEL SCHEDULE AND COMPUTED LOAD, ETC.
 IF THE PANEL IS EXISTING, THE ENGINEER
 NEEDS TO INDICATE SAME ON PLAN.215.5 NEC
 2002.
  
 THE RISER SUBMITTED FOR THE SECOND
 REVIEW DOES NOT INDICATE WHERE THE POOL
 FEED FROM THE MAIN PANEL TERMINATES.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-02 Cont ID  
Sent By btrobaug Date 2006-06-02 Time 11:14 Rev Time 0.50
Received By btrobaug Date 2006-06-02 Time 11:02 Sent To P
Notes
2006-06-02 00:00:00 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 PLEASE SUBMIT DETAILS FOR THE PANEL
 SHOWN ON THE SCHEMATIC, FEEDER AND CONDU
 IT SIZE AND TYPE, PANEL RATING AND OCP,
 PANEL SCHEDULE AND COMPUTED LOAD, ETC.
 IF THE PANEL IS EXISTING, THE ENGINEER
 NEEDS TO INDICATE SAME ON PLAN.215.5 NEC
 2002.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-06-05 Cont ID  
Sent By mperson Date 2006-06-05 Time 14:48 Rev Time 0.00
Received By mperson Date 2006-06-05 Time 14:48 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-08-22 Cont ID  
Sent By adarroug Date 2006-08-22 Time 14:59 Rev Time 0.00
Received By adarroug Date 2006-08-22 Time 14:59 Sent To E
Notes
2006-08-22 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-08-12 Cont ID  
Sent By adarroug Date 2006-08-12 Time 13:24 Rev Time 0.00
Received By adarroug Date 2006-08-12 Time 13:24 Sent To Z
Notes
2006-08-12 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-08-01 Cont ID  
Sent By adarroug Date 2006-08-01 Time 18:13 Rev Time 0.00
Received By adarroug Date 2006-08-01 Time 18:13 Sent To E
Notes
2006-08-01 00:00:00SENT TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-07-25 Cont ID  
Sent By adarroug Date 2006-07-25 Time 09:58 Rev Time 0.00
Received By adarroug Date 2006-07-25 Time 09:58 Sent To E
Notes
2006-07-25 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-05-31 Cont ID  
Sent By adarroug Date 2006-05-31 Time 14:50 Rev Time 0.00
Received By adarroug Date 2006-05-31 Time 14:50 Sent To E
Notes
2006-05-31 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-06-15 Time   Rev Time 0.00
Received By adarroug Date 2006-05-15 Time 09:39 Sent To  
Notes
2006-05-15 00:00:00TO "Z" BOX

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-02-08 Cont ID  
Sent By pschmitz Date 2007-02-08 Time 10:42 Rev Time 0.00
Received By pschmitz Date 2007-02-08 Time 10:42 Sent To  
Notes
2007-02-08 10:44:47LETTER FROM ENGINEE, VERIFING PSI TEST OF 35 PSI ON
 MAIN DRAIN

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-08-09 Cont ID  
Sent By mperson Date 2006-08-09 Time 14:28 Rev Time 0.33
Received By mperson Date 2006-08-09 Time 14:28 Sent To B
Notes
2006-08-09 00:00:00RESUBMITTAL: NEW SHEETS

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-06-05 Cont ID  
Sent By mperson Date 2006-06-05 Time 14:44 Rev Time 0.45
Received By mperson Date 2006-06-05 Time 14:44 Sent To G
Notes
2006-06-05 00:00:00 
  
 ******PROVISO******
 1) FBC-2004 SEC. 424.2.6.6.5, OR
 FBCR-2004 SEC. R4101.6.6.5 WHERE
 PROVIDED, THE VACUUM OR PRESSURE CLEANER
 FITTING SHALL BE LOCATED AT LEAST 6" AND
 NOT GREATER THAN 12" BELOW THE MINIMUM
 OPER- ATING WATER LEVEL OR AS AN
 ATTACHMENT TO THE SKIMMER.(MANUFACTURER
 CUT SHEETS REQUIRED, OR ADD MAKE AND
 MODEL NUMBER TO PLANS)

Review Stop Z ZONING
Rev No 2 Status P Date 2006-07-30 Cont ID  
Sent By mmclean Date 2006-07-30 Time 06:46 Rev Time 0.00
Received By mmclean Date 2006-07-30 Time 06:45 Sent To I
Notes
2006-08-19 00:00:00NOTE:
 THE PROPOSED POOL EQUIPMENT SHALL NOT BE
 CLOSER THAN 1FT FROM REAR PROPERTY LINE.
  
 NOTE: THE PROPOSED POOL SHALL BE 5FT
 FROM THE SIDE & 5.6FT IN THE REAR. THE
 PROPOSED DECK SHALL BE 3FT ON THE SIDE.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-05-30 Cont ID  
Sent By mmclean Date 2006-05-30 Time 15:55 Rev Time 0.00
Received By mmclean Date 2006-05-30 Time 15:55 Sent To I
Notes
2006-05-30 00:00:00DENIED,
 1. THE PROPOSED POOL MUST BE 5FT ON THE
 ZERO SIDE. (SURVEY SHOWS 4FT)
 2. THE PROPOSED DECK MUST BE 2FT ON THE
 ZERO SIDE, (THE SURVEY SHOWS NO SETBACK
 FOR PROPERTY LINE)
 3. MUST PROVIDE THE DISTANCE OF THE POOL
 EQUIP FROM REAR PROPERTY LINE & SIDE
 PROPERTY LINE.
  
 NOTE: THE POOL EQUIP. CAN ONLY ENCROACH
 4FT INTO A SETBACK AND CANNOT ENROACH ON
 THE PROPERTY LINE.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720